Engine Connection and Parameter Setting Volvo Connection and Parameter Setting TD/TAD420VE, TD/TAD520GE, TAD520VE, TAD530GE, TAD531GE, TAD532GE, TAD620VE, TD720GE, TAD720GE, TAD720VE, TAD721GE/VE, TAD722GE/VE, TAD730/731/732/733GE Connection Control unit The control unit must be installed separately from the engine. Control unit working temperature must be between - 40 ° C to +85 ° C. Accelerator pedal (VE engines) Idling: 0-5 V (standard value 0.3 V) Full throttle: 0-5 V (default value 4.6 V) A fault code is generated when the voltage is: U > 4.9 V (standard value) U < 0.1 V (standard value) Engine speed potentiometer/external voltage input (GE engines) Rotary potentiometer for fine adjustment of Volvo engine speed (GE engines) On 1500 rpm or 1800 rpm GE engines, the Volvo engine speed can be finely adjusted ± 5 %. A fault code is generated when the voltage is: U > 4.8 V (standard value) U < 0.2 V ...