How to Analysis faults of Emergency Diesel Generator

Emergency power supply (EPS) is composed of fire protection facilities, emergency lighting, accident lighting and other first-class load power supply equipment. In this article, Starlight Power mainly introduces the fault analysis of emergency diesel generator.

As a backup power source, emergency diesel generator set provides AC power to the load in case of main power failure, ensuring continuous power supply of the load. It is widely used in various industries such as communication, coal mine, etc., and various faults occurred in the operation of the diesel generator set. Most of them are caused by untimely, inoperative or improper operation of the operation manager.

Emergency Diesel Generator Failure

Fault
Fault characteristics and causes
Elimination method
Oil pressure alarm shutdown
Pressure sensor broken
Replace the pressure sensor
Poor quality of lubricating oil
Replace the lubricating oil
Oil filter is dirty
Replace the oil filter
Pressure valve failure
Repair or replace pressure valves
Oil pump failure
Replace the oil pump
Insufficient oil
Add oil
High water temperature alarm and stop
Insufficient cooling water
Add cooling water, the cooling water must be distilled water
Engine cannot start
Water temperature sensor is broken
Replace the water temperature sensor
Tubing has air
Check, exhaust air
Tank valve is not open
Open the oil tank valve
Oil tank without oil
Add fuel
Poor fuel quality
Replace the fuel
Starter motor failure
Replace the starting motor
Insufficient battery capacity
Charge the battery
Battery terminal oxidation, poor contact
Rust removal, fasten battery connection bolt
High pressure oil pump failure
Repair or replace the oil pump
Air filter is blocked
Replace or clean air filter
Diesel engine power
Fuel line, fuel filter into air or blocked
Remove air or replace fuel filter cartridge
Fuel injection pump does not atomize oil
Check for repair or replacement of coupling parts
The generator body is overheated, the ambient temperature is too high, the   temperature of the oil and cooling water is high, and the discharge temperature is also greatly increased.
Check the cooler and radiator to remove scale; check if the pipe diameter is toosmall. If the ambient temperature is too high, the ventilation should be improved to improve the cooling effect.
There is abnormal noise when the diesel engine is running.
The transmission gear is worn and the tooth gap is too large; the front cover   emits an abnormal sound, and when the engine suddenly drops, the impact sound can be heard.
Adjust the backlash and replace the gear according to the wear condition
Inlet   and the exhaust valve clearance is too large, and a loud rhythmic noise is   heard at the cylinder head.
Recalibrate the valve clearance
There is no oil between the rocker arm adjusting screw and the spherical seat of the push rod. The "squeak" of dry friction is heard at the cylinder.
Add oil
Exhaust black smoke
Air filter blocked, intake air blocked
Check and clean the air filter
The fuel supply of each cylinder is uneven.
Adjust the fuel injection pump
Incorrect valve clearance and poor valve seal
Adjust the valve clearance, check the sealing cone, and eliminate the defects
Exhaust white smoke
The atomization of injector is poor, there is oil drop phenomenon, and the injection pressure is insufficient.
Check the nozzle couplings for grinding or replacement, and re-adjust the injection pressure to the specified range
Incomplete combustion in individual cylinders when the engine is just started
Increase the speed and load properly, and run more time.

Emergency Diesel Generator Start-up Operation

Release the "emergency stop" button on the control panel.
Turn the power switch knob on the control panel to the “ON” position, the power indicator light is red, and the generator's controller power is on and displays normally.
Press the manual button on the generator controller panel, the indicator on the manual button lights up, and a palm is displayed in the lower right corner of the LCD screen. This is the manual start mode.
Press the start button on the generator controller panel to start the generator, the generator start indicator lights up, and the LCD screen shows that the three-phase voltage rises from 0V to 230V.
Check the generator for abnormal noise or vibration, whether there is oil leakage, water leakage or air leakage, and whether the control panel displays abnormality.
After confirming that the generator power output has stabilized at about 230V, close the generator control cabinet output circuit breaker, and the diesel generator starts normal power supply.

emergency diesel generator

Emergency Power Output Operation

Check the emergency power supply incoming cabinet breaker, the voltage output shows about 230V, and check that the output status of each feeder circuit is normal.

Operation of Emergency Power Distribution Cabinet in Each Substation

Check and confirm that the incoming power supply of the emergency power distribution cabinet of each substation has been cut to the generator power supply state (backup power supply).
If ATS is not switched to the standby power state, the ATS control switch is cut to the manual state, and the special handle is used to manually switch to the standby power supply state (generator power supply).
Check the normal power supply status of each feeder circuit of the emergency power distribution cabinet.
After the diesel generator is working normally, it is necessary to check the running state of the generator and the output current, voltage and other parameters.

Emergency Diesel Generator Shutdown Operation

Confirm that the incoming power supply of the emergency power distribution cabinet of each substation has been cut to the mains power supply (common power supply).
Confirm that the load has completely exited and disconnect the generator emergency power inlet cabinet circuit breaker.
Disconnect the generator control cabinet output main circuit breaker.
Make sure that the generator is cooled for about 3 minutes at idle speed, then press the stop button on the generator controller panel, the stop button indicator lights up, and the generator stops normally.
If there is an emergency to stop the generator, you can not turn off the generator control cabinet output circuit breaker, directly press the red "emergency stop" button on the controller panel, and the generator will stop in an emergency.
After confirming that the generator is stopped, turn the power switch knob on the control panel to the “off” position, the power indicator light is off, and press the “emergency stop” button to complete the shutdown of the diesel generator.

Notes:
When the diesel generator is running at no load, it shall not exceed 5 minutes.
Do not take off the battery during the operation of the diesel generator to avoid the damage of electronic components.
Do not open the lid of the water tank before the diesel generator set is cooled to prevent scalds.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...