Coolant Temperatures of Diesel Generator Set

Today Starlight Power manufacturer talks about coolant temperatures of diesel generator set.

Summer temperatures are high and temperatures are more unusual this summer. Some high temperatures reach 44.5°. The coolant of the diesel generator rises rapidly during such high temperature seasons. Diesel engines are prone to cylinder accidents at 100 ° water temperature and high temperature, so diesel generators should stop working or reduce the load when the coolant exceeds 95 °.

The water temperature of the diesel generator set is preferably around 80°, and the maximum temperature cannot exceed 95°! Remember not to let the temperature be too high or too low, it will cause damage to the generator set.

 

1. Improper use of coolant or insufficient water. The diesel engine used in construction machinery generally has a higher working temperature. The antifreeze can ensure its high boiling point and reduce the scale generated by the cooling system. If the cooling system is not removed, or the coolant is not replenished in time, the cooling performance will be degraded. To raise the temperature of the coolant.

 


2. The water radiator is blocked. For example, the heat sink of the water radiator has a large area of lodging, and there are oil and mud debris between the heat sinks, which will prevent the heat from being emitted. Especially when the surface of the water radiator is contaminated with organic oil, the thermal conductivity of the sludge mixture formed by the dust and the oil is smaller than that of the scale, which seriously hinders the heat dissipation effect. At this point, use a thin steel sheet to carefully return the heat sink to its original position, restore the flat shape of the heat sink, and then use compressed air or a water gun to clean it. If the water is heated and put into the cleaning solution, sneeze, the effect is better.

3. The water temperature gauge or warning light is incorrectly indicated. Including the water temperature sensor is damaged; the line is ironed or the indicator is out of order, resulting in false alarm. At this time, the surface thermometer can be used to measure the temperature at the water temperature sensor, and it is observed whether the water temperature gauge indicates the actual temperature.

4. The fan speed is too low and the blade is deformed or reversed. If the fan tape is too loose, it will slip, causing the fan speed to be too low and the air supply effect to be weakened. If the tape is too loose, it should be adjusted. If the rubber layer is aged, damaged or the fiber layer is broken, it should be replaced. When the fan blade is deformed, it can be compared with the new blade of the same specification to see if the angle between the blade and the relative rotation plane becomes smaller. If the angle is too small, the air supply strength will be insufficient.

5. The cooling water pump is faulty. The pump itself is damaged, the rotation speed is too low, the scale in the pump body is excessively deposited, and the narrowing of the passage will make the flow rate of the coolant smaller, the heat dissipation performance is lowered, and the temperature of the diesel engine oil is increased.

6. The thermostat is faulty. The function of the thermostat is to control the size cycle of the cooling system. When the thermostat is working at about 85 degrees, the valve starts to open, and the valve is fully opened at about 105 degrees. The method of checking the thermostat is to remove the thermostat, suspend it in a container filled with warm water, and place a thermometer in the water, then heat it from the bottom of the container to observe that the thermostat valve starts to open and If the water temperature is completely turned on, if the above requirements are not met or there is obvious damage, the thermostat should be replaced immediately.

7. The cylinder head gasket is damaged. If the cylinder head is burned by the high temperature gas, the high pressure gas will rush into the cooling system to make the coolant roll and boil. The method of judging whether the cylinder head is burnt is: turning off the diesel engine, waiting for a while, then restarting the diesel engine and increasing the speed. If at this time, the water radiator cap can be seen to have a large number of bubbles emerging, and at the same time, there is a small water droplet in the exhaust pipe discharged with the exhaust gas, it can be concluded that the cylinder head gasket is damaged.

8. Inappropriate fuel injection time. The injector is not working well. If the fuel supply advance angle is too early or delayed, the contact area of the high temperature gas with the cylinder wall increases during combustion, and the time is prolonged, and the heat transferred to the coolant increases, and the temperature of the coolant rises. At this time, there is a phenomenon that the power of the diesel engine is lowered and the fuel consumption is increased. If the fuel injection pressure of the injector drops, the fog will be poor, and the fuel will not be completely burned. The increase of the exhaust temperature will indirectly lead to an increase in the water temperature.

9. The diesel engine is overloaded. When the diesel engine is overloaded, it will cause too much oil supply. When the generated heat exceeds the heat dissipation capacity of the diesel engine, the temperature of the coolant of the diesel engine will also rise. At this time, the diesel engine has more black smoke, increased fuel consumption, and abnormal sound.

Starlight Power not only supply technical support, but also supply diesel power generators from 20kw to 2200kw, if you are interested, please contact us by email sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...