Part 1: Solutions for faults of electrical control in diesel generator


This article mainly talks about how to solve the faults of electrical control in diesel generator set.

1.When the key is turned to “START” for the manual control genset, the genset does not start or the liquid crystal display module controls the genset, and the genset does not start when turn on the start button.

A.Check whether the key switch is working correctly or whether the module start-up port has output;

B.Check whether there is any fault indication, repair the fault if necessary, and reset the corresponding fault information;

C.Check the battery voltage. If the voltage is too low, you need to recharge the battery to full. If the voltage value is normal, you should gradually check whether the voltage signal is correctly sent to all control links according to the drawing, such as throttle solenoid valve and starter motor etc;

D.Check if the emergency stop button has been relaxed;

E.Check whether the start relay good.

2.Start motor, it can work, but the diesel generator can not drive.

A.Check the fuel level and make sure the tubing is properly connected;

B.For the mechanical speed control system generator set, check whether the throttle solenoid valve is properly sucked;

C.For the electronic speed control system diesel generator, check whether the EPG power supply is properly connected and the voltage is normal;

D.For the electronic speed control system genset, when the starter motor is running, use the electric meter to measure whether the MPU has the correct AC voltage signal;

E.Check whether the genset speed has reached or exceeded the set start normal speed;

F.Check whether the fuel delivery system is blocked;

G.Check whether the air filter is blocked;

F. In cold areas, should ensure electric generator is warmed up before starting.

3. High water temperature fault alarm or shutdown.

A. Check whether genset is overload;
B. Check the tightness of the fan belt;
C. After the diesel genset is completely cooled, check if the water level of the cooling water is sufficient;
D. Check whether the water temperature sensor is damaged;
E. Check whether the water temperature sensor switch alarm is correct;
F. Check if the thermostat valve opens correctly;
G. Check that the gap between the pump and the water tank is correct;
H.Confirm that the temperature in the equipment room is not higher than 40 °C.

Hope this article can help you to solve the faults of electrical control system in diesel generator set.

Starlight power manufacturer was set up in 1974, has rich experience in sell and after-sales diesel generator, if you need any information, welcome to inquiry sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How Do You Check Diesel Consumption In The Diesel Generator Set?

  Diesel generator sets   are crucial assets in various industries, providing backup power during outages or serving as primary power sources in remote locations. With fuel costs being a significant operational expense, monitoring diesel consumption becomes essential for efficiency and cost-effectiveness. Here's a comprehensive guide on how to effectively check diesel consumption in a generator set. Understanding Diesel Consumption Metrics Before delving into the monitoring process, it's crucial to grasp the key metrics associated with diesel consumption: Fuel Consumption Rate: This indicates the rate at which diesel is being consumed by the generator set, typically measured in liters per hour (L/hr) or gallons per hour (GPH). Load Factor: The percentage of the generator's maximum capacity being utilized at any given time. It directly influences fuel consumption, with higher loads resulting in increased fuel usage. Fuel Efficiency: A measure of how effectively the generator...