Control Governor for Cummins Diesel Engine Smoothly Rising



Introduction

The 4914090/4914091 governor is a high performance diesel engine speed governor which was developed based on environmental protection concept.

As our previous generation products, it includes wide-supply-voltage adaptability, anti -interference ability, and protection ability for a variety of abnormal condition.

It could reduce the emission and smoke during engine start.

It is a diesel engine protection controller which is stable, reliable and safe.

Technical Characteristics

1.1 Basic Functions

It is suitable for N, M11, K, KV series Cummins diesel engine.

Generator

The 4914090 type is suitable for N, M11 series, K series engine (K19 or below capacity);

The 4914091 type is suitable for KV series engine (K38 or above capacity).

1.1.1 Run/Idel mode,

Remote Speed Adjust,
Run speed and idle speed setting,
Gain and Droop setting,
Smoothly rising control setting.
Working parameters
Rated Voltage: 24V DC
Maximum Output Current: 2.1A
Speed Signal: Sinusoidal Signal, effective value not less than 1.7V
Speed Adjustment Range: ±600RPM

Work Environment
Temperature Range: -40+65
Relative Humidity: 90%
Vibration Acceleration: 100m/S2
Shock Acceleration: 150m/S2
Operating Instruction
Appearance and Installation Dimension:

Connection mode

Battery:
1# TerminalPower+2# TerminalGND.
Use 1mm2 or larger copper wire.
Actuator:
3# & 4# Terminals: Actuator
Use 1mm2 or larger copper wire.
Do not short circuit the terminals to GND.

Speed Signal
5# Terminals: Speed Signal6# Terminals: GND for Speed Signal

Make sure the Common Ground Terminals are unified, when the speed signal source is common used by more than one equipment.

Remote Speed Adjust:

A potentiometer installed on the panel would be connected to 7#, 8# and 9# terminals as a Remote Speed Adjuster.

The 47K- Ohm Potentiometers PN is 3035105. 2# pin should be connect to the 8# terminal of Control Governor. A 200K-Ohm resistor could be series connection in the wire in order to improve engine stability, if necessary.

Keep the 8# and 9# terminals open if Remote Adjusting is not needed.

Idel/Run Mode Switch:

10 # terminal is Idle / Run mode switch interface. A switch or relay could be connected between 7# and 10 # terminals.

When the switch or relay is open, control governor will work in RUN Mode. When the switch or relay is connected, control governor will work in IDLE Mode.

Common GND

11 # terminal is spare GND, and do not need to be connected. Do not attach the battery negative to 11 # terminal, the control governor may be damaged.

A# and B# terminals are damping, it was needed when the oscillation of the coupling between engine and generator occurred, and do not need to be connected in general condition.

Debugging and Use:

Droop
 This Potentiometer is used to set the speed decline percent when the engine is loaded.
Droop Potentiometer is used with Gain Potentiometer in order to keep the engine work stability.

GAIN
This Potentiometer is used to set the sensitivity of speed adjustment when the engines load is changed.
Gain Potentiometer is used with Droop Potentiometer in order to keep the engine work stability.

RUN
This Potentiometer is used to set the target Run-Speed.
IDLE
This Potentiometer is used to set the target Idle-Speed.

SMOOTHLY RISING CONTROL
This setting time is used to set the sensitivity of Smoke Control.
The larger potentiometer set, the more smoke control. But too large setting time may cause difficult engine start.
The potentiometer is usually arranged on the 10s point.
Note: See details per Cummins publication 3379231.



Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...