Magnetizing Methods to Volvo Generators--Starlight Power

1.Use the starting battery (12V) of the diesel engine to power on the excitation wire (2 carbon brush wires) for a few seconds. It is better to magnetize it during operation. As soon as the battery contacts the excitation wire, the generator magnetizes and circulates to increase the magnetic field.
2.It should be noted that the time of grounding should not be too long, and that the speed of the diesel engine is slightly higher, it is better to carry a load, and connect an electric lamp, so as to know whether the magnetization is successful at any time.

The reasons of no electricity in Volvo generators:
1.After shutdown, the remanence is often lost because the material used for the exciter pole is close to soft steel, and the remanence is small. When there is no current in the excitation winding after shutdown, the magnetic field disappears.
2.The pole of the generator loses magnetism.
3.The excitation circuit element is damaged or the circuit has open circuit, short circuit or grounding phenomenon.
4.The contact between the exciter brush and the commutator is poor or the brush holder pressure is insufficient.
5.The wiring of excitation winding is wrong and the polarity is opposite.
6.The contact between the brush and the slip ring is poor, or the pressure of the brush is insufficient.
7.Generator stator winding or rotor winding open circuit.
8.The outgoing wire of generator is loose or the switch is in poor contact.
Solution ways:
1.The standing battery shall be magnetized before power generation.
2.In the winding, direct current (short time) larger than the rated current is applied for magnetization, and the specific current is determined by the test.
3.Replace the damaged components and repair the faulty circuit.
4.Remove the sharp dirt on the contact surface, adjust the brush pressure and fasten the brush holder.
5.Correct the wiring and press the correct polarity for magnetization.
6.Remove the sharp dirt on the contact surface, grind the brush, adjust the brush pressure, and make the brush and the slip ring in close contact.
7.Check and repair the open circuit.
8.Connect the connector or repair the contact part of the switch.
9.Find out the cause of the fuse, and replace the specified fuse after determining that the generator itself and the circuit are normal.
Starlight Power company founded in 1974, as one of leading manufacturer of diesel generator set in China, we can supply Cummins genset, Volvo generator, Perkins generator, Yuchai generator, Shangchai generator, Deutz generator etc. Power range is from 25kva to 3125kva. If you are interested, please contact us by email sherly@dieselgeneratortech.com, or WhatsApp:+8613471123683.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Silent Cummins 640kw Diesel Generating Sets

Technical data of 800KVA AC diesel generator set The DG Set is skid mounted, directly coupled with Cummins water cooled engine with built in shock absorber for anti vibration. The alternator is Stamford brand with brushless and self excited, with control panel and protection system complete set. Prime power: 640KW/800KVA Standby power:704KW/880KVA Rated voltage: 230/400V Rated current: 1152A Speed/frequency:1500rpm/50Hz ( or 1800rpm/60Hz) Power factory:0.8lag Size: open type genset: 4.2 x1.82x2.25m, silent genset: 6.5 x2.6 x2.78m Net wight: open type genset: 7800kg,   silent genset : 12000kg Technical Data of Diesel Engine Diesel engine brand/model: Chongqing Cummins/ KTA38-G2B( full new) Prime/standby power: 790KW/920KW 4 Stroke Cycle , 60° Vee , 12 Cylinder, Turbocharged &Aftercooled, 1500rpm, 50Hz, bore/stroke: 159/159mm. The Cummins diesel engine is equipped with electronic type governor, over speed shutdown devices to protect against runaway when electronic governor or con...

Guides to Clean VOLVO Diesel Generator Cooling System

VOLVO Engine Cooling System Volvo engine's internal cooling system makes sure the engine works at the right temperature. It is a closed system that must always be filled with a mixture of concentrated coolant and water in order to protect the engine against internal corrosion, cavitation and bursting due to freezing. Coolant of a suitable chemical composition must be used all year round. This also applies in areas where there is never any risk of freezing, to provide the engine of  diesel generator set   with full corrosion protection. The use of anti-corrosion agents alone is not permitted in Volvo Penta engines. Never use water alone as a substitute for coolant. The corrosion protection additives become less effective over time, which means that the coolant must be changed at regular intervals; refer to Maintenance Schedule. The cooling system must be flushed whenever the coolant is changed; Volvo Penta coolants have been prepared to work best ...