Maintenance Methods for Lube Oil System of Emergency Genset

How to maintain lubricating oil system of emergency diesel generator set?
1.Select suitable engine oil for emergency diesel generator.
Generally speaking, the instruction manual of each generator set specifies the type of lubricating oil used for the unit. If there is no lubricating oil specified in the manual, the lubricating oil of similar brand can be used. Never mix different brands of engine oil.
2.During the use of emergency generator set, often check the quality of lubricating oil.
Check the mechanical admixture in the engine oil when the engine is hot, and pull out the engine oil scale to check.

emergency diesel generator

Why should the oil level be suitable?
The oil level of the diesel generator set shall be checked before starting each time to ensure that the oil level is within the specified range.
1.Low oil level will causes over wear, tile burning and cylinder pulling.
2.High oil level will cause oil leaking into cylinder, combustion chamber carbon deposit, piston ring binding and blue smoke from exhaust.
Therefore, when the oil in crankcase is insufficient, add it to the specified oil level and find out the reason for the lack of oil. When the oil level is too high, check whether there is water and fuel in the engine oil, find out the cause and solve it. When adding oil, use a cleaning funnel with a filter screen to prevent impurities from entering the crankcase and affecting the normal operation of the generator set.

Why should oil pressure of diesel generator be suitable?
When starting the unit to rated speed or middle speed, the oil pressure should rise to the specific value within 1min. If oil pressure can not reach to the specific value, we should find out the reason to adjust pressure to the specific value.

Check engine oil quality during the use of emergency diesel generator
1.Inspection of mechanical admixture. Check the mechanical impurities in the engine oil of the generator set when the engine is hot (at this time,impurities floating in the engine oil). When checking, draw out the oil scale and observe at the bright place. If small particles is found on the oil scale or the scribe on the oil scale can’t be seen clearly, it indicates there are many impurities in engine oil. Besides, we also can twist engine oil to check whether there are particles, to confirm if the oil can be used. If the oil appears black or there are too many impurities, change the oil and clean the oil filter.

2.Inspection of oil viscosity. The accurate method is to use viscometer to measure. But the more commonly used method is: put the engine oil on the finger and twist it, if there is viscosity feeling, and there is drawstring phenomenon, it indicates that the engine oil viscosity is suitable. If not, it indicates that the engine oil viscosity is poor. We should find out the reason and replace engine oil.

Clean lubricating system and change oil regularly
1.The engine oil filter shall be cleaned regularly; the engine oil basin and oil passage shall be cleaned when the engine oil is changed.
2.Cleaning method:
Drain the oil when the engine is hot, so as to remove the impurities in the oil basin, oil passage and oil filter as much as possible. Replay the mixed oil in the oil basin (15% ~ 20% kerosene, or mix according to the proportion of diesel oil: oil = 9:1), the quantity is 60% ~ 70% of the capacity of the lubrication system. Run the diesel engine at low speed for 5 to 8 minutes (oil pressure above 0.5kgf/cm2), then shut down, drain the mixed oil, clean the oil filter, filter screen, oil radiator and crankcase, and add new oil.

Starlight Power not only provides genset technical support, but also supplies 20-3000kw prime/emergency/standby electric generators. Contact us by email sales@dieselgeneratortech.com directly, we will answer your question and guide you to choose the suitable genset.

Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz