When install CCEC Cummins engine and diesel generator, all installation systems must meet the requirement, otherwise they will not be able to work normally, even cause serious faults. In this article, Starlight mainly talks about installation and use of CCEC Cummins engine and generator. 1.The design of machine room 2.Ventilation system The machine room should be well ventilated. A.Closed cooling mode of fan water radiator: Fan radiator units have been installed in a complete set, users do not need to install additional cooling devices; B.The air inlet area of generator room is 1.0 to 1.5 times of the front area of the radiator, and the air outlet area is 1.0 to 1.5 times of the front area of the radiator. If the ventilator is equipped with shutters or grids, the area of the air outlet should also be increased; C.If there is window shades on exhaust duct which to adjust indoor temperature, when indoor temperature, when indoor temperature is higher than 1...