How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you.

1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips.

(2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened.

(3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose.

(4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is sound of discharge, the high-voltage fuse is blown, and the indication of the secondary side voltmeter is unstable, varying from high to low. Causes of failure: system over-voltage, long-term overload operation, insulation aging, poor manufacturing process.

(5) The winding is broken. Fault phenomenon: during operation, arc may be generated at the broken line, with discharge sound, and the voltmeter indication of broken line phase is reduced or zero. Causes of the fault: poor welding process, insufficient mechanical strength or unqualified outgoing line, resulting in broken winding lead.

(6) Insulation breakdown of winding to ground. Fault phenomenon: the fuse on the high voltage side is continuously fusing, and there may be discharge sound. Causes of failure: winding insulation aging or conductive impurities in the winding, insulation oil moisture, overvoltage breakdown, serious oil shortage, etc.

(7) Short circuit between windings. Fault phenomenon: high voltage side fuse is blown, oil temperature increases sharply, and even fuel injection smoke phenomenon. Causes: winding insulation aging, insulation oil moisture, serious oil shortage.

(8) Discharge flashover between bushing. Fault phenomenon: high voltage side fuse is blown, bushing flashover discharge. Causes of failure: the casing is mechanically damaged by external force, foreign matters or small animals enter between the casings, the casing is seriously polluted and the insulation is poor.

We are manufacturer of diesel power generator in China, if you are interested, contact us by email sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz