Diesel generator set is a common emergency power supply in civil buildings, the proper selection of diesel generator set is an important problem in the electrical design of civil buildings. So when we choose self-contained diesel generator set, how to select a suitable capacity according to the load? 1.Setting principle. Class I high-rise buildings shall be supplied power according to class I load requirements. Class II high-rise buildings shall be supplied power according to class II load requirements. Article 3.1 of code for electrical design of civil buildings (JGJ / t16-92): The primary load shall be supplied by two power sources, when one power supply fails, the other power supply should not be damaged at the same time; When the secondary load conditions permit, two-way power supply should also be used for power supply, especially the secondary load for fire protection, the power supply shall meet the requirements of two return circuits. For the particularly importan...