What is Common Problems of Cummins Generator Supercharger

Why supercharger is the most vulnerable assembly on Cummins engine?

Because the rated working speed of the supercharger is more than 130,000 rpm, and it is at the outlet of the exhaust manifold, the temperature is extremely high (above 800°C), and the inlet and exhaust pressure is also large, high temperature, high pressure and high speed. Therefore, the requirements for lubrication, cooling and sealing of the supercharger are relatively high.

In order to ensure the service life of the supercharger, it is necessary to ensure the lubrication and cooling of the turbocharger floating bearing. At the same time, in use, it is required to:

a. The engine should idle for 3-5 minutes after starting. Do not add load immediately to ensure good lubrication of the supercharger. The main reason is that the supercharger is located at the top of the engine. If the supercharger starts to run at high speed immediately after the engine starts, it will cause the oil pressure to fail to rise in time to supply oil to the supercharger, resulting in oil shortage damage of the supercharger, and even burning out the whole supercharger.

b. Idle time should not be too long, generally not more than 10 minutes. If the idle time is too long, it will easily cause oil leakage at the compressor end.


c. Do not turn off the engine immediately before stopping. It should be idling for 3-5 minutes to reduce the speed of the supercharger and the temperature of the exhaust system to prevent heat recovery—oil coking—bearing burning and other faults. Frequent incorrect use can damage the supercharger.

d. Long-term unused engines (generally more than 7 days), or engines with new superchargers, should be filled with oil at the inlet of the supercharger before use, otherwise the life may be reduced or the supercharger may be damaged due to poor lubrication.

e. Regularly check whether the connection parts are loose, leaking, oil leakage, and whether the return pipe is unobstructed, if any, should be removed timely.

f. Keep the air filter clean and regularly replace it as required.

g. Regularly change the oil and oil filter.

h. Regularly check the radial axial clearance of the turbocharger shaft. The axial clearance should not be more than 0.15 mm. The radial clearance is: the clearance between the impeller and the pressure shell should not be less than 0.10 mm. Otherwise, it should be repaired by professionals to avoid loss.

Cummins diesel generator

Why is the new supercharger often short life after the supercharger on the engine is damaged?

Reason
a. The lubricating oil is not clean.
b. There are impurities in the oil passage.
c. There are foreign bodies in the intake and exhaust pipes.

Diagnosis and treatment
a. Check that the lubricating oil is clean. Because the speed of supercharger is very high, the matching precision between bearings is also very high, if the lubricating oil is not clean, the shaft of the new supercharger will be damaged quickly, so it is very important to replace the lubricating oil and oil filter at the same time.

b. If the lubricating oil and oil filter are replaced when the turbocharger is replaced, the service life of the supercharger is still very short. It is caused by too much impurities in the oil passage. The oil passage needs to be cleaned. Refer to the following cleaning methods:

1. Remove the broken supercharger and drain the oil when the engine is hot.
2. Add a certain amount of mixed oil (30% oil + 70% diesel oil).
3. Plug the inlet pipe of the supercharger into the return pipe or seal the outlet of the inlet pipe.
4. Start the engine, stop after 1 to 2 minutes of idle speed, and release the mixed oil (if it is dirty, it is best to clean twice). The above work is carried out in the hot car.
5. Clean or replace supercharger inlet pipe, clean oil pan, and replace oil filter and air filter.
6. Install a new supercharger and pre-lubricate the oil at the inlet of the supercharger, then put it into the oil pipe, fill the filter with oil and install it, and finally install other pipes.
7. Start the engine, idle for 3 to 5 minutes, and then speed up to check if there is any oil leakage and air leakage.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...