Hazards of Diesel Generator Set Small Load



Longer than 10 minutes of low idle speed or no load can damage the engine. Because the temperature of the combustion is so low that the fuel can not be completely burned. This will cause the formation of carbon deposition and valve adhesion around injector holes and piston rings.

If the engine coolant temperature is below 60°C, the unburned fuel will wash away the lubricating oil on the cylinder wall and dilute the oil in the crankcase. Fuel diluents will affect the quality of lubricant and shorten the engine life. Its better to shorten idle time to prevent this from happening.

Running diesel generator set under small load, with the continuation of running time, the following five hazards will occur.

1. Piston-cylinder liner seal is not good, oil channelling, entering to the combustion chamber to burn, exhaust blue smoke;

2. For turbocharged diesel engine, supercharging pressure is low due to low load and no-load. It is easy to cause the effect of turbocharger oil seal (non-contact type) seal to decline, oil moves into the pumping chamber, along with the intake into the cylinder;

3. A part of the oil in the cylinder takes part in the combustion, part of the oil cannot be completely burned, and the carbon deposits are formed at the valve, inlet, piston top, and piston ring, etc, and some are discharged with the exhaust. In this way, the cylinder sleeve exhaust duct will gradually accumulate oil, will also form a carbon deposit;

4. The supercharger indoor oil accumulates to a certain extent, it will leak out from the joint surface of the supercharger;

5. Running under small load for a long time will lead to more serious wear and serious of moving parts and deterioration of engine combustion environment, which will lead to the early overhaul period.

Therefore, the diesel engine manufacturers emphasize that the low load / no load operation time should be minimized in the use of both naturally aspirated and pressurized diesel engines, and the minimum load should not be lower than 25%-30% of the rated power of the genset.

Full load operation of diesel generating sets for a long time can not only improve the performance, find out the hidden dangers of safety, but also avoid major communication accidents.

First. Preparation before start-up

Check that the cooling water or antifreeze in the diesel engine tank is satisfied before starting, if it is lacking, then fill it up. Pull out the oil gauge to see if the lubricating oil is lacking, if it is missing, add it to the prescribed tick mark, and then carefully check whether the components have hidden trouble, if fault found to be timely troubleshooting before starting up.

Second. it is strictly forbidden to start diesel engine with load.

Before starting the diesel engine, you should pay attention to the output air switch of the diesel generator must be closed. After starting the diesel engine of the ordinary generator set, it will take 3-5 minutes of idle operation (about 700rpm/min), the winter temperature is low (700 rpm) and the idle running time should be extended for a few minutes. After starting the diesel engine, it is necessary to observe whether the oil pressure is normal and whether there is oil leakage, water leakage and other abnormal phenomena. (The oil pressure must be above 0.2MPa under normal conditions,) If abnormalities found, stop and overhaul the engine. If there is no abnormality, the diesel engine speed will be increased to the rated speed of 1500 RPM/min. At this time, the generator display frequency is 50Hz and the voltage is 400V, then the output air switch can be closed and put into use.

Generator sets are not allowed to run under no-load for a long time. Because long hours of no-load operation will cause the diesel fuel injected from fuel injector not to be completely burned, resulting in carbon deposits, valve and piston ring leakage. If it is an automatic generator set, there is no need for idle speed because the automatic unit is usually equipped with water heater, so that the cylinder block of the diesel engine is always kept at about 45 , and the diesel engine can transmit power normally within 8-15 seconds after starting.

Third. pay attention to observe the working state in operation.

During the operation of the generator set, specially-assigned person should be on duty to observe a series of possible faults, especially the changes of oil pressure, water temperature, oil temperature, voltage, frequency and so other important factors. In addition, it should be noted that there is sufficient diesel fuel in operation, such as fuel interruption in operation, which will objectively cause load shutdown, which may lead to the damage of generator excitation control system and related components.

Fourth, it is strictly forbidden to stop with load.

Before each shutdown, the load must be cut off step by step, the generator output air switch should be closed. Finally, the diesel engine should be slowed down to idle state for 3-5 minutes before stopping the engine.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Silent Cummins 640kw Diesel Generating Sets

Technical data of 800KVA AC diesel generator set The DG Set is skid mounted, directly coupled with Cummins water cooled engine with built in shock absorber for anti vibration. The alternator is Stamford brand with brushless and self excited, with control panel and protection system complete set. Prime power: 640KW/800KVA Standby power:704KW/880KVA Rated voltage: 230/400V Rated current: 1152A Speed/frequency:1500rpm/50Hz ( or 1800rpm/60Hz) Power factory:0.8lag Size: open type genset: 4.2 x1.82x2.25m, silent genset: 6.5 x2.6 x2.78m Net wight: open type genset: 7800kg,   silent genset : 12000kg Technical Data of Diesel Engine Diesel engine brand/model: Chongqing Cummins/ KTA38-G2B( full new) Prime/standby power: 790KW/920KW 4 Stroke Cycle , 60° Vee , 12 Cylinder, Turbocharged &Aftercooled, 1500rpm, 50Hz, bore/stroke: 159/159mm. The Cummins diesel engine is equipped with electronic type governor, over speed shutdown devices to protect against runaway when electronic governor or con...

Guides to Clean VOLVO Diesel Generator Cooling System

VOLVO Engine Cooling System Volvo engine's internal cooling system makes sure the engine works at the right temperature. It is a closed system that must always be filled with a mixture of concentrated coolant and water in order to protect the engine against internal corrosion, cavitation and bursting due to freezing. Coolant of a suitable chemical composition must be used all year round. This also applies in areas where there is never any risk of freezing, to provide the engine of  diesel generator set   with full corrosion protection. The use of anti-corrosion agents alone is not permitted in Volvo Penta engines. Never use water alone as a substitute for coolant. The corrosion protection additives become less effective over time, which means that the coolant must be changed at regular intervals; refer to Maintenance Schedule. The cooling system must be flushed whenever the coolant is changed; Volvo Penta coolants have been prepared to work best ...