why your generator fails to start



why your generator fails to start



In the result of a power failure standby generators are there for us when we need them the mostat least thats what we hope. As with any piece of machinery a generator cannot be 100% reliable, this blog will explore some of the common reasons why a diesel generator may fail to start and most importantly, how to reduce the risk of a failure.

Standby generators are often operated infrequently, meaning that monthly tests and service plans are vital to ensure problems are not occurring unknown to the operator. Lets take a look at the most common reasons why a generator will fail to start and what you can do to prevent these happening in the future.
1. Battery Failure
Image of a battery conntected to a diesel generator

One of the most common reasons a generator will not start is due to a battery failure. Often this could be caused by a loose connection or a sulfation build-up (a build-up of lead sulphate crystals on the plates of lead-acid batteries). When sulfate molecules in the electrolyte (battery acid) become so deeply discharged it causes a build-up covering the plate leading to the battery not being able to provide enough current.

 A battery failure can also occur due to the charger breaker being open inoperable, usually by a fault within the battery charger unit itself or the AC supply being disconnected by a tripped circuit breaker. This can often happen after a service or maintenance has been carried out when the charger has been turned off and not turned back on again. It is always worth double checking the generator set system after a service or maintenance has been carried out to ensure the charger supply circuit breaker is in the correct position.

Finally, a battery failure could be due to dirty or loose connections. Connections need to be regularly cleaned and tightened to prevent a potential for failure.

At Power Electrics we recommend you replace your batteries every three years to reduce the risk of failure.
2. Low Coolant Levels

Without radiator coolant, an engine would soon overheat, leading to mechanical breakdown and engine failure. Coolant levels should be checked on a regular basis by visually checking if there are any puddles of coolant. The coolant colour varies depending on the manufacturer although it most commonly will look red.

Internally plugged radiator cores can also lead to low coolant level shutdowns. When the generator is operating under load, the thermostats open completely when the engine reaches the optimum operation temperature, meaning the radiator cannot allow the proper amount of flow through the core. Because the coolant has to go somewhere, it escapes through the overflow line. When the engine cools off and the thermostat closes, the level drops and activates a low coolant level shutdown to your generator. Because this only happens when the generator has reached to optimum running temperature under load, it is suggested that you test your generator with an external load bank with sufficient load to reach the temperature value needed to open the thermostats.
3. Bad Fuel Mix

Often the reason your generator will not start is linked in some way to fuel. A bad fuel mix can occur in several ways:

    When your fuel runs out the engine receives air but no fuel
    The air intake gets clogged, meaning there is fuel but no air
    The fuel system might be supplying too much or too little fuel to the mix. As a result, combustion does not occur properly within the engine.
    Finally, there may be impurities in the fuel (i.e. water in the fuel tanks) which causes the fuel not to burn. This is often the case when fuel has been standing in a tank for long periods of time.

As part of a routine service of any standby generator, it is always best practice to test the fuel to ensure it does not cause a fault in the future.
4. Controls not in Auto

When your control panel displays the Not in automessage this is a result of humanControl panel error, normally due to the main control switch being left in the off/reset position. When it is in this position the generator may not start in the event of a power outage.

Regularly check the control panel of your generator to make sure the not in automessage is not displaying. There are plenty of other faults which display upon the control panel that can result in your generator not starting. Find out more about these and how to reset them in our How Tovideo series.

Hopefully this blog has provided some insight into common reasons why your generator fails to start. It is important to remember that a generator, much like a car, needs to be serviced on a regular basis.

Click here to find out about the diesel generator services that we provide at Power Electrics along with the range of maintenance services to meet your requirements.




Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

Function Of Battery, Breather And Radiator In Diesel Generator

A diesel generator is a diesel powered machine capable of converting mechanical energy to electrical energy. It basically consists of a diesel engine, who's drive shaft is directly connected to something called an alternator. The job of the alternator is to convert the mechanical energy provided to it by the diesel engine to electrical energy. So the alternator consists of 2 windings called the stator winding and the rotor winding. During operation the stator winding is stationary while the rotor winding are performing circular motion (since they are connected to the drive shaft of the diesel engine). Working Of The Alternator: The rotor windings are excited by some DC current so that a magnetic field is produced around the coil. Since it is performing circular motion the magnetic flux linked with it also keeps performing circular motion at the same speed. This magnetic flux is intersected by the stator winding which is fitted around the rotor. According to Faraday...