Generator Set Noise Source And Solution



Generator Set Noise Source And Solution

The noise of generator set is mainly comes from engine and generator. To reduce the noise of the generator set, it is necessary to control the noise source. This article will show you the detailed information about the genset noise source as well as the solution.

The main noise source of engine is as follows:

Induction noise
Exhaust noise
Combustion noise
Mechanical noise
Cooling fans noise

The main noise source of generator is as follows:

Ventilation noise

Electromagnetic noise

Mechanical noise

Main noise source of engine

1. Air intake and exhaust system noise is the most powerful noise source of the engine.

The main source of intake noise is as follows:

1) The pressure fluctuation of air in the intake pipe, which results in low frequency noise.

2) The air flows through the flow area of the intake valve at high speed, which results in high frequency eddy noise.

3) The noise of turbocharger compressor

4) The noise of scavenging pump for two-stroke diesel engine

The main source of exhaust noise is as follows:

1) The pressure fluctuation of exhaust gas in the exhaust pipe, which results in low and intermediate frequency noise.

2) High frequency eddy current noise at the flow area of exhaust valve.


2. Combustion noise

Combustion noise is the main noise source of internal combustion engine. The burning of combustible mixture in the cylinder causes a sharp change of gas pressure. The piston, cylinder liner, connecting rod, piston pin and crankshaft parts are subjected to impact load, which causes structural vibration and noise.


3. Mechanical noise

The main components to cause mechanical noise include piston, cylinder head, cylinder liner, cylinder block, connecting rod, piston pin, crankshaft, valve gear, drive gear and fuel injection pump, etc. Therefore, the design of these parts, manufacturing quality as well as the material selection have an important effect on the noise. The diesel engine stiffness, rotating speed, and movement clearance are the main factors to afftect the mechanical noise.

4. Cooling fan noise

It results from the sound of air being moved at high speed across the engine and through the radiator.


Main noise source of generator


1. Ventilation noise

It includes fan and other ventilation equipment as well as the gas weirl noise formed by rotor. Fan rotation makes cooling gas periodic fluctuation so as to produce the single frequency noise. Resonance of thin wall parts in wind path, or the pipingproduced due to unreasonable return circuit design.

2. Electromagnetic noise

The noise refers that due to the interaction of stator and rotor magnetic field in generator air gap, it produces radial force changing with time and space, causing stator core and engine base to vibration due to periodic deformation over time so as to produce noise.

3. Mechanical noise

The mechanical noise of generator includes the mechanical vibration noise (caused by centrifugal force that is produced by rotor mechanical unbalance), bearing ventilation noise, brush connector ring or commutator sliding contact noise, and the axial vibration noise of end cap excited by bearing vibration.


Noise Reduction Measures

There is no doubt that it will have certain effects on the surrounding environment and personnel if the working noise of the machine is too large. Therefore, some necessary noise reduction measures should be taken. In addition to reduce the noise of generator set itself, it is also important to carry out special design for generator room.


1. Room sound insulation

The room door and window should adopt fireproof sound insulation door and window. Besides, the sound insulation requirement of brick wall needs more than 40dB (a). On the other hand, it is also important to eliminate sound paths through cracks in doors or walls.

2. Air intake and exhaust

After dealing with room sound insualtion,  you should turn to solve the problem of ventilation and heat dissipation in the generator room. The air inlet shall be in the same line as the generator set and the air outlet. The air inlet shall be equipped with resistive chip muffler. Due to the air inlet pressure loss is within the allowable range, it can make the air flow in the room reach balance naturally, meanwhile, the effect of ventilation and heat dissipation is obvious.

3. Exhaust muffler

In general, generator set is always equipped with an exhaust muffler to limit exhaust noise from the machine. Exhaust silencer comes in a wide variety of types, it is usually divided into two types: chamber-type silencer and spiral type device. The chamber-type device tends to be more effective, but the spiral-type device is more compact and may provide sufficient attenuation for many equipments.

4. Sound absorption treatment

In the machine room, the five walls except for the ground can be used for sound absorption treatment. According to the frequency spectral characteristic of the generator set, the perforation board resonance sound absorption structure is adopted. In addition, acoustic insulation sound-absorbing materials are available for lining air ducts and covering walls and ceilings. Reducing noise at a wall covered in sound absorbing material can be very effective.

5. Air exchange in the room

Good sound insulation in the generator room will make there is no air convection in the machine room when the closed water-cooled generator set power off, the high temperature in the room cant be lowered in time. To solve the problem, you can adopt low noise axial flow fan and equip with a resistive chip muffler.

6. Cooling air attenuation

Inlet and outlet air attenuation baffles can help reduce the noise produced by the cooling air as it moves across the engine and through the radiator.

7. Unit vibration isolation

Before installing the generator set, users should strictly follow the relevant information provided by the manufacturer to carry out vibration isolation treatment so as to avoid the long-distance transmission of structural sound, which continuously radiate air noise in the propagation so that the factory noise level fail to reach standard. For the generator units that are required to deal with due to exceed standard, the vibration of the ground near the unit must be measured. If the vibration is obvious, the vibration isolation treatment of the generator set must be carried out first.




Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Silent Cummins 640kw Diesel Generating Sets

Technical data of 800KVA AC diesel generator set The DG Set is skid mounted, directly coupled with Cummins water cooled engine with built in shock absorber for anti vibration. The alternator is Stamford brand with brushless and self excited, with control panel and protection system complete set. Prime power: 640KW/800KVA Standby power:704KW/880KVA Rated voltage: 230/400V Rated current: 1152A Speed/frequency:1500rpm/50Hz ( or 1800rpm/60Hz) Power factory:0.8lag Size: open type genset: 4.2 x1.82x2.25m, silent genset: 6.5 x2.6 x2.78m Net wight: open type genset: 7800kg,   silent genset : 12000kg Technical Data of Diesel Engine Diesel engine brand/model: Chongqing Cummins/ KTA38-G2B( full new) Prime/standby power: 790KW/920KW 4 Stroke Cycle , 60° Vee , 12 Cylinder, Turbocharged &Aftercooled, 1500rpm, 50Hz, bore/stroke: 159/159mm. The Cummins diesel engine is equipped with electronic type governor, over speed shutdown devices to protect against runaway when electronic governor or con...

Guides to Clean VOLVO Diesel Generator Cooling System

VOLVO Engine Cooling System Volvo engine's internal cooling system makes sure the engine works at the right temperature. It is a closed system that must always be filled with a mixture of concentrated coolant and water in order to protect the engine against internal corrosion, cavitation and bursting due to freezing. Coolant of a suitable chemical composition must be used all year round. This also applies in areas where there is never any risk of freezing, to provide the engine of  diesel generator set   with full corrosion protection. The use of anti-corrosion agents alone is not permitted in Volvo Penta engines. Never use water alone as a substitute for coolant. The corrosion protection additives become less effective over time, which means that the coolant must be changed at regular intervals; refer to Maintenance Schedule. The cooling system must be flushed whenever the coolant is changed; Volvo Penta coolants have been prepared to work best ...