Idle Speed Problem of Diesel Industrial Generators

When we use diesel generator set, maybe we meet the problem of idle speed of engine, how to solve it? Today Starlight Power generator manufacturer answers for you.

There is no idle speed during cold start, which is generally normal, because the temperature is too low, the oil viscosity is too large, the engine resistance increases, the spray and evaporation conditions of diesel oil become worse, resulting in the engine can not maintain the minimum steady speed operation, and when the throttle is lifted, it will soon flameout. In this case, the throttle can be adjusted to operate slightly higher than idle speed, and the idle operation can be resumed after the engine warms up.

If the engine of diesel industrial generators has been used for a long time, there is no idling condition, and the fuel consumption is not normal with insufficient power, it is generally due to the excessive wear of the plunger and the increase of oil leakage during idling, which makes the fuel supply unable to meet the requirements of idling condition; or the cylinder pressure is too low, and the injection advance angle is too large and too small, which causes poor combustion conditions of the engine. As long as we deal with the problem of insufficient power, the idling condition will recover naturally.

If the above conditions are normal, consider whether the idle working element of the governor is abnormal. Check whether the governor spring is broken, or the governor element is worn too much or the spring is too soft, so that the centrifugal force of the flying hammer at idle speed is far greater than the spring tension and the oil is reduced, or the maintenance personnel adjust improperly. The fuel injection pump assembly must be removed for repair and adjustment on the test bench.

When checking the governor, first adjust it by idle screw. If the adjustment is invalid, adjust the pre tension of idle spring. The idle speed spring adjusting nut can be slightly screwed in or the spring seat can be padded to increase the preload and raise the idle speed. If the spring is broken, it should be replaced and then adjusted to restore the idle working performance.

Starlight Power is a diesel generator set manufacturer in China, founded in 1974, focused on high quality product for more than 43 years, covering Cummins, Volvo, Perkins, Deutz, Yuchai, Shangchai, Ricardo, Weichai etc. Power range is from 25kva to 3125kva. Welcome to contact us by email sales@dieselgeneratortech.com or Whatsapp +8613471123683.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Silent Cummins 640kw Diesel Generating Sets

Technical data of 800KVA AC diesel generator set The DG Set is skid mounted, directly coupled with Cummins water cooled engine with built in shock absorber for anti vibration. The alternator is Stamford brand with brushless and self excited, with control panel and protection system complete set. Prime power: 640KW/800KVA Standby power:704KW/880KVA Rated voltage: 230/400V Rated current: 1152A Speed/frequency:1500rpm/50Hz ( or 1800rpm/60Hz) Power factory:0.8lag Size: open type genset: 4.2 x1.82x2.25m, silent genset: 6.5 x2.6 x2.78m Net wight: open type genset: 7800kg,   silent genset : 12000kg Technical Data of Diesel Engine Diesel engine brand/model: Chongqing Cummins/ KTA38-G2B( full new) Prime/standby power: 790KW/920KW 4 Stroke Cycle , 60° Vee , 12 Cylinder, Turbocharged &Aftercooled, 1500rpm, 50Hz, bore/stroke: 159/159mm. The Cummins diesel engine is equipped with electronic type governor, over speed shutdown devices to protect against runaway when electronic governor or con...

Guides to Clean VOLVO Diesel Generator Cooling System

VOLVO Engine Cooling System Volvo engine's internal cooling system makes sure the engine works at the right temperature. It is a closed system that must always be filled with a mixture of concentrated coolant and water in order to protect the engine against internal corrosion, cavitation and bursting due to freezing. Coolant of a suitable chemical composition must be used all year round. This also applies in areas where there is never any risk of freezing, to provide the engine of  diesel generator set   with full corrosion protection. The use of anti-corrosion agents alone is not permitted in Volvo Penta engines. Never use water alone as a substitute for coolant. The corrosion protection additives become less effective over time, which means that the coolant must be changed at regular intervals; refer to Maintenance Schedule. The cooling system must be flushed whenever the coolant is changed; Volvo Penta coolants have been prepared to work best ...