How to Ground Diesel Generating Sets

In order to ensure the safety of human body and power system operation, the diesel generator set is usually required to take grounding measures. According to different grounding purposes, it can be divided into working grounding, protective grounding and protective zero connection.

The first way: working grounding.
Due to the need of operation and safety of power system, the neutral point is often grounded, which is called working grounding. Working grounding has the following purposes:

Reduce electric shock voltage. In systems with ungrounded neutral point, when one phase is grounded, and other two phases touch the human body, electric shock voltage is 1.732 times of phase voltage. While in systems with grounded neutral point, electric shock voltage is reduced to equal or close to the phase voltage.

Cut off faulty equipment quickly. In systems with ungrounded neutral point, when one phase is grounded, the grounding current is very small( because there is electric capacity and insulation resistance between conducting wire and ground, it can also form a current path). It is not enough to make the protection device act and cut off the power supply. Faulty grounding can not be found easily, it will maintain for a long time and not safe for human body. While in systems with grounded neutral point, the grounding current is bigger( close to single phase short circuit), the protection devices act quickly and cut off faulty place.
Reduce the insulation level of electrical equipment to the ground. In systems with ungrounded neutral point, when one phase connect to ground, will let ground voltage of other two phases increase to line voltage. While in systems with grounded neutral point, it is close to phase voltage, so it can reduce the insulation level of electrical equipment and transmission lines and save investment outlay. At the same time, ungrounded neutral point also has benefit. First, one phase grounding is usually instantaneous and can be eliminated automatically. In the system with ungrounded neutral point, there will be no power failure due to tripping. Second, one phase to ground fault can be allowed to exist for a short time, so as to find and repair the fault.

 微信图片_20190829161439_副本.jpg

The second way: protective grounding.
Protective grounding is to ground the metal shell of electrical equipment (which is uncharged under normal conditions), which is suitable for low-voltage system with ungrounded neutral point. We can analyze the protective grounding of the motor.
When the insulation of one phase winding of the motor is damaged, the shell is charged and ungrounded, the human body touches the shell, it is equivalent to single-phase electric shock. At this time, the grounding current capacity (the current flowing into the earth through the fault point) depends on human body resistance and insulation resistance. When the insulation of the system decreases, there is a risk of electric shock.

When insulation of one phase winding of generator is damaged, which making the shell charge, while the shell is grounded and human body touches the shell. Because the resistance of human body is in parallel with the grounding resistance, and usually the resistance of human body is far greater than the grounding resistance, the current passing through human body is very small, so there is no danger. This is the role of protective grounding to ensure personal safety.

The third way: protective zero connection.
Protective zero connection is to connect the metal shell of electrical equipment to the zero line, which is suitable for the low-voltage system of neutral point grounding.

Let us take motor as an example again, when the insulation of one phase winding of motor is damaged, which causing to touch the shell, a single-phase short circuit is formed, which quickly fuses the fuse in this phase, so the shell is no longer electrified. Even when the human body touches the shell before the fuse is fused, the current passing through the human body is extremely small because the human body resistance is far greater than the line voltage.

At the same time, it should be noted that the protective grounding is not used in the system of generator set neutral grounding.

Starlight company is a manufacturer of diesel generator set, more supports or product details, please feel free to contact us by email sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz