Volvo Penta Engine Operator Manual


Volvo Penta Engine Operator Manual



Volvo Penta Engines
This Operator's Manual covers the industrial engines: 4 cylinders TD520GE, TAD530GE, TAD531GE and TAD532GE. 6 cylinders TAD620VE, TAD730GE, TAD731GE, TAD732GE, TAD720VE and TAD721VE of Volvo Penta Engine.

The engines are four-stroke, direct injection in-line diesel engines with replaceable wet cylinder liners (except TAD620VE, which has dry liners).

The engines are fitted with turbochargers, piston cooling and a water-cooled charge air cooler that reduces the temperature of inlet air to provide a greater mass of air to the cylinders. This makes greater engine output possible at the same time as combustion and exhaust temperatures can be maintained at suitable levels. Also, NOx emissions are reduced.

To facilitate start and reduce exhaust emissions in cold weather, the engines are fitted with electric intake air heaters (exceptions TAD520GE and TAD720VE).

Instruments and Controls
This chapter describes the instrument box and the instrumentation in Volvo Pentas range. Variations in the appearance of instrumentation may occur in certain applications (mobile for example). If this is the case, see the Instruction Manual for the relevant application.

Warning

If the instrument box does not have an ignition switch, the engine/operator compartment must have a lock to prevent unauthorised persons starting the engine. (Alternatively a lockable main switch can be used.)

Instrument box

1. Oil pressure gauge. Normally within the green field (300500 kPa).

2. Warning lamp: Low engine coolant level (accessory)

3. Engine coolant temperature gauge. Normally within the green field (7095°C).

4. Warning lamp: High engine coolant temperature (accessory)

5. Tachometer

6. Operating hour counter

7. Starter button

8. Warning lamp: Generator not charging

9. Interlock: Press in the button to disengage the automatic stop for low oil pressure and to activate preheating.

10. Warning lamp: Low oil pressure (accessory)

11. Stop button

12. Semi-automatic fuses: Reset by pressing the button on the fuse.

Before Starting
Check that the oil level is between the MIN and MAX marks. For filling refer to Oil level, checking and topping up.

Open the fuel cocks.

Check that there are no coolant, fuel or oil leaks.

Check the air filter pressure drop indicator. Please refer to Engine, General.

Check coolant level. Check that the outside of the radiator is not clogged. Please refer to Coolant Level, Checking and Topping Up, and Charge Air Cooler, External Cleaning.

WARNING!

Do not open the coolant filler cap when the engine is hot, except in emergencies as this could cause serious personal injury. Steam or hot fluid could spray out.

Turn the main switch on.

IMPORTANT: Never break the circuit with the main switch while the engine is running.

Alternator and electronics could be damaged.

Set the engine speed control to idle. Disengage the disengageable clutch/transmission.

Starting the Engine
1. Press the Interlock button(1) and check that the warning lamps in the instrument box are functioning. (This applies to engines equipped with alarm separators).


2. If the engine is hot: Press the Interlock button(1) and hold it in while pressing the Starter button (2). If the engine is cold: Press the Interlock button (1) and hold it in for approximately 50 seconds to preheat the engine. Then press the Start button(2) as well.


3. Release the Start button immediately when the engine starts. However the Interlock button must be held down for a further 5 seconds approximately. This is to allow the oil pressure to reach the correct level. Otherwise the automatic stop will engage and stop the engine.

NOTICE! In extreme cold, the preheating can be re-engaged for a few minutes after start if necessary. Hold the Interlock button (1) pressed in.



Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...