Why diesel generator set undervoltage

After using diesel generator set for a period of time, there will always be some faults, such as the generator cannot start normally, low oil pressure alarm, low frequency, overspeed, abnormal noise, etc. In this article, we mainly discuss the cause of diesel generator undervoltage faults.

1. Diesel engine mechanical speed regulation

The speed regulation of diesel engine is divided into electronic speed regulation and mechanical speed regulation. If it is mechanical speed regulation, then there is a fuel  pump mechanism on the diesel engine that controls the oil quantity and oil paths. There is a pull rod on the top to control the oil quantity. It is called speed control pull rod. A speed limit (high speed) push rod and a speed control push rod are distributed on both sides of the speed control pull rod. When the power is turned on for 20 seconds, the low voltage is reported. Don’t know whether the voltage and frequency is always not to go up. If it is not going up, it may be the speed, you can adjust the speed control push rod. However, if the diesel engine fails, there is usually a major fault. The main fault is solved, and a series of minor faults are solved.

diesel generator set

2. The voltage sampling line is loose – The voltage cannot be measured

3. Remanence

If the generator has no residual magnetism, then the voltage system of the generator cannot be built at the beginning. For this problem, we need to know how much volt the excitation output of the generator AVR voltage regulator is, and then connect the corresponding voltage source to the excitation output line for magnetization (the voltage type should be corresponding and the polarity should not be reversed).

4. Ground fault

If three-phase grounding occurs, the voltage and current are very low. At this time, it is mainly necessary to check whether the grounding discharge device is closed or grounded.

5. Voltage regulating plate failure

Due to changes in environmental factors, the parameters of the AVR pressure regulating plate are no longer applicable and need to be re-adjusted. Generally speaking, non-parallel diesel units basically do not have such problems, because the parameters of the pressure regulating plate are fixed values ( 400V), which is generally not adjustable. This problem may occur only for gensets that are used in parallel because the AVR voltage regulator is regulated in accordance with the main bus voltage, it is not static. At this time, the parallel device usually has a voltage regulating signal sent to the AVR voltage regulating plate. In this case, either check whether the voltage regulating signal is connected incorrectly, or try to use the electronic control quickly when the power is turned on (parallel device, voltage regulating plate, etc.) to reset the voltage.

6. The varistor or rectifier bridge diode on the generator winding is damaged

The function of the varistor is: when the overvoltage fault occurs, the varistor is turned on to reduce the voltage. If the varistor is broken down or turned on for other reasons, it is conceivable that the voltage must be very low. The rectifier bridge has six diode, the set DC power supply is used to supply the voltage regulating plate and the excitation device. If the rectifier bridge diode is damaged, the functions of the voltage regulating board and the excitation device will be greatly reduced.

In order to avoid generator failure, regular maintenance is very necessary. This can not only give a full play to the excellent performance of the diesel generator set, but also extend the service life of the genset. Due to different brands of diesel generators, the maintenance items are different. In order to maintain your diesel generator accurately, the units should be maintained strictly in accordance with the user's maintenance manual provided by the supplier.

Jiangsu Starlight Power is as a professional diesel generator set OEM with more than 40 years in the field of generator manufacturing. We can provide multiple brands of emergency diesel generators with good quality, such as Cummins, Perkins, Volvo, Deutz, Yuchai, Weichai, Shangchai, etc. If you are interested, please contact us to get the price now!

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Silent Cummins 640kw Diesel Generating Sets

Technical data of 800KVA AC diesel generator set The DG Set is skid mounted, directly coupled with Cummins water cooled engine with built in shock absorber for anti vibration. The alternator is Stamford brand with brushless and self excited, with control panel and protection system complete set. Prime power: 640KW/800KVA Standby power:704KW/880KVA Rated voltage: 230/400V Rated current: 1152A Speed/frequency:1500rpm/50Hz ( or 1800rpm/60Hz) Power factory:0.8lag Size: open type genset: 4.2 x1.82x2.25m, silent genset: 6.5 x2.6 x2.78m Net wight: open type genset: 7800kg,   silent genset : 12000kg Technical Data of Diesel Engine Diesel engine brand/model: Chongqing Cummins/ KTA38-G2B( full new) Prime/standby power: 790KW/920KW 4 Stroke Cycle , 60° Vee , 12 Cylinder, Turbocharged &Aftercooled, 1500rpm, 50Hz, bore/stroke: 159/159mm. The Cummins diesel engine is equipped with electronic type governor, over speed shutdown devices to protect against runaway when electronic governor or con...

Guides to Clean VOLVO Diesel Generator Cooling System

VOLVO Engine Cooling System Volvo engine's internal cooling system makes sure the engine works at the right temperature. It is a closed system that must always be filled with a mixture of concentrated coolant and water in order to protect the engine against internal corrosion, cavitation and bursting due to freezing. Coolant of a suitable chemical composition must be used all year round. This also applies in areas where there is never any risk of freezing, to provide the engine of  diesel generator set   with full corrosion protection. The use of anti-corrosion agents alone is not permitted in Volvo Penta engines. Never use water alone as a substitute for coolant. The corrosion protection additives become less effective over time, which means that the coolant must be changed at regular intervals; refer to Maintenance Schedule. The cooling system must be flushed whenever the coolant is changed; Volvo Penta coolants have been prepared to work best ...