Cooling Tests of Volvo Diesel Engine




Cooling Tests of Volvo Diesel Engine


Cooling Tests, General


Glossary

A number of terms are used to define cooling system capacity. Maximum ambient temperature. The maximum ambient temperature the machine may be used in without exceeding the permissible water temperature.

Δt water (delta t) - the temperature differential between radiator inlet and outlet

coolant.

Δt air - the temperature differential between radiator inlet and outlet air.



Cooling capacity

A cooling system installation's cooling capacity is often measured using a reference temperature for coolant boiling point called ATB (Air To Boil). The ATB temperature is defined as the ambient temperature at which the coolant attains its maximum permissible coolant temperature. AOT (Air On Temperature) refers to the maximum permissible coolant temperature after the Volvo engine. It is defined as the temperature of the cooling air entering the charge air cooler. The difference between AOT and ATB temperatures is that the input cooling air temperature is used instead of the ambient temperature.



The maximum permissible temperatures for each engine type are given in Technical data, in Sales Support Tool, Partner Network This concerns unpressurized cooling systems. If the system is fitted with a pressure cap or pressure valve the boiling point will rise according to the pressure setting value.





Cooling Test Preparation

Before the application is prepared for a cooling test it is extremely important to ensure that the installation in general is satisfactory. If any adjustments are necessary as a consequence of the tests, and which may affect cooling in particular, such changes must be made at this stage. It is also extremely important to have accurate and reliable instruments available, as well as other equipment and aids recommended for performing the cooling tests. Sometimes all the recommended equipment may not be available, but remember that the main objective is to ensure that the application is tested under a load cycle that corresponds to the most difficult conditions the application can be exposed to during use.



If there is any uncertainty about how difficult the conditions the application will be exposed to will be, we recommend always to attempt maximum output at rated rpm. Measuring instruments must be installed at the recommended locations. All tests must be performed with a fixed open thermostat. A short test run must be made to check that all parts with temperature probes attached are functioning correctly. The test must be carried out in dry conditions with a wind speed that does not exceed 7 m/s (23 ft./s) and preferably with an ambient temperature above +5 °C (+41 °F). Before the cooling test is carried out, exhaust back pressure must be determined at rated rpm under full load.



Air filter resistance must be determined with the engine at maximum rated rpm and load. Regardless of the type of application being tested, the maximum load condition expected during application use must be determined. One practical method of determining maximum load conditions is to check exhaust gas temperature. When the maximum load condition has been determined, the application must be run continually at this load until temperatures have stabilized. This usually takes 50 to 60 minutes. The installation checks must be concluded with a technical report that includes all test results, a detailed description of the installation and a conclusion.







Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

Silent Cummins 640kw Diesel Generating Sets

Technical data of 800KVA AC diesel generator set The DG Set is skid mounted, directly coupled with Cummins water cooled engine with built in shock absorber for anti vibration. The alternator is Stamford brand with brushless and self excited, with control panel and protection system complete set. Prime power: 640KW/800KVA Standby power:704KW/880KVA Rated voltage: 230/400V Rated current: 1152A Speed/frequency:1500rpm/50Hz ( or 1800rpm/60Hz) Power factory:0.8lag Size: open type genset: 4.2 x1.82x2.25m, silent genset: 6.5 x2.6 x2.78m Net wight: open type genset: 7800kg,   silent genset : 12000kg Technical Data of Diesel Engine Diesel engine brand/model: Chongqing Cummins/ KTA38-G2B( full new) Prime/standby power: 790KW/920KW 4 Stroke Cycle , 60° Vee , 12 Cylinder, Turbocharged &Aftercooled, 1500rpm, 50Hz, bore/stroke: 159/159mm. The Cummins diesel engine is equipped with electronic type governor, over speed shutdown devices to protect against runaway when electronic governor or con...