Control Governor for Cummins Diesel Engine Smoothly Rising



Introduction

The 4914090/4914091 governor is a high performance diesel engine speed governor which was developed based on environmental protection concept.

As our previous generation products, it includes wide-supply-voltage adaptability, anti -interference ability, and protection ability for a variety of abnormal condition.

It could reduce the emission and smoke during engine start.

It is a diesel engine protection controller which is stable, reliable and safe.

Technical Characteristics

1.1 Basic Functions

It is suitable for N, M11, K, KV series Cummins diesel engine.

Generator

The 4914090 type is suitable for N, M11 series, K series engine (K19 or below capacity);

The 4914091 type is suitable for KV series engine (K38 or above capacity).

1.1.1 Run/Idel mode,

Remote Speed Adjust,
Run speed and idle speed setting,
Gain and Droop setting,
Smoothly rising control setting.
Working parameters
Rated Voltage: 24V DC
Maximum Output Current: 2.1A
Speed Signal: Sinusoidal Signal, effective value not less than 1.7V
Speed Adjustment Range: ±600RPM

Work Environment
Temperature Range: -40+65
Relative Humidity: 90%
Vibration Acceleration: 100m/S2
Shock Acceleration: 150m/S2
Operating Instruction
Appearance and Installation Dimension:

Connection mode

Battery:
1# TerminalPower+2# TerminalGND.
Use 1mm2 or larger copper wire.
Actuator:
3# & 4# Terminals: Actuator
Use 1mm2 or larger copper wire.
Do not short circuit the terminals to GND.

Speed Signal
5# Terminals: Speed Signal6# Terminals: GND for Speed Signal

Make sure the Common Ground Terminals are unified, when the speed signal source is common used by more than one equipment.

Remote Speed Adjust:

A potentiometer installed on the panel would be connected to 7#, 8# and 9# terminals as a Remote Speed Adjuster.

The 47K- Ohm Potentiometers PN is 3035105. 2# pin should be connect to the 8# terminal of Control Governor. A 200K-Ohm resistor could be series connection in the wire in order to improve engine stability, if necessary.

Keep the 8# and 9# terminals open if Remote Adjusting is not needed.

Idel/Run Mode Switch:

10 # terminal is Idle / Run mode switch interface. A switch or relay could be connected between 7# and 10 # terminals.

When the switch or relay is open, control governor will work in RUN Mode. When the switch or relay is connected, control governor will work in IDLE Mode.

Common GND

11 # terminal is spare GND, and do not need to be connected. Do not attach the battery negative to 11 # terminal, the control governor may be damaged.

A# and B# terminals are damping, it was needed when the oscillation of the coupling between engine and generator occurred, and do not need to be connected in general condition.

Debugging and Use:

Droop
 This Potentiometer is used to set the speed decline percent when the engine is loaded.
Droop Potentiometer is used with Gain Potentiometer in order to keep the engine work stability.

GAIN
This Potentiometer is used to set the sensitivity of speed adjustment when the engines load is changed.
Gain Potentiometer is used with Droop Potentiometer in order to keep the engine work stability.

RUN
This Potentiometer is used to set the target Run-Speed.
IDLE
This Potentiometer is used to set the target Idle-Speed.

SMOOTHLY RISING CONTROL
This setting time is used to set the sensitivity of Smoke Control.
The larger potentiometer set, the more smoke control. But too large setting time may cause difficult engine start.
The potentiometer is usually arranged on the 10s point.
Note: See details per Cummins publication 3379231.



Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...