Guides to Check Volvo Engine Before Starting



Starting



Make it a habit of giving the engine and engine room a visual check before starting. This will help you to discover quickly if anything abnormal has happened, or is about to happen. Also check that instruments and warning displays show normal values after you have started the engine.

WARNING!
Never use start spray or similar agents to start an engine. This may cause an explosion in the inlet manifold. Danger of personal injury.

Before Starting



Check that the oil level is between the MIN and MAX marks.

NOTICE! The oil level can be read both when the Volvo engine is stopped (the STOP side of the dipstick) and with the engine running (the OPERATING side of the dipstick).



For filling refer to Oil level, checking and topping up.



Open the fuel valves.

Check the fuel pre-filter; refer to Draining condensate, fuel system page 54.

Check the coolant level and that the radiator is not blocked externally. Refer to Coolant Level, Checking and Topping Up page 58 and Charge Air Cooler, External Cleaning page 59



WARNING!

Do not open the coolant filler cap when the engine is hot, except in emergencies, this could cause serious personal injury. Steam or hot fluid could spray out.

Check that no leakage of oil, fuel or coolant is present.

Turn the main switch(es) on.

Move the engine speed control to idle, and open the disengageable clutch/gearbox if installed.

IMPORTANT!

Never break the circuit with the main switch while the Volvo engine is running, as this may damage the alternator.





Starting the Engine



The pre-heating time is adjusted to suit the engine temperature, and can last for up to 50 seconds both before and after starting. The starter motor connection time is maximized to 20 seconds. After that, the starter motor circuit is temporarily cut to protect the starter motor against overheating.

Starting in Extreme Cold

Certain preparations must be made to enable engine starting in extreme cold, and in some cases to make starting possible at all:

Use a winter grade fuel (of a well-known make) that is approved for the prevailing temperature. This reduces the risk of paraffin wax precipitation in the fuel system. At extremely low temperatures, we recommend the use of a fuel heater.

Use a synthetic engine oil of a viscosity recommended for the prevailing temperature to achieve satisfactory lubrication. Refer to Viscosity page 70. Synthetic lubricants are able to handle a wider temperature range than mineralbased lubricants.

Pre-heat the coolant with a separately-installed electric engine heater. In extreme cases, a dieselfired engine heater may be necessary. Ask your Volvo Penta dealer for advice.

Make sure the cooling system is filled with a glycol mixture. Refer to Maintenance page 56.

The batteries must be in good condition. Cold weather reduces battery capacity. Increased battery capacity may be necessary.





Never Use Start Spray

WARNING!



Never use start spray or similar agents to start an engine. This may cause an explosion in the inlet manifold. Danger of personal injury.

Starting Using Auxiliary Batteries



WARNING!

Explosion hazard. Batteries contain and give off an explosive gas which is highly flammable and explosive. A short circuit, open flame or spark could cause a violent explosion. Ventilate well. 1 Check that the auxiliary batteries are connected (series or parallel) so that the rated voltage corresponds to the engine system voltage.

2 First connect the red (+) jumper cable to the auxiliary battery, then to the flat battery. Then connect the black (-) jumper cable to the auxiliary battery and to a location that is somewhere away from the discharged battery, e.g. the main switch negative terminal or the negative terminal on the starter motor. 3 Start the engine.



WARNING!

Do not touch the connections during the start attempt: Risk of arcing. Do not bend over any of the batteries either. 4 Remove the cables in the reverse order.



IMPORTANT!

The ordinary cables to the standard batteries must not be loosened under any circumstances.





Operation

Correct operating technique is very important for both fuel economy and engine life. Always let the engine warm up to normal operating temperature before operating at full power. Avoid sudden throttle openings and operation at high engine rpm.



Reading the Instruments

Check all instruments directly after starting, and then regularly during operation.

NOTICE! On engines in continuous operation, the lubrication oil level must be checked at least every 24 hours. Refer to Oil level, checking and topping up.



Alarms

If the EMS receives abnormal signals from the engine, the control unit generates fault codes and alarms, in the form of lamps and audible warnings. This is done by means of CAN signals to the instrument. More information about fault codes and fault tracing can be found in the chapter. Fault Handling.







Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...