Volvo Penta Engine Maintenance Guides




Volvo Penta Engine Maintenance Guides


General inspection

Make it a habit to give the engine and engine compartment a visual inspection before starting the and after operation once the engine has stopped. This will help you to discover quickly if anything abnormal has happened, or is about to happen. Look especially carefully at oil, fuel and coolant leakage, loose bolts, worn or poorly tensioned drive belts, loose connections, damaged hoses and electrical cables. This inspection only takes a few minutes and can prevent serious malfunctions and expensive repairs.

WARNING!



Accumulations of fuel, oil and grease on the engine or in the engine room is a fire hazard and must be removed immediately they are detected.



WARNING!



If an oil, fuel or coolant leak is detected, the cause must be investigated and the fault rectified before the Volvo engine is started.

IMPORTANT!

Remember the following when washing with a power washer: Never aim the water jet at radiators, charge air cooler, seals, rubber hoses or electrical components.



Air Filter, Check and Change



The engine is equipped with electronic air filter indication. The control unit provides an output signal which is announced as a warning on the instrument panel. The warning indicates a pressure drop in the air filter, which must then be checked and possibly changed.

Scrap the old filter. No cleaning or re-use is permissible

In continuous operation, the filter should be checked every 8 hours. For operations in extremely dirty environments such as coal mines and rock crushing mills, special air filters must be used.

Charge Air Pipe, Leakage Check

Inspect the condition of the charge air hoses, hose union    s and clamps for cracks and other damage. Change as necessary.

IMPORTANT!

Clamps must be tightened using a torque wrench to 9 ±2 Nm (6.6 ±1.5 lbf.ft.).



Drive Belt and Alternator Belt,

Inspection



Inspections must be carried out after operations, while the belts are hot. You should be able to depress the alternator belt and the drive belt about 3-4 mm between the pulleys.



The alternator belts and drive belts have automatic belt tensioners and do not need to be adjusted. Check the condition of the drive belts. Replace as necessary; refer to Alternator Belt, Change page 51 and Drive Belt, Change page 50.



Drive Belt, Change

1 Disconnect the main switch(es) and check that the engine is not connected to system voltage.

2 Remove the fan guard and fan ring round the cooling fan.

3 Remove the belt guard.

4 Place a 1/2" square wrench in the belt tensioner (1). Lift the wrench and remove the drive belt.

5 Thread the drive belt round the fan and remove it.

6 Check that the pulleys are clean and undamaged.

7 Thread the new drive belt over the fan.

8 Lift the 1/2" wrench and install the new drive belt.

9 Install the belt guards.

10 Install the fan guard and fan ring round the cooling fan.

11 Start the Volvo engine and perform a function check.

Alternator Belt, Change



IMPORTANT!



Always replace a drive belt that seems worn or is cracked.



1 Disconnect the main switch(es) and check that the engine is not connected to system voltage.

2 Remove the fan guard and fan ring round the cooling fan.

3 Remove the belt guard.

4 Place a 1/2" square wrench in the belt tensioner (1). Lift the wrench up and lift the water pump drive belt off.

5 Place a 1/2" square wrench in the belt tensioner (2). Press the wrench down and remove the alternator belt.

6 Check that the pulleys are clean and undamaged.

7 Press the 1/2" wrench in the belt tensioner (2) down and install the new alternator drive belt.

8 Lift the 1/2" wrench in the belt tensioner (1) and reinstall the water pump drive belt.

9 Install the belt guards.

10 Install the fan guard and fan ring round the cooling fan.

11 Start the engine and perform a function check.


Lubrication System

Oil change intervals may vary according to the lubrication oil grade, fuel sulfur content and running conditions.

Refer to Technical data, Lubrication system.

The oil change interval may under certain conditions be increased. To see if the engine complies Volvo Penta oil analysis needs to be performed. Contact your Volvo Penta dealer for further information.
NOTICE! Oil change intervals must never exceed a period of 12 months.



Oil level, checking and topping up



The oil level must be inside the marked area on the dipstick and must be checked daily before the first start.

Top up with oil via the filler opening, please refer to Maintenance page 47. Check that the correct level has been achieved. If the engine is stationary, wait for a few minutes to allow the oil to run down into the oil pan.

The oil level can be read both when the engine is stationary (the STOP side of the dipstick) and with the engine running (the OPERATING side of the dipstick). Do not fill up above the maximum oillevel. Only use a recommended grade of oil, please refer to Technical Data page 69.

The oil level sensor only measures the oil level at the time when the ignition is turned on. In other words, not continually during operation.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...