Exhaust System of Volvo Diesel Engine



Exhaust System of Volvo Diesel Engine


Dry Exhaust Line

Silencer

In general there are two types of silencer: absorbing and reactive.



Absorbing silencers

These silencers work according to the principal of absorbing sound with the aid of an absorbent lining inside the silencer. They usually provide silencing over a broad frequency range. They are generally of straight-through construction and only offer a marginally higher back pressure than a straight pipe of the same length.



Expansion silencers (reactive)

These silencers work according to the principal of reflecting sound and thereby retaining it inside the silencer. The silencer has internal baffle plates that divide it up into sections that can be adjusted individually to a given frequency. A reactive silencer creates a relatively high back pressure owing to the meandering route of the gas flow, i.e. past the baffles that redirect the flow. Volvo Penta HD silencers combine reactive and absorbing silencing. Silencer location Reactive silencers are located as close to the exhaust manifold as possible (to impede sound from the manifold) or at the end of the system. The absorption unit is generally located in line directly after the reactive unit. There must only be a short end pipe (1 m) after the silencer if it is installed at the end of the exhaust line. Insulation of long exhaust lines affects exhaust back pressure and exhaust pipe diameter must therefore be increased.

General points for consideration

The exhaust system must be planned from the beginning of the installation.

The main objectives are to:

A ensure that back pressure in entire system is below the max limit set by the engine manufacturer.

B reduce strain on the manifold and turbocharger by supporting the system.

C provide space in the correct directions for heat expansion and contraction.

D provide flexibility if the Volvo engine is fitted with vibration dampening mounts.

E reduce exhaust noise. The illustration on the right shows a typical installation.

IMPORTANT!

Exhaust gases from multi-engine installations may not be led together in a common system, as this can be very dangerous and cause engine damage. The reason for this is that if one engine is at rest while the other is running, exhaust gases, condensate and soot will be forced into the resting engine's exhaust system and on into the cylinders, which may cause corrosion. If a good quality butterfly valve is installed in every exhaust line close to the duct, common exhaust lines

may sometimes be approved. Use the following formula for calculating the total diameter of the common exhaust pipe:

DTOTAL = D x K

D = exhaust pipe diameter for one engine.

K = factor (refer to the table).

Back Pressure

The exhaust system will give a certain resistance to exhaust gas flow. This resistance (back pressure) must be kept within given limits.


Excessive back pressure causes:

- Loss of power

- Poor fuel economy

- High exhaust temperature



Such conditions will cause overheating and excessive engine smoke, and will reduce valve and turbocharger service life. Maximum permissible engine pressure values for Volvo Penta engines are specified in the Sales Support Tool, Partner Network.



A manometer is used to measure exhaust back pressure at maximum rated power.

It may be difficult to use a flange in many installations because of a lack of space. If a hole must be drilled specially for the pressure test it is important that the hole is small max Ø 2 mm (0.08") and located on a straight pipe section. Make sure the hole is free from swarf. The distance from the hole to pipe bends and tapered sections must be at least 100 mm (4").



Calculation of Back Pressure

Calculation of back pressure for HD silencers For the purpose of calculating back pressure on Volvo Penta silencers exhaust flows and temperatures are specified in an Excel-based system in the Sales Support Tool, Partner Network.



NOTICE! The application for calculating exhaust system back pressure is based on a worst case, namely an insulated exhaust pipe at its full length. This means that the calculated exhaust back pressure is somewhat excessive for uninsulated exhaust systems. The calculation application is also based on system pipe bends having a radius of 2.5 times the pipe diameter. Silencer back pressure used in the application is only applicable to Nelson-Burgess DDA type silencers. These silencers are described with their diameters in inches followed by HD in the Industrial Sales Guide.

Installation

Flexible connection pipes

The exhaust pipe is isolated from the engine with flexible connection pipes. The flexible connection pipes are located close to the engine exhaust outlet and have three functions:

1 Isolating vibrations and exhaust pipe weight from the engine.

2 Compensating exhaust pipe expansion.

3 Compensating sideways motion when the engine starts or stops when the engine is attached to vibration dampening mounts.

The flexible pipe is able to absorb small radial movements, but no twisting or axial movements.

The flexible unit can be installed in different positions, but should preferably be installed vertically and not be bent.

In the calculations, consideration must be given to exhaust pipe heat expansion to avoid excessive strain on the supporting structure.

For every temperature increase of 100 °C (212 °F) one meter of steel pipe will expand around 1.2 mm (0.047"). It is therefore important to locate the holders such that the pipe is able to expand away from the engine to avoid straining and twisting connected equipment. Furthermore,

equipment must removable without additional support.



Long pipes are divided into sections using expansion joints. Each section is fixed at one end and is able to expand at the other.




Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...