The reason of fuel injector pump of genset not supply oil

Electric generator fuel supply and its speed control system mainly includes fuel injection pump, fuel injector, fuel delivery pump and regulator, etc. No matter which of the above components fails, the unit will not work normally.

Today Starlight generator manufacturer shares the reason why fuel injection pump not supply oil. Hope it is helpful to you.


Why does fuel injection pump of electric generators not supply oil?

1.There is no fuel in fuel tank or the oil switch did not open.

2.Fuel filter is blocked up.

3.There is a lot of air in the oil way.

4.Fuel injection pump plunger spring is broken.

5.Excessive wear of plunger coupling (plunger and plunger sleeve).

6.Plunger is stuck.

7.The position of the screw groove of the plunger is wrong.

8.The oil outlet valve is excessively worn or the oil outlet valve is covered with dirt.

9.The plane contact between the oil outlet valve and the plunger sleeve is not tight (if there is any impurity), which causes the diesel to leak out from the gap of the contact surface, and the fuel injection pump does not supply oil because the oil valve is not pushed out.

10.Oil outlet valve pad is broken.

 

PS: If all cylinders do not supply oil, the diesel engine will not work at all. If the individual cylinder does not supply oil, it is difficult for the diesel engine to start, that is to say, it starts and works unevenly.


 power generating sets


How to deal with the problem?

1.After finding the fault, first check whether there is fuel in the fuel tank, whether the tank switch is open, and whether the air vent of the tank is blocked.

2.If there is air bubble in the diesel oil flowing out of the vent screw, it indicates that the air has leaked into the oil circuit. The cause should be found out, which is caused by the shortage of diesel oil in the oil tank or the loosening of the oil pipe joint or the rupture of the oil pipe and the untight sealing gasket.

3.After troubleshooting, continue to pump oil by hand pump or gravity flow by diesel until there is no bubble in the diesel. Then tighten the bleed screw and hand oil pump. If the oil supply is not smooth, it means that the low-pressure oil circuit is blocked.

4.Check whether the fuel filter and the low-pressure oil circuit are blocked; if there is oil leakage in the low-pressure oil circuit, it will cause the oil to be blocked.

5.If there is no problem with the delivery pump, the problem is with the injection pump. For the combined fuel injection pump, at this time, the side cover of the fuel injection pump can be removed, the throttle handle can be placed at the stop oil supply position, the plunger spring seat of the fuel injection pump can be pried with a screwdriver, and the pump oil action can be done to check whether the plunger spring is broken and whether the plunger is stuck. At the same time, it is also necessary to check whether the screw of adjusting ring gear is loose, which will cause the change of oil supply. If they are all in good condition, then it is necessary to check the wear degree of the plunger coupling and the tightness of the oil outlet valve.

 

How to maintain the fuel injector pump of diesel generator set?

1.Use good quality diesel oil and filter to ensure that the diesel oil entering the injection pump is highly clean.

2.Always check whether the oil quantity and quality in the oil pool of the injection pump meet the requirements.

3.Regularly check and adjust the fuel supply advance angle and oil supply interval angle of each cylinder.

4.Regularly check and adjust the oil supply quantity of each cylinder of injection pump.

5.Check the camshaft clearance regularly.

6.Check the sealing condition of the valve coupling regularly.

7.Use standard high pressure tubing.

8.Regularly check the wear of relevant keyway and fixing bolt.

9.Replace the worn plunger and outlet valve coupling in time.

10.To maintain the accessories of the injection pump correctly.

 

The fuel injection pump of the diesel generator set is an important part of the fuel supply system of the diesel engine. Its working condition directly affects the power, economy and reliability of the diesel engine. Correct maintenance is an important prerequisite to ensure the normal operation and prolong the service life of fuel injection pump.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Silent Cummins 640kw Diesel Generating Sets

Technical data of 800KVA AC diesel generator set The DG Set is skid mounted, directly coupled with Cummins water cooled engine with built in shock absorber for anti vibration. The alternator is Stamford brand with brushless and self excited, with control panel and protection system complete set. Prime power: 640KW/800KVA Standby power:704KW/880KVA Rated voltage: 230/400V Rated current: 1152A Speed/frequency:1500rpm/50Hz ( or 1800rpm/60Hz) Power factory:0.8lag Size: open type genset: 4.2 x1.82x2.25m, silent genset: 6.5 x2.6 x2.78m Net wight: open type genset: 7800kg,   silent genset : 12000kg Technical Data of Diesel Engine Diesel engine brand/model: Chongqing Cummins/ KTA38-G2B( full new) Prime/standby power: 790KW/920KW 4 Stroke Cycle , 60° Vee , 12 Cylinder, Turbocharged &Aftercooled, 1500rpm, 50Hz, bore/stroke: 159/159mm. The Cummins diesel engine is equipped with electronic type governor, over speed shutdown devices to protect against runaway when electronic governor or con...

Guides to Clean VOLVO Diesel Generator Cooling System

VOLVO Engine Cooling System Volvo engine's internal cooling system makes sure the engine works at the right temperature. It is a closed system that must always be filled with a mixture of concentrated coolant and water in order to protect the engine against internal corrosion, cavitation and bursting due to freezing. Coolant of a suitable chemical composition must be used all year round. This also applies in areas where there is never any risk of freezing, to provide the engine of  diesel generator set   with full corrosion protection. The use of anti-corrosion agents alone is not permitted in Volvo Penta engines. Never use water alone as a substitute for coolant. The corrosion protection additives become less effective over time, which means that the coolant must be changed at regular intervals; refer to Maintenance Schedule. The cooling system must be flushed whenever the coolant is changed; Volvo Penta coolants have been prepared to work best ...