How to Do Noise Reduction in Generator Room



How to Do Noise Reduction in Generator Room


In normal operation, the noise of diesel generator set is mainly exhaust noise. The noise of diesel generators will cause certain pollution to the environment, which will easily affect people's work efficiency and interfere with their normal life. Low noise generators/silent generators must be used in densely populated areas or in places with stringent environmental noise requirements. Therefore, it is necessary to reduce noise in the diesel generator room.

1. Ventilation and noise reduction in machine room
In practical work, we must consider both the effective noise reduction and the air flow required for the operation of the generator set. Two air inlet shaft are built with bricks outside the machine room. A low-noise axial flow fan is installed under the air inlet wall to supply air to the machine room. A large air volume combined muffler is installed in the air duct to absorb airflow noise and mechanical noise. An air inlet is opened on the wall outside the air inlet duct and a protective screen is installed at the air inlet to prevent foreign matter from entering the air duct.

2. Machine room exhaust system silencing
Exhaust air must be silenced through the muffler air duct provided outside the machine room to minimize noise. The outside of the muffler air duct is a brick wall structure, and the inside is a sound absorbing panel. Air outlet is arranged directly in front of the genset, and the front end of the unit radiator is provided with a vibration-damping flexible joint and a wind-conducting expansion sound-absorbing air duct, which is connected to the exhaust hot air silencing channel. Special aluminum alloy shutters and protective wire mesh are installed at the outlet of the exhaust duct to prevent foreign matter from entering the air duct.

3. Genset exhaust silencer

A sound reducing enclosure can be added to the exhaust gas system of the generating set, and at the same time, the exhaust silencing pipes are all wrapped with fireproof rock wool material, which can not only reduce the heat dissipation of the unit into the machine room, but also reduce the working vibration of the unit, so as to achieve the purpose of noise attenuation.

4. The machine room sound absorption

Since the generator room is brick concrete structure, it has strong noise reflection. In order to achieve the sound absorption effect, the wall and the top surface of the machine room are reasonably equipped with high-efficiency sound absorbing materials, and the sound absorbing layer structure is an aluminum alloy perforated gusset plate + centrifugal sound absorbing cotton + light steel keel + support hanger. The original average sound absorption coefficient in the equipment room is α10.10. After the sound-absorbing material is installed, the average sound absorption coefficient in the machine room is α20.750.85, and the sound absorption can reach 912dB(A), and the reverberation time can be reduced to 2~3s. The loudness in the equipment room is also greatly reduced, which greatly improves the working conditions and the sound insulation performance of the generator room.


5. Sound insulation system

In order to ensure good sound insulation performance of the machine room, a fireproof soundproof door is installed in the connection between the machine room, and the sealing material of the door is a rubber seal strip. Other holes that cause sound leakage are blocked with brick walls.





Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz