Generator Set Fan Belts And Crankcase Breather Maintenance


Generator Set Fan Belts And Crankcase Breather Maintenance

Any spare parts of engine is important for a diesel generator set. In this article, you will learn the maintenance procedures of Perkins 4000 Series diesel genset. The post mainly introduces the genset belt, fan bearings and crankcase breather related technical knowledge.

FAN BEARINGS AND BELTS

WARNING!! Disconnect batteries or any other means of starting.

Remove the mesh guard around the fan belts, grease the fan and jockey pulley bearings Fig.23 using high melting point lithium based grease (e.g. Shell Alvania R.A.)

Check the tension and condition of the fan belts. Using a spring balance and rule, or a belt tension indicator, check that the force compares with the kgf (lbf) values shown below for the correct belt deflection. See Fig.23.


Fan belts if worn, should be replaced as a complete, matching set. Individual belts should NOT be replaced.

To adjust slacken the jockey pulley pivot and adjuster bolts, and operate the jockey pulley lever.

Moving the jockey pulley lever outwards will tension the belts and inwards will slacken the belts.

The correct tension is obtained by measuring the deflection at the mid point between the fan pulley and the crankshaft pulley when the above force is applied.

To apply the force place a rule across the outside width of the belts and attach spring balance as shown Fig.23 pull on the spring balance until the required force is reached and measure the belt deflection.

Adjust the position of the jockey pulley lever until the force on the spring balance and the belt deflection agree with the figures given above.

When using a belt tension indicator position the indicator on top of a belt at the mid center distance and apply a force at right angles to the belt deflecting it to the point where the lower marker is level with the top of the adjacent belt. Read off the force value indicated by the top edge of the upper marker. Having set the tension on the belts, tighten the adjuster and pivot bolts. refit the fan belt guard.

NOTE: If the measured force falls within the values given,the drive should be satisfactory, if it is below the lower value under tensioning is indicated.

A new drive should be tensioned to the higher value to allow for the normal drop in tension during the running-in period. After the drive has been running for 30 minutes, the tension should be checked and re-adjusted to the higher value.

FAULT TRACING

a) Small cracks on V-Belt Side and Base

Generally caused by lack of belt tension but excessive heat and/or chemical fumes can also lead to similar failure.

b) V-Belt swelling and softening

Caused by excessive contamination by oil, certain cutting fluids or rubber solvents.

c) Whipping during running

Usually caused by incorrect tensioning principally on long center drives. If slightly higher (or lower) tension does not cure the problem there may be a critical vibration frequency in the system which requires re-design or a banded belt (2 belts banded together to make a W belt).
CRANKCASE BREATHING

WARNING!! Disconnect batteries or any other means of starting. When using compressed air or cleaning agents always wear eye protection, and protective gloves.

CRANKCASE BREATHER ON EARLIER ENGINES (RADIATOR COOLED)

The crankcase breather is mounted on the side of the radiator Fig.24 and is connected to an elbow mounted on the gearcase by a flexible pipe Fig.26.

CRANKCASE BREATHER ON EARLIER ENGINES (HEAT EXCHANGER COOLED)

The crankcase breather is mounted on the side of the thermostat housing Fig. 25 and is connected to a breather body mounted on the gearcase by a flexible extension pipe Fig.26.

Unscrew the breather by turning it anti-clockwise, wash thoroughly using a suitable cleaning agent, shake as dry as possible, finally blow dry with compressed air then screw the breather firmly back into position.

Key

(Fig.26)

1. Position of breather when engine is fitted with a radiator

2. Position of breather when engine is fitted with heat exchanger

3. Flexible pipe

4. Elbow

To clean the breather remove the top cover and withdraw the two wire mesh elements and wash thoroughly using a suitable cleaning agent, Shake as dry as possible, finally blow dry with an compressed air. Refit the elements into the breather body, and fit the top cover firmly.

NOTE: When replacing the cover check the sealing gasket of diesel generator is in good condition and the cover has located on its dowel.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...