100kw WP6D132E310 Weichai Diesel Engine Generator



WP6 series diesel engine was developed based on STEYR series diesel engine. WP6D132E310 is one type of turbocharger centering structure generating diesel engine,which developed in 2016. It is manufactured by WEICHAI POWER CO.,LTD.

Diesel engine can run anytime and continuous operation at constant load of maximum power. ISO standard power.
Diesel engine can run anytime and continuous operation under variable load maximum power. It can overload of 10% ISO standard power.
Diesel engine can running up to 200h by the maximum power of variable power per year. the ISO standard power be oil defined.
Main technical parameters:
Diesel Model:WP6D132E310
Type: In-line, 4-Strokes, Wet-cylinder liner, direct injection, Turbocharged and Intercooled.
No. of cylinders / valves: 6/12
Bore/Stroke: 105mm/130mm
Compression Ratio: 18:1
Displacement: 6.75L
Continuous Power: 102 kW
Rated Power: 120kw
Overload Power: 132kW
Rated Speed: 1500r/min
Idle Speed: 750±30 r/min
Fire Sequence: 1-5-3-6-2-4
Crankshaft Rotating Direction: Counterclockwise facing flywheel
Starting method:DC24V Electrical Start
Starting motor Power/voltage: 4.5kW/24V
Governing control: Electronic Control
Cooling mode:water cooled
Min. coolant temperature of engine working: 40℃
Coolant capacity: 8L
The capacity of oil sump: 16L(follow the oil dipstick)
Engine noise: Acoustic power level107.8 dB(A)
Steady governing rate: 0-5%
Consume ratio of oil and fuel: ≤0.2%
The diesel generator set should be able to output rated power in the following conditions.
Atmospheric pressure, PX:100kPa (or 0 meter above sea level);
Ambiance temperature : 298K(25℃);
Relative air humidity Φr30%.
The diesel generator set should be able to work continuously and reliably in the following
Conditions:
Range of ambiance temperature: -30℃≤T≤50℃;
Relative air humiditythe max relative humidity is 90% of the wettest month in a year(It
means that the lowest average temperature of this month is 25℃).
The working environment should be without explosive gas and electric mote.
The customer should illuminate in advance if there has any especial and dangerous
condition at the working space (for example, explosive and flammable gas).

Starlight Power Wechai diesel generator set power range is from 20kw-600kw, if you are interested, please contact us sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...