Magnetizing Methods to Volvo Generators--Starlight Power

1.Use the starting battery (12V) of the diesel engine to power on the excitation wire (2 carbon brush wires) for a few seconds. It is better to magnetize it during operation. As soon as the battery contacts the excitation wire, the generator magnetizes and circulates to increase the magnetic field.
2.It should be noted that the time of grounding should not be too long, and that the speed of the diesel engine is slightly higher, it is better to carry a load, and connect an electric lamp, so as to know whether the magnetization is successful at any time.

The reasons of no electricity in Volvo generators:
1.After shutdown, the remanence is often lost because the material used for the exciter pole is close to soft steel, and the remanence is small. When there is no current in the excitation winding after shutdown, the magnetic field disappears.
2.The pole of the generator loses magnetism.
3.The excitation circuit element is damaged or the circuit has open circuit, short circuit or grounding phenomenon.
4.The contact between the exciter brush and the commutator is poor or the brush holder pressure is insufficient.
5.The wiring of excitation winding is wrong and the polarity is opposite.
6.The contact between the brush and the slip ring is poor, or the pressure of the brush is insufficient.
7.Generator stator winding or rotor winding open circuit.
8.The outgoing wire of generator is loose or the switch is in poor contact.
Solution ways:
1.The standing battery shall be magnetized before power generation.
2.In the winding, direct current (short time) larger than the rated current is applied for magnetization, and the specific current is determined by the test.
3.Replace the damaged components and repair the faulty circuit.
4.Remove the sharp dirt on the contact surface, adjust the brush pressure and fasten the brush holder.
5.Correct the wiring and press the correct polarity for magnetization.
6.Remove the sharp dirt on the contact surface, grind the brush, adjust the brush pressure, and make the brush and the slip ring in close contact.
7.Check and repair the open circuit.
8.Connect the connector or repair the contact part of the switch.
9.Find out the cause of the fuse, and replace the specified fuse after determining that the generator itself and the circuit are normal.
Starlight Power company founded in 1974, as one of leading manufacturer of diesel generator set in China, we can supply Cummins genset, Volvo generator, Perkins generator, Yuchai generator, Shangchai generator, Deutz generator etc. Power range is from 25kva to 3125kva. If you are interested, please contact us by email sherly@dieselgeneratortech.com, or WhatsApp:+8613471123683.

Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz