Terminal Pillars Letters Meaning in Deutz Generator Set


In generally, there is terminal pillars in generator, such as armature, magnetic field, tower, neutral point, etc. These terminal pillars have different letters, what does the letters mean? Today Starlight manufacturer talks about terminal pillars letters meaning in Deutz generator set.
1. Armature terminal pillars. It is a coarser terminal pillars in generator, in generally, its diameter is 6mm;
2. Magnetic field terminal pillars and neutral point terminal pillars. There are two buttons on the generator, usually 3 mm in diameter. One of the screw roots contacts directly with the outside or connects with conductive copper sheet, which is a tower terminal pillars. Another adjacent thin terminal is the magnetic field terminal, and an independent terminal is the neutral point terminal;
3. Use multimeter to measure and identify. Before measure, remove the wires on the terminal pillars of the generator, place the multimeter in RX10 gear and RX100 gear, then one watch rod is connected to the generator housing, and the other one is connected to two thin terminal pillars on the brush rack. If the resistance value is 0, that is tower terminal pillars, if there is resistance value, that is magnetic field terminal pillars.

The rectifier end of the generator has different terminals and different alphabetical symbols on the corresponding positions. The meaning is as follows:
1. “A”, “B+” or “B” ( Battery) is armature terminal pillars, which connecting with positive rectifier board inside the generator and output electric energy outward. Connect with positive battery and starter through thicker conductor. Generally power output line also known as “B”.
2. “F” ( Field) is magnetic field terminal pillars, which applied to generator. It connects to the one end of inside generator and excitation winding, and connects to the "F" terminal of the voltage regulator. For an integrated generator (built-in integrated circuit voltage regulator), the end of the excitation winding connected to the integrated circuit regulator is also called "F".
3. “N” or “P” is neutral point terminal pillars, which connecting to the star type neutral point inside the generator. Generally used to control relays for various purposes, such as charging indicator relay, magnetic field relay, etc. For the integrated generator (built-in circuit regulator), the neutral point (or the contact point in three-phase winding) is generally connected with the integrated circuit regulator.
4. “L” (Light) is charging indicator terminal. Inward, connected with integrated circuit voltage regulator, through the voltage regulator to control the operation of charging indicator; outward, generally connected to charging indicator through the burning switch.

5. “E” ( Earth) is a common sign of the earth terminal pillars. Generally it is connected to generator casing. Inward, connect to “E” or “-” letter terminal pillars on voltage regulator, the purpose is to let the generator and voltage regulator form a good circuit to ensure the normal operation of the charging system.
6. “IG” (Ignition) is Ignition terminal pillars, generally control the operation of generator though it. Outward connect to positive electrode of battery through ignition switch.

Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz