What Causes Fuel Atomization of 200kw Generator Poor

When the fuel injector of 200kw generator set works, it must have a good atomization function, so as to ensure the fuel combustion of the genset is good, the smoke color of the unit is normal, and the power of the generator is normal.

But maybe we meet fuel atomization of the injector is poor, why? Today Starlight tells you the reasons.

The process of dispersing fuel into fine particles is called fuel spray (or atomization). That can greatly increase the surface area of fuel evaporation and the chance of fuel and oxygen contact to achieve rapid mixing. There are many factors that affect the characteristics of the fuel spray, mainly is structure and size of fuel injector, injection pressure, back pressure of compressed air in cylinder, fuel pump cam contour and speed, fuel viscosity etc.

1.Back pressure of compressed air in cylinder
When Back pressure of compressed air in cylinder of 200kw generator set increasing, density of compressed air will increase, which can increase air resistance acting on fuel spray. Therefore, fuel atomization can be improved, spray cone angle is increased, and range is reduced. In the non supercharged diesel generator, the reverse pressure of the compressed air in the cylinder does not change much, so it has no significant effect on the characteristics of the oil spray.

200kw generator set

2.Fuel pump cam contour and speed
When the cam contour is steep or the camshaft speed is high, the speed of fuel supply in plunger of injection pump will increase. Because injector orifice reduces expenditure, fuel can not folw out directly. Which causes fuel pressure in fuel pipe increased and the speed at which fuel flows out of the orifice increased. Therefore, fuel spray and spray cone angle increases.
3.Fuel viscosity
When the viscosity of the fuel increases, the fuel particles are not easy to disperse into fine drops, resulting in poor atomization. Therefore, for high-speed diesel generators, we generally select light diesel oil with low viscosity as fuel oil.
4.Structure and size of fuel injector
Different structure of injector, the internal perturbation of oil spray will be different, which produce different types of oil spray. The fuel bunches should be closely matched with the combustion system. Different combustion modes require different oil spray, so the fuel injectors with different structures are used.
Under the conditions of unchanged injection pressure, back pressure of compressed air in cylinder and the total size of injector hole, to increase the quantity of injector hole, as the diameter of each orifice decreases, fuel will be throttled more when it flows out of the orifice. So the disturbance increases in the orifice. Therefore, the quality of atomization is improved. If diameter of each orifice increases, the core of the oil spray is dense and the range is increased.
5.Injection pressure
The bigger injection pressure, the bigger initial speed of fuel outflow. Degree of fuel disturbance in the injector hole is bigger, and resistance of compressed air after fuel flow out injector hole, so that the fineness and uniformity of atomization are improved, that is a good quality  atomization. When injection pressure increases, range of oil spray will increase.

How to maintain injector of 200kw diesel generator set?
In order to make the fuel injected into the cylinder by the injector burn completely in time, the oil supply time of the oil pump must be checked regularly. If the fuel supply time is too early, the unit will have difficulties in starting and knocking fault. If fuel supply time is too late, it will lead to black smoke from exhaust, high temperature and increased fuel consumption. The fitting accuracy of the injector needle valve is very high, and the orifice diameter is very small, so we must select specific diesel oil by seasonal variation. Otherwise, the fuel injector can not operate normally.

Do not collide with other hard objects or drop them to the ground when cleaning the needle valve parts of the fuel injector to avoid damaged. When replace the needle valve parts of the fuel injector, should immerse the new coupling in 80℃ hot diesel oil for about 10s. After antirust oil is fully dissolved, spasm the needle valve back and forth in the valve body in clean diesel oil, and thoroughly clean it. In this way, the failure of sticking needle valve due to the dissolving of antirust oil can be avoided.

Above information is about the reasons of fuel atomization poor in 200kw diesel generator set, hope it is helpful to you. When you meet the problem, you can check and remove faults by above reasons.

Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...