How to Clean VOLVO Diesel Generator Cooling System





Volvo engine's internal cooling system makes sure the engine works at the right temperature. It is a closed system that must always be filled with a mixture of concentrated coolant and water in order to protect the engine against internal corrosion, cavitation and bursting due to freezing.

Coolant of a suitable chemical composition must be used all year round. This also applies in areas where there is never any risk of freezing, to provide the engine with full corrosion protection. The use of anti-corrosion agents alone is not permitted in Volvo Penta engines. Never use water alone as a substitute for coolant.

The corrosion protection additives become less effective over time, which means that the coolant must be changed at regular intervals; refer to Maintenance Schedule. The cooling system must be flushed whenever the coolant is changed;

Volvo Penta coolants have been prepared to work best with Volvo Penta engines and offer excellent protection against corrosion, cavitation damage, and bursts due to freezing. Only coolants of this quality are adapted to, and approved by, Volvo Penta.


IMPORTANT!

Volvo Penta engines are delivered with either Volvo Penta Coolant (green) or Volvo Penta Coolant VCS (yellow); both are available as concentrates and Ready Mixed.

We recommend that the coolant supplied with the engine on delivery be used. Future warranty claims related to engine and accessories may be denied if an unsuitable coolant has been used, or if the instructions for coolant mixture have not been followed. Engines using yellow Volvo Penta Coolant VCS must have a yellow decal with the text VOLVO COOLANT VCS on the expansion tank.

The two types of Volvo Penta coolant may never  be mixed with each other as this will affect the anti-corrosion properties.

Coolant filters may not be used together with Volvo Penta Coolant VCS.

Ready Mixed
The ready-mixed coolant protects the engine from corrosion damage, cavitation damage and bursts due to freezing down to

-28 °C (-18 °F) Volvo Penta Coolant (green).

-24 °C (-11 °F) for Volvo Penta Coolant VCS (yellow).

Coolant, Mixing
WARNING! All coolant is hazardous and harmful to the environment. Do not consume. Coolant is flammable.

IMPORTANT: Different types of coolant must not be mixed with each other.

The concentrated coolant must be mixed with pure water (distilled or deionized water) according to specifications; refer to Water Quality page 61.

Mix: 40% concentrated coolant and 60% water

This mixture prevents against internal corrosion, cavitation and bursts due to freezing down to

-28°C (-18°F) Volvo Penta Coolant (green).
-24°C (-11°F) Volvo Penta Coolant VCS (yellow).
At 60% glycol concentration, the freezing point is lowered to
-54°C (-65°F) Volvo Penta Coolant (green).
-46°C (-51°F) Volvo Penta Coolant VCS (yellow).
Never mix in more than 60% of the concentrated coolant. A greater volume of concentrate entails a reduced cooling effect with the risk for overheating and reduced anti-freeze protection.



It is extremely important that the system be filled with the correct coolant concentration. Mix in a separate clean vessel before filling the cooling system. Make sure that the liquids mix.

Coolant Level, Checking and Topping Up


WARNING! Do not open the cooling water filler cap when the engine is hot, except in emergencies, this could cause serious personal injury. Steam or hot fluid could spray out.


Check the coolant level daily before starting. Top off with coolant as necessary. The level should be about 5 cm below the sealing plane of the filler cap or between the MIN and MAX markings if a separate expansion tank is installed.

IMPORTANT! Topping off must take place using a mixture of the same type as that already in the cooling system.

Filling a completely empty system

Check that all drain points are closed.

NOTICE! The location of drain and venting nipples is shown on the next page.

Topping off must be done with the engine stopped. Fill slowly, to allow air to flow out through the venting nipples and the filler.

If a heating unit is connected to the engine cooling system, the heat control valve must be opened and the installation vented during filling.

IMPORTANT! Fill up with coolant to the correct level. Do not start the engine until the system is vented and completely filled.

Start the engine and warm it up until the thermostats are fully open (about 20 minutes). Open any venting nipples a short while after starting, to allow trapped air to escape. Check the coolant level and top up as necessary.



Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...