Coolant Temperatures of Diesel Generator Set

Today Starlight Power manufacturer talks about coolant temperatures of diesel generator set.

Summer temperatures are high and temperatures are more unusual this summer. Some high temperatures reach 44.5°. The coolant of the diesel generator rises rapidly during such high temperature seasons. Diesel engines are prone to cylinder accidents at 100 ° water temperature and high temperature, so diesel generators should stop working or reduce the load when the coolant exceeds 95 °.

The water temperature of the diesel generator set is preferably around 80°, and the maximum temperature cannot exceed 95°! Remember not to let the temperature be too high or too low, it will cause damage to the generator set.

 

1. Improper use of coolant or insufficient water. The diesel engine used in construction machinery generally has a higher working temperature. The antifreeze can ensure its high boiling point and reduce the scale generated by the cooling system. If the cooling system is not removed, or the coolant is not replenished in time, the cooling performance will be degraded. To raise the temperature of the coolant.

 


2. The water radiator is blocked. For example, the heat sink of the water radiator has a large area of lodging, and there are oil and mud debris between the heat sinks, which will prevent the heat from being emitted. Especially when the surface of the water radiator is contaminated with organic oil, the thermal conductivity of the sludge mixture formed by the dust and the oil is smaller than that of the scale, which seriously hinders the heat dissipation effect. At this point, use a thin steel sheet to carefully return the heat sink to its original position, restore the flat shape of the heat sink, and then use compressed air or a water gun to clean it. If the water is heated and put into the cleaning solution, sneeze, the effect is better.

3. The water temperature gauge or warning light is incorrectly indicated. Including the water temperature sensor is damaged; the line is ironed or the indicator is out of order, resulting in false alarm. At this time, the surface thermometer can be used to measure the temperature at the water temperature sensor, and it is observed whether the water temperature gauge indicates the actual temperature.

4. The fan speed is too low and the blade is deformed or reversed. If the fan tape is too loose, it will slip, causing the fan speed to be too low and the air supply effect to be weakened. If the tape is too loose, it should be adjusted. If the rubber layer is aged, damaged or the fiber layer is broken, it should be replaced. When the fan blade is deformed, it can be compared with the new blade of the same specification to see if the angle between the blade and the relative rotation plane becomes smaller. If the angle is too small, the air supply strength will be insufficient.

5. The cooling water pump is faulty. The pump itself is damaged, the rotation speed is too low, the scale in the pump body is excessively deposited, and the narrowing of the passage will make the flow rate of the coolant smaller, the heat dissipation performance is lowered, and the temperature of the diesel engine oil is increased.

6. The thermostat is faulty. The function of the thermostat is to control the size cycle of the cooling system. When the thermostat is working at about 85 degrees, the valve starts to open, and the valve is fully opened at about 105 degrees. The method of checking the thermostat is to remove the thermostat, suspend it in a container filled with warm water, and place a thermometer in the water, then heat it from the bottom of the container to observe that the thermostat valve starts to open and If the water temperature is completely turned on, if the above requirements are not met or there is obvious damage, the thermostat should be replaced immediately.

7. The cylinder head gasket is damaged. If the cylinder head is burned by the high temperature gas, the high pressure gas will rush into the cooling system to make the coolant roll and boil. The method of judging whether the cylinder head is burnt is: turning off the diesel engine, waiting for a while, then restarting the diesel engine and increasing the speed. If at this time, the water radiator cap can be seen to have a large number of bubbles emerging, and at the same time, there is a small water droplet in the exhaust pipe discharged with the exhaust gas, it can be concluded that the cylinder head gasket is damaged.

8. Inappropriate fuel injection time. The injector is not working well. If the fuel supply advance angle is too early or delayed, the contact area of the high temperature gas with the cylinder wall increases during combustion, and the time is prolonged, and the heat transferred to the coolant increases, and the temperature of the coolant rises. At this time, there is a phenomenon that the power of the diesel engine is lowered and the fuel consumption is increased. If the fuel injection pressure of the injector drops, the fog will be poor, and the fuel will not be completely burned. The increase of the exhaust temperature will indirectly lead to an increase in the water temperature.

9. The diesel engine is overloaded. When the diesel engine is overloaded, it will cause too much oil supply. When the generated heat exceeds the heat dissipation capacity of the diesel engine, the temperature of the coolant of the diesel engine will also rise. At this time, the diesel engine has more black smoke, increased fuel consumption, and abnormal sound.

Starlight Power not only supply technical support, but also supply diesel power generators from 20kw to 2200kw, if you are interested, please contact us by email sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz