Skip to main content

Archive

Show more

How to Properly Install Diesel Generator Exhaust Pipe

The exposed part of exhaust pipe should not come into contact with wood or other flammable materials.
The extension of the exhaust pipe must allow thermal expansion, and the pipe can prevent rainwater from entering.

There are two ways to install the exhaust pipe:
 Horizontal overhead: The advantage is less turning and less resistance; the disadvantage is poor indoor heat dissipation and high temperature in the machine room.
 Laying in the trench: The advantage is good indoor heat dissipation; the shortcomings have many turns and the resistance is large.

The temperature of the exhaust pipe of the generator set is high. In order to prevent the scalding operator and reduce the rise of the temperature of the machine room caused by radiation heat. It is advisable to carry out heat preservation treatment. The heat-insulating material can be wrapped with glass silk or aluminum silicate, which can place a role in heat insulation and noise reduction.

Starlight Shangchai diesel generator set

1. Diesel generator exhaust pipes are usually made of unwelded flat steel material, and in some special cases, asbestos cement pipes are used.

2. The exhaust pipe of the diesel generator set shall discharge the gas to an area where will not cause damage or danger, and a protective cap or similar device at the end of the exhaust pipe to prevent rainwater from entering the pipe.

3. The part of the exhaust pipe that passes through the wall is recommended to be thermally insulated to prevent heat from escaping to the wall.

4. The connection of each exhaust pipe of the diesel generator must be well sealed to prevent gas leakage. The connection between flange and gasket is ideal. It is recommended to place a condenser with a socket at the bottom of the pipe.

5. The connection between the exhaust outlet of the diesel generator engine and the pipeline should use elastic hoses, which can alleviate the vibration of the diesel generator engine and the thermal expansion of the pipeline to avoid damage to other components.

6. The exhaust pipe of the diesel generator set also needs a flange (not the flange on the unit), so the exhaust pipe must be fixed on the wall or the top of the machine room with a strong support to prevent it from relying on the diesel generator engine (concentrator, turbo blower), can extend the length of the diesel genset exhaust pipe.

7. When a longer exhaust pipe is required, an expansion joint of an elastic sealing element should be installed.

8. When designing the exhaust pipe, the designer of the diesel generator set manufacturers suggest that the exhaust pipe should be installed away from the air filter of the diesel generator engine to prevent the machine from absorbing hot air or to conduct thermal insulation treatment on the exhaust pipe.

9. When using multiple diesel generator sets, it is not recommended to install all the exhaust pipes on the same pipe, because when some gensets are running and other units are shut down, there will be a problem: the exhaust gas will enter the unused units, resulting in unit damaged.

10. The exhaust back pressure of the engine has a great impact on the power and heat exchange generated by the unit. Excessive back pressure (measured at the exhaust outlet of a naturally aspirated engine or at the turbine outlet of a turbocharged engine) can cause the power of the diesel generator set to drop, the exhaust temperature is too high, and smoke is generated, increasing fuel consumption, causing the cooling water to overheat, the lubricant function fails and other engine components are damaged.

11. If the size of the exhaust pipe exceeds the range specified by the unit, please consult the diesel generator set manufacturer.

12. In order to calculate the total length of the exhaust pipe (which is very important for exhaust back pressure), the following factors must be considered:
 The diameter of the exhaust pipe is larger than the diameter of the engine exhaust pipe, and the linear exhaust pipe is preferably slightly inclined during installation to prevent backflow of condensate.
 When the pipe diameter is too large, a conical joint with a taper less than 30° should be used for connection to the engine exhaust port to avoid loss of more load.

13. The exhaust muffler is generally mounted on the extension of the engine exhaust pipe. If the unit is installed indoor, the exhaust pipe is also installed indoor. However, the installation of the exhaust pipe can also be separated from the diesel generating set. Industrial silencer can reduce the noise level by about 15-20 dB.

14. In order to reduce the noise generated by the machine itself, it can be achieved by reducing the distance of the pipe connected to the engine, so that the position of the muffler will be different.

diesel generator sets

Starlight Power relies on quality products and good service to win the trust of customers. We not only supply diesel generator sets to our customers, but also provide installation, commissioning and training according to customer needs. Starlight 20KW to 2500KW Diesel Power Generator for Sale! Contact us: sales@dieselgeneratortech.com

Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...