Control Governor for Cummins Diesel Engine Smoothly Rising



Introduction

The 4914090/4914091 governor is a high performance diesel engine speed governor which was developed based on environmental protection concept.

As our previous generation products, it includes wide-supply-voltage adaptability, anti -interference ability, and protection ability for a variety of abnormal condition.

It could reduce the emission and smoke during engine start.

It is a diesel engine protection controller which is stable, reliable and safe.

Technical Characteristics

1.1 Basic Functions

It is suitable for N, M11, K, KV series Cummins diesel engine.

Generator

The 4914090 type is suitable for N, M11 series, K series engine (K19 or below capacity);

The 4914091 type is suitable for KV series engine (K38 or above capacity).

1.1.1 Run/Idel mode,

Remote Speed Adjust,
Run speed and idle speed setting,
Gain and Droop setting,
Smoothly rising control setting.
Working parameters
Rated Voltage: 24V DC
Maximum Output Current: 2.1A
Speed Signal: Sinusoidal Signal, effective value not less than 1.7V
Speed Adjustment Range: ±600RPM

Work Environment
Temperature Range: -40+65
Relative Humidity: 90%
Vibration Acceleration: 100m/S2
Shock Acceleration: 150m/S2
Operating Instruction
Appearance and Installation Dimension:

Connection mode

Battery:
1# TerminalPower+2# TerminalGND.
Use 1mm2 or larger copper wire.
Actuator:
3# & 4# Terminals: Actuator
Use 1mm2 or larger copper wire.
Do not short circuit the terminals to GND.

Speed Signal
5# Terminals: Speed Signal6# Terminals: GND for Speed Signal

Make sure the Common Ground Terminals are unified, when the speed signal source is common used by more than one equipment.

Remote Speed Adjust:

A potentiometer installed on the panel would be connected to 7#, 8# and 9# terminals as a Remote Speed Adjuster.

The 47K- Ohm Potentiometers PN is 3035105. 2# pin should be connect to the 8# terminal of Control Governor. A 200K-Ohm resistor could be series connection in the wire in order to improve engine stability, if necessary.

Keep the 8# and 9# terminals open if Remote Adjusting is not needed.

Idel/Run Mode Switch:

10 # terminal is Idle / Run mode switch interface. A switch or relay could be connected between 7# and 10 # terminals.

When the switch or relay is open, control governor will work in RUN Mode. When the switch or relay is connected, control governor will work in IDLE Mode.

Common GND

11 # terminal is spare GND, and do not need to be connected. Do not attach the battery negative to 11 # terminal, the control governor may be damaged.

A# and B# terminals are damping, it was needed when the oscillation of the coupling between engine and generator occurred, and do not need to be connected in general condition.

Debugging and Use:

Droop
 This Potentiometer is used to set the speed decline percent when the engine is loaded.
Droop Potentiometer is used with Gain Potentiometer in order to keep the engine work stability.

GAIN
This Potentiometer is used to set the sensitivity of speed adjustment when the engines load is changed.
Gain Potentiometer is used with Droop Potentiometer in order to keep the engine work stability.

RUN
This Potentiometer is used to set the target Run-Speed.
IDLE
This Potentiometer is used to set the target Idle-Speed.

SMOOTHLY RISING CONTROL
This setting time is used to set the sensitivity of Smoke Control.
The larger potentiometer set, the more smoke control. But too large setting time may cause difficult engine start.
The potentiometer is usually arranged on the 10s point.
Note: See details per Cummins publication 3379231.



Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz