System Adjustments of Single Unit Governor


Panel Mounted Governor Control Adjustments

The panel mounted governor control has four potentiometers for making system adjustments. These components are mounted on the control which is located inside the engine instrument panel or generator control panel.

NOTE: When a two bearing generator or a single bearing generator with a flexible drive between the flex discs and shaft (eg. Kohler 4T10 generators. Models 230ROZ, 250 ROZ and 275ROZ) is installed, use a remote mounted control. If the engine is not stable after the gain adjustment is made, install a jumper wire between terminals A and B.

The gain control is a one-turn potentiometer. It is used to adjust the sensitivity of the governor. A clockwise rotation of the potentiometer dial will shorten the response time of the governor to load changes. Refer to the glossary for the gain drescription.

The droop control is a one-turn potentiometer. It is adjustable for zero % (isochronous) to five % speed droop. Counterclockwise rotation will decrease the speed droop.

The idle speed controi is a 20-turn potentiometer for adjusting the idle speed. A clockwise rotation will increase the idle speed.

The run speed control is a 20 turn potentiometer for setting the desired no-load governed speed. A clockwise rotation will increase the run speed.

An idle-run switch, located on the engine instrument panel, allows the selection of the idle or run mode.

Also located on the engine instrument panel is the Speed Adjust potentiometer which is used for fine speed ajustment after Run Speed, Droop, and Gain have been set.

The panel mounted governor control wiring.

Caution: Measure the voltage on the engine control circuit board terminal strip and not on the control terminal strip. If two terminals on the control terminal strip are shorted, it can damage the control unit.

Preliminary Adjustments

The idle speed potentiometer adjustment.

1. Turn the screw counterclockwise 20 turns.

2. Turn the screw clockwise 10 turns.

3. This will set the idle speed potentiometer to its mid position.

The run speed potentiometer adjustment.
This will set the run speed potentiometer to its mid position. (Firs and second points are same to idle speed.)
Turn the gain potentiometer adjustment to midposition or 50.

The droop potentiometer adjustment.

1. Turn the potentiometer fully counterclockwise for isochronous operation.
2. Turn the potentiometer to approximately 40 for 3 percent droop.
3. Turn the potentiometer to approximately 80 for 5  percent droop.
Adjust any remote speed potentiometers to the center of their adjustment range.

Governed Speed Adjustment

Place the idle-run switch on the engine instrument panel in the idle position.

NOTE: Open the main line circuit breaker while the engine is at idle.

Start the engine. Adjust the idle speed potentiometer the governor control until the engine i:s running at 600 to 650 RPM.
Adjust the run speed potentiometer on the governor control until the no load speed is correct.

NOTE: Close the main line circuit breaker.

Droop Adjustment Isochronous Operation

For isochronous operation, the droop potentiometer must be turned fully counterclockwise and will not require any further adjustment.

Gain Adjustment

Close the main line circuit breaker and apply approximately 1/4 of the rated load. Make sure the engine speed is constant.

If the engine speed is constant, turn the GAIN potentiometer clockwise slowly until the engine speed is not constant.


1. Slowly turn the potentiometer counterclockwise until a constant speed is achieved.

2. Turn the potentiometer counterclockwise an additional 1/2 division.
Fine Speed Adjustment

After the gain adjustment is made, the full load governed engine speed may require a minor adjustment to equal the desired speed (i.e. 60 Hz, 1800 RPM or 50 Hz, 1500 RPM). Use the SPEED ADJUST potentiometer on the engine instrument panel for fine speed adjustments of  less than ±100 RPM.

System Adjustment Remote Mounted Governor Control

Follow the panel mounted governor control instructions for setting the governed speed, idle, droop and gain on the remote mounted control. The wiring for the remote mounted control is shown.

Caution: Do not attach the battery negative to Terminal Number 11. The control circuitry will be damaged.

NOTE: When a two bearing generator or a single bearing generator with a flexible drive between the flexible drive between the flex discs and shaft (eg. Kohler 4T10 generators, Models 230ROZ, 250 ROZ and 275 ROZ) is used, install a jumper between terminals A and B. This jumper provides additional stability in the governor control. The oscillation frequency of the coupling between the engine and the generator can cause the governor control to react to this oscillation in addition to a change in engine speed.
Caution: Measure the voltage of the panel mounted governor control on the printed circuit board terminal strip. Do not measure the voltage on the control terminal strip.

Notes For Auto-Synchronizer

1. The "Gain Range" is changed by adding a jumper between Terminals 6 and 14.

No jumper 6 to 14: Auto-Synchronizer is set for fast responding engines.

With jumper 6 to 14: Auto-Synchronizer is set for slow responding engines.

2.

a. Closing a contact or jumpering 11 to 12 allows the Auto-Synchronizer to perform as a sync check relay only, with circuit breaker contact output but no control on the incoming generator.

b. Closing a contact between 12 to 13 allows the Auto-Synchronizer to perform as a speed matching unit. The speed and phase of the incoming generator are controlled and contact is closed to drive circuit breaker. Once the circuit breaker is closed, the contact between 12 and 13 should be opened.

c. Open contacts or no jumper 11 to 12 or 12 to 13 allows the Auto-Synchronizer to still sense any error but it does not provide any control or contact closures.

3. Phasing of voltage potential to the Auto-Syncrhonizer is necessary to keep each signal in its correct phase relationship. If the generator voltage is not the same as the voltage rating of the Auto-Synchronizer, step-down transformers are required. Correct phasing of the transformer leads is necessary. Step-down transformers require a nominal 10 VA/PHASE for the GEN. input to the Auto-Synchronizer and 7 VA/PHASE for the BUS input to the Auto-Synchronizer.

Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...