Information about Volvo Engine TAD734GE




Information about Volvo Engine TAD734GE

The DU is an computerized instrument panel which shows engine working values on an LCD screen. In the display it is possible to show multiple windows with different information, i. g. Volvo engine rpm, coolant temperature, fuel consumption and fault messages.

At start up, the display performs a self-test. If an constant signal is heard, the system has discovered a malfunction. The display will work but may act in an unexpected way.

The DU is connected between the engine control unit and the CIU or DCU.

Contrast

In the display modes Engine, Trip and Graph, it is possible to adjust the contrast. Press button 5 outside the menu and then + (button 4) or - (button 3) to adjust the contrast.

Contrast.jpg



Engine

Rpm and coolant temperature is shown in the upper part of the display. In the lower part it will show trip computer and a fuel level indicator, if these functions are installed.

Coolant.jpg



Multi

In the multi mode, button 2, the information can be shown in four windows, analogue or digital. The display toggles between the two when button 2 is pressed repeatedly. By pressing button 5, the right arrow, you choose what information to be shown in the different windows. Press repeatedly on the button that correspond to the window, until desired information is shown.



Multi.jpg



Trip

To display the trip computer press button 3, Trip

Trip Fuel, since last reset

Fuel Rate, fuel consumption

Trip hours, since last reset

Engine hours, total amount of operating hours

Reset by pressing button 3 for three seconds until a beep is heard.

Trip.jpg



Graph

The information is shown as graphs. Press button 4 repeatedly to choose what information will be shown. The time interval is set in the Configuration menu.

If the connection is broken there will be a straight line in the display.

Graph.jpg



Configuration menu

Press button 5 for three seconds to enter the Configuration menu. Navigate with the up and down  arrows, select with the right arrow.

Configuration menu.jpg



Units

- PRESSURE: kPa, PS

- VOLUME; LITRE, GAL, Imperial GAL.

Fuel rate is adjusted according to volume unit, L/H, GAL/H, IGAL/H.

- TEMPERATURE; °C, °F

Units.jpg



Alarm Status

List of active alarms, refer to Reading fault codes via the DU (Display Unit)

Alarm status.jpg



Settings

LANGUAGE; setting of what language is to be used in the display.

BLEEP; On/Off, setting if pressing the instrument buttons will be followed by a beep or not.

DISPLAY; setting of ENGINE RPM gauges RPM ENGINE, 2500-9000 RPM, in steps of 500

RPM

GRAPH RANGE, 2 minutes- 8 hours in the following steps,

2MINS, 10MINS, 30MINS, 60MINS, 2HRS, 4HRS, 8HRS

Setings.jpg



SYSTEM

DEMO, switches the DEMO mode ON/OFF

RESTORE DEAFAULTS, reset all configuration to default values.

COM VIEWER, displays latest message on communication ports

PROG TX, transfers content of the application on

Flash memory to other CAN units on the same CAN bus.

ABOUT, displays

ID NO - display serial number

EEPROM - number of write on EEPROM

VERS - software version number

CHK - Flash memory checksum

PART No - Volvo software part number

SOURCE - source of received data

LABEL - Allocated Label on the same bus



System.jpg



CIU (Control Interface Unit)

The CIU is a "translator" between the control unit (EMS) and the customer's own control panel. The CIU has two serial communication links, one fast and one slow.

The fast one is a so-called CAN link. All data related to instruments, indication lamps, connectors and potentiometers is controlled by this link.

The slow link manages diagnostic information for flashing codes etc.

Control Interface Unit.jpg



Easy Link Instruments

The following Easy Link instruments are available

- Tachometer / hours counter (fault codes are also displayed on the tachometer display when the diagnostic button is pressed)

- Coolant temperature

- Oil pressure

- Oiltemperature

- Batteryvoltage

- Alarm panel

- Turbo pressure



DCU (Display Control Unit)

The pre-heating time is adjusted to suit engine temperature, and may last up to 50 seconds both before and after starting.

The starter motor connection time is maximized to 20 seconds. After that, the starter motor circuit is cut for 80 seconds to protect the starter motor against overheating.

NOTICE! Preheat must be activated when the temperature is below o °C (32°F)

DCU.jpg



With preheating

1 Press the ON/OFF button (6)

2 Press the SEL button (7) to come to the main menu

3 Navigate to Preheat with the browse button (9). Press the SEL button (7)

4 In the Preheat menu, press the SEL button (7) to select pre-heating; the text "Preheat active please wait" is shown in the display.

5 Wait until the text disappears and then press the START button (2).

Without pre-heating

1 Press the ON/OFF button (6)

2 Press the START button (2).

Warm through the engine at idle (1,500/1,800 rpm)





Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...