Balance the Power Distribution of Parallel GenSet



Parallel connection of diesel generator sets should first meet the requirements of even power distribution. The even distribution of power includes both active power and reactive power. The so-called uniform distribution means that the active power and reactive power of each generator should be proportional to their rated power. There are clear requirements for the power distribution of parallel-operated generator sets in China, when the alternator sets are operated in parallel. When the load changes within the range of 20% to 100% of the total rated power, it should be able to operate stably, and its power distribution error should meet the following requirements.








1. The difference between the actual active power of each generator and the calculated value according to the rated power ratio shall not exceed ±10% of the rated active power of the generator when the rated power of the generator is the same; when the rated power of the generator is different, Should not exceed 110% of the maximum rated active power of the generator, ±20% of the rated active power of the minimum generator.

2. The difference between the actual reactive power of each generator and the calculated value according to the ratio of rated power of the generator not exceeding the maximum generator amount

If there is a large imbalance in power distribution, whether it is active power or reactive power, it will not only affect the efficiency and economy of the genset operation, but also cause the failure of the entire power station.

If the active power distribution of the parallel generator set is seriously unbalanced, when the total load power is large, it is often that one generator set is fully loaded or overloaded, and the other generator is still under light load, so that it cannot be fully utilized. The capacity of the genset is used to make the performance of the entire power station. The overload of the genset will not only bring harm to the diesel engine or the generator, but also cause the protection equipment to operate and affect the operation of the entire power station. Conversely, when the total load power is small, the imbalance of active power tends to cause active circulation between the generator sets, causing some generator set to switch to the motor state, which is also not allowed for diesel engines. When the genset has reverse power protection, the reverse power phenomenon will cause the reverse power to trip causing a malfunction.

For diesel power plans with frequent load changes and large variation, the above situation should be paid more attention. For example, in a diesel power station of a ships electric propulsion device, due to the uneven distribution of active load of the parallel generator, when the ship is sailing at full speed, the total load power is large, often overloading the heavy-duty generator, causing the switch then trips, causing a serious power failure. When the ship stops at the dock, the light load generator enters the reverse power state due to the small total load, causing the reverse power trip, which affects the reliability of the operation of the power station and even the entire ship. The above situation is sufficient to show that the even distribution of power between generators in parallel operation is not only a problem of economic operation of a generator, but also an important factor to ensure the reliability of power supply of the entire diesel engine power station.

The reactive power distribution is uneven, although it will not seriously affect the diesel engine, but the rated value of the generator power is determined according to the apparent power, and the reactive power imbalance will inevitably cause the unbalanced apparent power of the generator. It will limit the capacity of the generator set, especially for power plants with lower power factor, the load capacity of the genset does not depend on the rated power of the diesel engine, but depends on the rated current value of the generator.

The imbalance of the reactive load can also be regarded as a kind of ring between the two generators. The flow sometimes exceeds the load current of the generator and generates additional losses inside the generator. And even overload the generator. The reactive overcurrent also trips the generators main switch, causing a malfunction.

In addition, the magnitude of the reactive current of the generator is consistent with its excitation current. The imbalance of the reactive current tends to occur at the same time as the excitation current imbalance, which causes the excitation system of overload or even cause failure, such as the rotor winding of the generator is burned/ the rectifier diode of the compound excitation device is damaged, etc., and the consequences of such failure are often quite serious. It can be seen that the uniform distribution of the reactive load and the uniform distribution of the active load have the same meaning.






Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz