How to operate diesel generators safely

In this article, Starlight will share the safety operation rules and commissioning operation procedures of diesel generator sets.

General provisions

1. The operating personnel should be specially trained, must fully understand the construction performance and function of diesel generator set and auxiliary equipment, and be familiar with the operation and maintenance procedures before they can operate alone.

2. It is strictly forbidden to drink. Operators must not engage in anything unrelated to operation. It is not allowed to leave the work position without authorization, and it is not allowed to decide to replace the work by non-machine operators without authorization.

3. When working at night, the work area should have sufficient lighting.

4. When cleaning the genset body with diesel or oil, smoking is strictly prohibited, and the accessories must not be flammable. Used waste oil, rags, and cotton yarn must be properly disposed of, and they must not be thrown or placed indiscriminately.

5. Cleaning, tightening and other maintenance work on each moving part must be carried out after shutdown.

6. The machine room should be equipped with sufficient fire extinguishing equipment, and the operating personnel should be skilled in using it.


diesel generator set

Inspection of diesel generator set before operation

1. Check that there is no looseness in the fasteners, reliable connection of parts, and no cracks and leakages in the lubrication system and oil supply system joints.

2. The cooling water of the water tank should be filled, oil and diesel oil shoule be sufficient, the battery should be fully charged, the wiring should be reliable, and all electrical circuits should be reliable.

3. The exhaust water treatment should be filled with water from above to below 30cm, and the water valve should be closed, otherwise water will flow into the exhaust pipe.

4. All parts of the generator should be in good contact.

Manual start-up operation

1. Press the key manual code, the controller enters "manual mode", the manual mode indicator lights, and then press the key generator start, after the start-up delay ends, enter the fuel relay output 1s delay.

The fuel relay outputs 1s, and then the starting relay outputs; if the genset does not start successfully within the "starting time", the fuel relay and the starting relay stop output, enter the "starting interval time", and wait for the next start;

2. If the genset does not start successfully within the set starting times, the LCD jumps to the alarm screen, and the LCD displays the alarm of starting failure;

3. At any start, if the start is successful, enter the "safe operating time 10s". During this time, low oil pressure, high water temperature, underspeed, charging failure, and auxiliary input (configured) alarms are invalid. After the end of safe operation delay, it will enter the “start idle delay 10s”;

4. During the start-up idling delay, the under-speed, under-frequency and under-voltage alarms are invalid. After the start-up idling delay is over, enter the "high-speed warm-up time delay 15s";

5. When the high-speed warm-up delay ends, the power generation status indicator lights if the power generation is normal. If the generator voltage and frequency reach the load requirements, the power generation closing relay outputs, the generator set is loaded, and the power supply indicator lights, and the generating set enters normal running state; if the voltage or frequency of the genset is abnormal, the controller will stop and alarm (the LCD screen displays the amount of power generation alarm);

Automatic start operation

1. Press the key to auto startset the generator set to automatic mode.

2. The LCD screen displays the countdown of "Power On Delay";

3. After the start-up delay ends, the fuel relay outputs 1s, and then the start relay outputs; if the genset does not start successfully within the "start time", the fuel relay and the start relay stop output, enter the "start interval time", and wait for the next start;

4. Within the set starting times, if the genset does not start successfully, the LCD jumps to the alarm screen, and the LCD displays an alarm of starting failure;

5. At any start, if the start is successful, enter the "safe operating time 10s". During this time, the low oil pressure, high water temperature, underspeed, charging failure, and auxiliary input (configured) alarms are invalid. After the safe running delay is over, it will enter the “start idle delay 10s”;

6. During the start-up idle speed delay, the under-speed, under-frequency, and under-voltage alarms are invalid. After the start-up idle speed delay is over, enter the "high-speed warm-up time delay 30s";

7. When the high-speed warm-up delay ends, the power generation status indicator lights if the power generation is normal. If the generator voltage and frequency meet the load requirements, the power generation closing relay outputs, the generator set is loaded, the power supply indicator lights, and the generator set enters normal running state; if the voltage or frequency of the generating set is abnormal, the controller will stop and alarm (the LCD screen displays the amount of power generation alarm);

Shutdown operation

Manual shutdown:

Method 1: Press the button generator stop to make the running genset go through stop delay  high-speed heat dissipation delay  stop idle speed delay  power stop delay  generator set stop time delay and then stop. After the generator stops, it enters the standby state of power generation; if the unit cannot stop, the controller alarms (the LCD screen displays the failure warning of stop).

Method 2: Press the "emergency stop" button on the control cabinet (used in case of emergency).

During operation

1. During mechanical operation, pay close attention to the indicator values of generator and generator set instruments, and immediately take measures or shut down after abnormalities are found.

2. During operation, maintenance and adjustment of the operating mechanism are not allowed. Do not open the power control box when transmitting power.

3. Make relevant records and shift work.

When parking

1. Check once a month. If corrosion is found, remove it in time and re-seal it.

2. Check whether the electrolyte of the battery is lacking every month.

3. Generally, diesel engine internal is not sealed, and it is started irregularly during storage to keep the inside of the cylinder dry to avoid corrosion, and the air inlet and exhaust outlet of the engine must be tightly sealed during storage to prevent moisture and dust Intrusion.


We are not only provide technical support, but also supply high quality diesel generators, if you are interested, please contact us by our sales email sherly@dieselgeneratortech.com.

Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz