Starting Procedure of Shangchai SC27G Diesel Engine




4.5.1 Normal starting procedure

The G series V type diesel engine can be started smoothly at temperature of -5°C and above. Starting procedure is as follows:
Disengage the diesel engine from the drive system. .
Put the mechanical operating devices into the 'running' position.
Push the governor controlling handle to unloaded position with speed at about 900 r/min.
Insert electric key and turn the switch from the OFF position to the START position to start the engine.if it cannot be started up in 10 seconds, turn the switch from the START position to the OFF position. Make another starting after 2 minutes. If the engine cannot be started up for three times, stop starting and refer to Section 6 for troubleshooting guideline to find cause. Each starting lasts 2 to 3 seconds.





Caution: The engine should be started without load.

After the engine has started up, the switch key goes back to the ON operation from the START position automatically. The oil pressure gauge should show reading within 15 seconds after the engine has started up; otherwise, stop the engine immediately to prevent damage to the engine and find the causes and remove the fault(s) according to Section 6 Troubleshooting Guidelines.
Having started up from a hot state, the engine should run at idle for l-3 minutes before being accelerated and loaded gradually. .
Having started up from a cold state, the engine should run at idle for 3-5 minutes. Increase engine speed slowly to 1,500 r/min and run the engine with partial load. Do not run the engine with full load until the outlet coolant temperature is higher than 75°C, oil temperature 50°C and oil pressure 0.40 MPa.

Caution: Especially starting the engine from a cold stat, increase the engine speed slowly as far as possible to have every bearing adequately lubricated and oil pressure stable.
Check the instruments during the engine running at idle to see whether they work normally.
Caution: Do not accelerate and load the engine immediately after it has been started up.
Caution: Do not idle the engine for a long period of time or it can cause problems to the engine. When an engine idles, the temperature in combustion chamber is low and combustion is not complete. It can cause carbon deposit in cylinder resulting in block of the orifices of fuel injector, as well as seizures of piston rings and valves, thus leading to engine performance deterioration.
Caution: If the engine is start by a jumper cable, parallel connection of the cable should be adopted by connecting the positive pole to the positive terminal and the negative pole to the negative terminal. If the engine is start by external power supply, the circuit breaker should be set to the OFF position. Take out the key to prevent accidental activation before connecting a jumper cable.

4.5.2 Cold Start

Cold start refers to starting the engine at temperature -50°C. Choose proper cold starting aid to warm the engine according to ambient temperature and then follow the normal starting procedures to start the engine. There are, in general, several ways to warm the engine:
Warming the engine oil and coolant to 40-50°C;
Installing a heating device in the air inlet pipe or heating air by fire at the entrance of the air inlet pipe, with which special precaution must be paid for safety;
Increasing the surrounding temperature of the engine room;
Using diesel fuel, engine oil and coolant that are suitable for cold areas;
Warming battery or using battery of larger capacity or having higher discharge rate (special battery for low temperature).

4.5.3 Staring after a longtime stop or replacement of lubricating oil

If the engine hasn't been used for less than 30 days or its engine oil has just been replaced, it is necessary to fill the lubricating system with oil. Crank the engine and make oil enter moving parts. Start the engine only after you feel light when cranking the engine. Finish the following preparation before starting the engine according to the procedures of normal starting or cold starting:
Check the oil level for being within the dipstick marks range.
Check the voltage of the battery for abnormality.
Prime the fuel system. Refer to Section 5.3 for operation.
In order to have a quick starting of a standby engine for emergency need, start the engine every three to five days and operate it until its engine oil and coolant temperatures reach 60'C and above.

4.6 Engine Operation

Cautions for operation of the engine:
Pay frequent attention to oil pressure and coolant temperature. In case of any abnormality, stop the engine immediately for inspection.
Lubricating oil pressure:
150 kPa @ idle speed (minimum allowable)
300 kPa @ rated speed (minimum allowable)
500 kPa @ rated speed (maximum allowable)
Coolant temperature:
75-95°C (normal working range)
When engine overheating starts to happen that is indicated by the coolant temperature alarming, reduce engine speed or load or take the both actions until the coolant temperature falls down into the normal range; otherwise, find the cause and remove the fault as per Section 6 Troubleshooting Guidelines.
During the operation, especially sudden decrease of load, attention should be paid to avoid the failure of the governor, which can cause sudden increase of engine speed exceeding the defined value (usually called flying away).
Once such case happens, make an emergency stop first and then check for the cause.
Caution: Over-speed running will cause serious damage to the engine.

There are significant signs before most engine faults occur, such as changes in performance, sound, or engine appearance. Listening and observing will help detect in advance or predict some problems of the engine that will occur later, with which the proper measures can be taken in time to eliminate such problems as can lead to a serious engine failure.
Typical engine fault signs:
Engine misrires
Engine vibrates abnormally
Engine sounds abnormal
Engine coolant temperature and oil pressure change abruptly
Engine produces black smoke
Engine power output is insufficient
Engine oil consumption is too much
Fuel consumption is too much
There is leakage of oil, fuel or/and coolant

4.7 Engine Shutdown

4.7.1 Normal shutdown
If the engine has just worked at a high speed and heavy load for a long time, reduce its load and speed gradually and run it at idle for 5 minutes before stopping it to let the engine cool down evenly and turbocharger speed fall considerably so as to protect the engine and turbocharger. Turn off the fuel tank cock after the engine has stopped.
If the engine will not be used for a period of time (6 months at most), keep it properly. Refer to Section 7 for engine storage.

4.7.2 Emergency shutdown

Under emergency or special condition, make an emergency stop to avoid serious engine failure. Manually pulling of the emergency stop handle can achieve an emergency shutdown.


Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz