Cooling Tests of Volvo Diesel Engine




Cooling Tests of Volvo Diesel Engine


Cooling Tests, General


Glossary

A number of terms are used to define cooling system capacity. Maximum ambient temperature. The maximum ambient temperature the machine may be used in without exceeding the permissible water temperature.

Δt water (delta t) - the temperature differential between radiator inlet and outlet

coolant.

Δt air - the temperature differential between radiator inlet and outlet air.



Cooling capacity

A cooling system installation's cooling capacity is often measured using a reference temperature for coolant boiling point called ATB (Air To Boil). The ATB temperature is defined as the ambient temperature at which the coolant attains its maximum permissible coolant temperature. AOT (Air On Temperature) refers to the maximum permissible coolant temperature after the Volvo engine. It is defined as the temperature of the cooling air entering the charge air cooler. The difference between AOT and ATB temperatures is that the input cooling air temperature is used instead of the ambient temperature.



The maximum permissible temperatures for each engine type are given in Technical data, in Sales Support Tool, Partner Network This concerns unpressurized cooling systems. If the system is fitted with a pressure cap or pressure valve the boiling point will rise according to the pressure setting value.





Cooling Test Preparation

Before the application is prepared for a cooling test it is extremely important to ensure that the installation in general is satisfactory. If any adjustments are necessary as a consequence of the tests, and which may affect cooling in particular, such changes must be made at this stage. It is also extremely important to have accurate and reliable instruments available, as well as other equipment and aids recommended for performing the cooling tests. Sometimes all the recommended equipment may not be available, but remember that the main objective is to ensure that the application is tested under a load cycle that corresponds to the most difficult conditions the application can be exposed to during use.



If there is any uncertainty about how difficult the conditions the application will be exposed to will be, we recommend always to attempt maximum output at rated rpm. Measuring instruments must be installed at the recommended locations. All tests must be performed with a fixed open thermostat. A short test run must be made to check that all parts with temperature probes attached are functioning correctly. The test must be carried out in dry conditions with a wind speed that does not exceed 7 m/s (23 ft./s) and preferably with an ambient temperature above +5 °C (+41 °F). Before the cooling test is carried out, exhaust back pressure must be determined at rated rpm under full load.



Air filter resistance must be determined with the engine at maximum rated rpm and load. Regardless of the type of application being tested, the maximum load condition expected during application use must be determined. One practical method of determining maximum load conditions is to check exhaust gas temperature. When the maximum load condition has been determined, the application must be run continually at this load until temperatures have stabilized. This usually takes 50 to 60 minutes. The installation checks must be concluded with a technical report that includes all test results, a detailed description of the installation and a conclusion.







Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...