Balance the Power Distribution of Parallel GenSet



Parallel connection of diesel generator sets should first meet the requirements of even power distribution. The even distribution of power includes both active power and reactive power. The so-called uniform distribution means that the active power and reactive power of each generator should be proportional to their rated power. There are clear requirements for the power distribution of parallel-operated generator sets in China, when the alternator sets are operated in parallel. When the load changes within the range of 20% to 100% of the total rated power, it should be able to operate stably, and its power distribution error should meet the following requirements.








1. The difference between the actual active power of each generator and the calculated value according to the rated power ratio shall not exceed ±10% of the rated active power of the generator when the rated power of the generator is the same; when the rated power of the generator is different, Should not exceed 110% of the maximum rated active power of the generator, ±20% of the rated active power of the minimum generator.

2. The difference between the actual reactive power of each generator and the calculated value according to the ratio of rated power of the generator not exceeding the maximum generator amount

If there is a large imbalance in power distribution, whether it is active power or reactive power, it will not only affect the efficiency and economy of the genset operation, but also cause the failure of the entire power station.

If the active power distribution of the parallel generator set is seriously unbalanced, when the total load power is large, it is often that one generator set is fully loaded or overloaded, and the other generator is still under light load, so that it cannot be fully utilized. The capacity of the genset is used to make the performance of the entire power station. The overload of the genset will not only bring harm to the diesel engine or the generator, but also cause the protection equipment to operate and affect the operation of the entire power station. Conversely, when the total load power is small, the imbalance of active power tends to cause active circulation between the generator sets, causing some generator set to switch to the motor state, which is also not allowed for diesel engines. When the genset has reverse power protection, the reverse power phenomenon will cause the reverse power to trip causing a malfunction.

For diesel power plans with frequent load changes and large variation, the above situation should be paid more attention. For example, in a diesel power station of a ships electric propulsion device, due to the uneven distribution of active load of the parallel generator, when the ship is sailing at full speed, the total load power is large, often overloading the heavy-duty generator, causing the switch then trips, causing a serious power failure. When the ship stops at the dock, the light load generator enters the reverse power state due to the small total load, causing the reverse power trip, which affects the reliability of the operation of the power station and even the entire ship. The above situation is sufficient to show that the even distribution of power between generators in parallel operation is not only a problem of economic operation of a generator, but also an important factor to ensure the reliability of power supply of the entire diesel engine power station.

The reactive power distribution is uneven, although it will not seriously affect the diesel engine, but the rated value of the generator power is determined according to the apparent power, and the reactive power imbalance will inevitably cause the unbalanced apparent power of the generator. It will limit the capacity of the generator set, especially for power plants with lower power factor, the load capacity of the genset does not depend on the rated power of the diesel engine, but depends on the rated current value of the generator.

The imbalance of the reactive load can also be regarded as a kind of ring between the two generators. The flow sometimes exceeds the load current of the generator and generates additional losses inside the generator. And even overload the generator. The reactive overcurrent also trips the generators main switch, causing a malfunction.

In addition, the magnitude of the reactive current of the generator is consistent with its excitation current. The imbalance of the reactive current tends to occur at the same time as the excitation current imbalance, which causes the excitation system of overload or even cause failure, such as the rotor winding of the generator is burned/ the rectifier diode of the compound excitation device is damaged, etc., and the consequences of such failure are often quite serious. It can be seen that the uniform distribution of the reactive load and the uniform distribution of the active load have the same meaning.






Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...