Fuel tank of diesel generator set is divided into base bottom fuel tank and external fuel tank. In generally, base bottom fuel tank capacity is continuous operation for 8 hours. Today Starlight Power will introduce fuel tank of generator set. 1.Calculation of fuel tank capacity The open type generator set below 500KW can be equipped with base bottom fuel tank as clients’ requirements. But our silent type generator set has base bottom fuel tank itself. The capacity of base bottom fuel tank depends on power capacity of generator set and its fuel consumption. For example, 500kw Cummins diesel generator set, its fuel consumption is about 209g/KW.h. Then we should know how many liters per hour: (0.209/0.85)x500KW=123L/h, then fuel tank capacity of 8 hours will be 123L/h x 8=984L. The simplest calculation method is to multiply the power (kw) of diesel generator set by 2.1, and the figure is approximately equal to the fuel consumption in eight hours. 2.Advant...