Skip to main content

Archive

Show more

Using Generator to Charge Batteries


There are going to be many times when the sun isnt shining, the wind isnt blowing and your batteries are low. The only choice you might have is to charge your batteries using your fossil fueled generator.

As you may already know, there is not a more expensive method of battery charging than using a 120/240 volt 60hz (230 volt 50hz) AC fossil fueled generator.

There are 3 ways to charge your battery bank and they are listed below in order of best to worst (most efficient to least efficient) methods of charging your battery bank. Most efficient just means you get more kWhs per dollar spent (or liter of fossil fuel consumed).

    Ideally you would have enough solar, wind or micro-hydro power (but that can be almost impossible in some climates).
    The second best would be a DC generator made from a fossil fueled engine and 3 phase alternator that is rectified to DC.
    Using an off-the-shelf or industrial 120/240 volt 60hz (or 230 volt 50hz) fossil fueled generator.


Making your own electricity with a gas, propane or diesel generator can cost anywhere from $2.50 t0 $5.00 per kilowatt hour compared to the $.05 to $.60 per kilowatt hour most utilities charge. It is horribly expensive and environmentally a disaster. Most fuel powered generators have no or very little emissions controls and are made to wear out in a matter of months when used to charge batteries in an off grid power system.

STEP 1: Bulk charge at 10% of the battery banks C20 rate

The first step in setting up your system to charge batteries efficiently is to program your inverter/battery charger to charge at 10% of the battery banks C20 AH rating.
Consult your battery manufacturers literature for the C20 amp hour (AH) rating.

For example:

Trojans L16s have a C20 amp hour rating of 370 AH at 6 volts.

If you were to take four of these L16s and place them in series you would now have a 24 volt battery bank rated at 370 amp hours.
Simply take the C20 AH rating and multiply by 10% or .10. This is your bulk charge current setting.

In the above example you should try to put 37 amps (370 multiplied by 10%) at 24 volts  into your battery bank. This would require about 880 to 1110 watts depending on the actual battery voltage.

To get the most bang for your bucktry your best to achieve the 10% of the banks AH rating. Obviously there will be times when this is not possible such as having too small of a generator or too small of a charger. You can charge at a lower current, it just wont be as efficient.

If you charge with more than 10% of C20, you risk damaging the batteries due to over heating and over gassing.

Lets try another example:

This time we have sixteen Trojan T105s (225 AH @ 6 volts) wired in series and parallel to make a 48 volt battery bank. There are two banks of eight batteries that are paralleled to make 450 amp hours (C20) at 48 volts. This is pretty common battery bank and is shown in the picture below

In this example, it is best to set your inverter/charger to bulk charge at 45 amps (450 amp hours multiplied by 10%). Forty five amps is approximately 2160 to 2700 watts depending on the real voltage of the battery bank.

Even if you have a much larger battery charger/generator, 45 amps is the target charge rate for this particular battery bank. Any less will result in excess generator run time and fuel consumption, any more can result in damage to your batteries.
STEP 2: Program correct bulk voltage into inverter/charger

Consult your battery manufacturer for the correct bulk voltage setting. Next examine your inverter/chargers manual to learn how to program the bulk voltage.

You need to be careful here as some manufacturers list:

    the bulk voltage per cell
    the bulk voltage per battery
    the absorption voltage (same thing as bulk voltage)
    the bulk/absorption voltage (same thing as bulk voltage)
    the bulk voltage as a range (i.e. 2.35-2.45 volts per cell)
    the daily charge voltage (same thing as bulk voltage)

All of the above terms like absorption, daily charge and bulk voltage are all referring to the bulk voltage setting.

If your bulk voltage is listed per cell, think of each cell as being two volts.

    a 6 volt battery or battery bank has three cells
    an 8 volt battery or battery bank has four cells
    a 12 volt battery or battery bank has six cells
    a 24 volt battery or battery bank has twelve cells
    a 48 volt battery or battery bank has twenty four cells

Once you know how many cells you have simply multiply the volts per cell by the number of cells you have. If your battery bank is 48 volts you know it will made up of 24 cells.

For our first example we have 4 Trojan L16s. Trojan lists the bulk/absorption voltage as 2.45 volts per cell.


Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz