How to store temporarily unused diesel generator set

Today Starlight mainly to share how to store temporarily unused diesel generator.

If a automatic diesel generator is not used for a period of time, a reasonable and feasible storage plan shall be made according to the required time.

Automatic diesel generator

The diesel generator set shall be stored according to the steps. It includes cleaning the unit completely, keeping the unit dry and ventilated, and replacing new lubricating oil of proper quality. Completely drain the water in the water tank and conduct rust prevention treatment for the unit.

Storage of automatic diesel generator when not in use in a short period of time.
1.Empty diesel oil.
2.Turn the piston of the diesel engine to the top dead center of compression.
3.Store indoors and and cover it with a cloth.
4.Don't put it in a wet place.
5.Do not put together with inflammable, explosive and corrosive articles.
6.Turn the crankshaft regularly.

Storage of automatic diesel generator when not in use for a long time.
1.First, it shall be carried out according to the items not used in a short period of time.
2.Clean the dirt on surface of whole set of diesel generator. Clean the unit with compressed air.
3.Fill the generator with desiccant and cover the generator end with thick paper. Cover air vent well and fasten with a rope.
4.Empty the engine oil in the oil filter, air filter, etc.
5.Inject 100-200g oil into each cylinder from exhaust manifold. Turn the crankshaft of the diesel engine dozens of times, so that the oil is evenly distributed in the cylinder and the piston is at the top dead center of compression.
6.Remove the valve cover and lubricate the valve structure with dehydrated oil.
7.Seal the exhaust port, air filter, fuel tank vent, smoke vent of low-temperature starting device, etc. with oiled paper.
8.Use detergent to clean diesel engine, alternator, coupling port, frame and components, tools and accessories etc. Of generator. Spread butter for needed part.
9.Rotate the crankshaft 1-2 times a month, and make the piston at the top dead center of compression after each rotation.

Long term storage of diesel generator sets will have a decisive adverse effect on diesel engines and alternators, and proper storage can minimize the adverse effect. Therefore, the correct storage method is very necessary.

In order to prevent the engine and other accessories of the cooling system from freezing and cracking, and prevent the cooling water from corroding the engine body for a long time, add antifreeze when the unit is used in the area where may be frozen. Antifreeze proportion shall refer to the proportion configuration recommended by the diesel engine manufacturer. During long-term storage, the cooling water in the engine and other accessories of the cooling system must be drained.

The unit shall be stored to avoid overheating, supercooling, rain, sun, etc. When storing batteries of the genset, should avoid direct exposure under sunlight or rain.

After a period of storage, it should be noted to check whether the diesel generator set is damaged before installation and use. Comprehensively check whether the electrical part of the unit is oxidized, whether all connecting parts are loose, whether the main generator coil is still dry and whether the engine body surface is clean and dry etc. If necessary, appropriate measures shall be taken to deal with it.

The stotage of temporarily unused diesel generator set is also an important point. Hope this article is helpful to you.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Silent Cummins 640kw Diesel Generating Sets

Technical data of 800KVA AC diesel generator set The DG Set is skid mounted, directly coupled with Cummins water cooled engine with built in shock absorber for anti vibration. The alternator is Stamford brand with brushless and self excited, with control panel and protection system complete set. Prime power: 640KW/800KVA Standby power:704KW/880KVA Rated voltage: 230/400V Rated current: 1152A Speed/frequency:1500rpm/50Hz ( or 1800rpm/60Hz) Power factory:0.8lag Size: open type genset: 4.2 x1.82x2.25m, silent genset: 6.5 x2.6 x2.78m Net wight: open type genset: 7800kg,   silent genset : 12000kg Technical Data of Diesel Engine Diesel engine brand/model: Chongqing Cummins/ KTA38-G2B( full new) Prime/standby power: 790KW/920KW 4 Stroke Cycle , 60° Vee , 12 Cylinder, Turbocharged &Aftercooled, 1500rpm, 50Hz, bore/stroke: 159/159mm. The Cummins diesel engine is equipped with electronic type governor, over speed shutdown devices to protect against runaway when electronic governor or con...

Guides to Clean VOLVO Diesel Generator Cooling System

VOLVO Engine Cooling System Volvo engine's internal cooling system makes sure the engine works at the right temperature. It is a closed system that must always be filled with a mixture of concentrated coolant and water in order to protect the engine against internal corrosion, cavitation and bursting due to freezing. Coolant of a suitable chemical composition must be used all year round. This also applies in areas where there is never any risk of freezing, to provide the engine of  diesel generator set   with full corrosion protection. The use of anti-corrosion agents alone is not permitted in Volvo Penta engines. Never use water alone as a substitute for coolant. The corrosion protection additives become less effective over time, which means that the coolant must be changed at regular intervals; refer to Maintenance Schedule. The cooling system must be flushed whenever the coolant is changed; Volvo Penta coolants have been prepared to work best ...