The causes reason for Volvo diesel generator overexcitation

When Volvo diesel generator or transformer has overexcitation fault, it does not always cause obvious damage to the equipment, which is easy to be neglected. However, repeated over excitation will cause insulation aging and reduce the service life of the equipment due to overheating.

The control of generator stator voltage is realized by adjusting the magnitude of rotor excitation current. The excitation corresponding to the amount of electricity generated is normal excitation. When the stator operating voltage is higher than the rated voltage, it is called overexcitation. Conversely, the stator operating voltage below the rated voltage is called underexcitation. In practice, there is a definite positive and negative value above or below the rated voltage. Different generators have different excitation control system and different excitation values.




Generators and transformers are composed of iron core windings. If the applied voltage of windings is U, the turn number is W, the cross section of iron core is S, and the magnetic density is B, then U = 4.44fWBS. Because W and S is definite number, so it is written in B=KU/f, K=1./4.44WS, for each particular generator or transformer, K is a definite number. We can know from B=KU/f: the increase of voltage and the decrease of frequency can lead to the increase of magnetic density B.

For diesel generator, when overexcitation multiple number n=B/BN=(U/UN)/(f/fN)=U*/f* is less than 1, it will cause damage by overexcitation. It is mainly manifested in the increase of leakage magnetic field in the back of stator core of generator, the induction of electric potential in the positioning bar of stator core, and the closed loop formed by stator core, which flows through the current. It not only causes serious overheating, but also may cause spark discharge at the contact surface between positioning bar and stator core, which is very disadvantageous to hydrogen-cooled generating sets.

When Volvo diesel power generators operating, the reasons for overexcitation maybe as follows:

1.Before the generator is parallel to the system, the excitation is caused by the incorrect increase of the excitation current due to the wrong operation. For example, misjudgement is caused by TV disconnection of generator.
2.During the start-up of the generator, the generator accompanies the low-speed heater of the steam turbine rotor. If the voltage is raised to the rated value by mistake, the overexcitation will be caused by the low-frequency operation of the generator.
3.During shutdown diesel generator set, main valve closed, outlet circuit breaker disconnected, and demagnetization circuit breaker refused to move. At this time, the speed of steam turbine decreases, the automatic excitation regulator strives to keep the terminal voltage equal to the rated value, so that the generator is subjected to overexcitation.
4.When the generator outlet circuit breaker trips, if the automatic excitation regulator operates manually failure or fails automatically, the voltage and frequency will increase, but the generator overexcitation will be caused by the slow increase of frequency.
5.If the generator does not reduce excitation in time during load rejection, the overvoltage will occur; even if the terminal voltage can maintain the previous value in the generator-transformer mode, the overvoltage will occur because the transformer is no-load.

If the allowable overexcitation multiple number of Volvo diesel generator is lower than that of transformer, it will be more vulnerable to the harm of overexcitation. Therefore, large diesel generators need to be equipped with overexcitation protection with perfect performance. For the generator set with circuit breaker installed at the generator outlet, in order to protect the generator and transformer under various operation modes, the overexcitation protection of the generator and transformer should be set separately.



Overexcitation protection should be adjusted according to the overexcitation curve provided by generator manufacturer under full load condition, the setting principle is to make the excitation curve of the adjusted excitation protection relay below the generator overexcitation curve as far as possible. That is to say, when the diesel generators operates under overexcitation conditions, the excitation protection relay should be able to reliably jump off the circuit breakers on each side of the main transformer in a shorter time than it can withstand. At the same time, generators should have a certain level of excitation resistance under ensuring normal operation, so start-up value of excitation protection relay is generally set to slightly greater than the normal maximum operating value.

Starlight series Deutz diesel generators power range is from 26kw to 660kw. If you have purchase plan recently, welcome to contact us.

Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz