Shangchai Diesel Engine Troubleshooting



Shangchai Diesel Engine Troubleshooting


(9) Coolant temperature too low



Fault feature


Possible cause

Correction



Low ambient temperature, low load.


Increase load to a proper degree.


The reading of water thermometer is not correct.


Regulate or replace the thermometer when required.


The thermostat does not work well or was damaged.


Replace the thermostat.

(10) Oil in coolant



Fault feature


Possible cause

Correction



Damage of the oil cooler core.

Replace the oil cooler core.


Fault of the cylinder head gasket.


Replace the gasket.

(11) Electrical system fault



Fault feature


Possible cause

Correction


Starting motor does not work.



(1) Poor contact of the connecting wires.

(2) Poor contact of the electromagnetic switch.

(3) Poor contact of the electric brush.

(4) Short-circuit of the starting motor.

(5) Poor electric charging or the capacity of battery too small.


Clean and tighten the terminals or joints.

Check the switch contactor and grind it by sandpaper.

Clean the surface of the reverser or replace the electric brush.

Locate and fix the short-circuit issue.

Replace the starting motor if required.

Charge the battery, or add more batteries with parallel connection.

Replace the battery if required.


The starting motor rotates but no engine starting takes places.


(1) Poor contact of the electric brush or terminal or sealing sleeve.

(2) Wear of the bearing sleeve.

(3) Partial short-circuit of magnetic field winding or electric field winding.

(4) Poor contact of the electromagnetic switch.

(5) Poor electric charging or the capacity of battery too small, and a big drop of starting motor circuit voltage.



Clean the surface and weld firm.

Make replacement if necessary.

Replace the bearing sleeve.

Locate the short-circuit and fix it out.

Check the switch contact and grind it by sandpaper.

Charge the battery and replace it if needed. Increase the wire cross section or decrease the wire length.



The starting motor gear collides with flywheel ring gear or the gear of the starting motor can not set back.


(1) The center of the starting motor is not parallel with that of flywheel ring gear.
(2) The switch contact of electro-magnetic switch fused together.



Install the starting motor again to make the two centers parallel.

Check the switch contact and grind it by sandpaper.


The starting motor keeps running when the starting button is released.


(1) The alternator belt is loose.

(2) Poor terminal contact of the alternator or/and battery.


Regulate it again.

Repair.


Alternator can not charge.


(1) The alternator belt is loose.

(2) Poor terminal contact of the alternator or and battery.

(3) Rotor failure (magnetic coil)


Adjust the belt to a proper tension.

Clean or tighten all terminals and connects of the alternator and battery, and replace wires and terminals and joints if required.

Change the rotor.


Too low alternator voltage or abnormal alternator charge.


(1) The drive belt is loose.

(2) Poor terminal contact of the alternator or/and battery.

(3) The voltage regulator of the alternator is damaged.

(4) Rotor failure (magnetic coil)

(5) Burn of the rectifier diode.


Adjust the belt to a proper tension.

Clean and tighten all the terminals and connects of the alternator and battery.

Replace wires and and terminals and joints if required.

Replace the voltage regulator.


Too big voltage of the alternator.


(1) Poor contact of the connector of the alternator or its voltage regulator.

(2) Fault of the alternator voltage regulator.


Tighten the all connectors.

Change the regulator.


Abnormal noise from the alternator.


(1) Abrasion or damage of the drive belt.

(2) The driver belt is loose.

(3) The centers of the drive belt and pulleys are not in alignment.

(4) Wear of the bushing.

(5) The armature or rotor bent.

(6) The alternator rectifier circuit is short.


Change the belt.

Adjust the belt to a proper tension.

Adjust and make them in alignment.

Change the alternator.

Change the alternator.

Change the alternator.


(12) Fuel injection pump fault



Fault feature


Possible cause

Correction


Fuel injection pump does not supply fuel.


(1) No fuel in the fuel tank.

(2) There is air in the fuel system.

(3) Block of the fuel filter or fuel pipes.

(4) Failure of the fuel transfer pump.

(5) Seizure of the plunger and barrel.

(6) Poor seal at the fuel delivery valve seats.


Add fuel in time.

Prime the fuel system, refer to Section 5.3 for the procedure.

Replace the fuel element and clean the low pressure fuel pipeline.

Replace the fuel transfer pump.

Let a professional serviceman check and repair the plunger and barrel assembly, and make replacement if necessary.

Let a professional serviceman check and repair the fuel delivery valve seats, and make replacement if necessary.



Uneven fuel supply.


(1) There is air in the fuel pipeline, resulting in inter-mitten fuel supply.

(2) Break of the delivery valve springs.

(3) Wear of the delivery valve-seats.

(4) Impurity leads to the seizure of plunger.

(5) Fuel inlet pressure too small.


Priming the fuel system and refer to Section 5.3 for the procedure.

Replace the fuel injection pump.

Let a professional serviceman replace the fuel delivery valve seats.

Let a professional serviceman clean the plunger and barrel assembly and make replacement if necessary.

Check the strainer of the inlet connector in the fuel transfer pump and the fuel filter for block. Clean and replace them if necessary. And maintain them according to the maintenance plan.


Insufficient fuel supply.


(1) Fuel leak at the delivery valve assembly.

(2) Block of fuel strainer on the fuel transfer pump or block of fuel filter.

(3) Wear of plunger and barrel assembly.


Let a professional serviceman check the delivery valve assembly, and replace the assembly when required.

Clean the strainer, replace the fuel filter.

Let a professional serviceman replace the plunger and barrel assembly.

We supply Shangchai diesel generator power range from 50KW to 1600KW, for more information, please contact us.



Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...