How to maintenance lubricating oil system of 600KW diesel generator

 

Today Starlight Power manufacturer shares how to maintenance lubricating oil system of diesel generator, hope it is helpful to you.


In order to let diesel generator set work normally, we need to pay attention to some items as follows:


1.Select suitable lubricating oil.

In general, every diesel engine manual requires the type of lubricating oil for diesel engine. If we can not buy a same type of lubricating oil required in the manual, we can buy a similar brand lubricating oil. Remember do not use different  lubricating oil.


2.Check the quality of engine oil during the use of diesel generator set.

A)Check mechanical impurities in engine oil when heating engine, take out the oil dipstick for inspection. If there are fine particles on the scale or the scale line cannot be seen clearly, it means that there are too many impurities in the oil. The oil should be replaced and the oil filter should be cleaned.


B)To check the oil viscosity, it is commonly used to twist the oil on the fingers. If there is a feeling of stickiness and stretching, it indicates that the oil viscosity is appropriate, otherwise it means that the oil viscosity is not enough. The accurate inspection method is to use the viscometer to measure.


 electric generators


3.The oil quantity should be appropriate.

Check the oil level before each startup to ensure that the oil level is within the specified range. When the oil level is too low, it is easy to burn the bush and pull the cylinder. The engine oil should be added in time, and the oil level should be within the specified range. When the oil level is too high, it is easy to cause the engine oil to enter the cylinder, the combustion chamber will deposit carbon, the piston ring will stick, and the exhaust will emit blue smoke. At this time, check whether there is water and fuel leakage in the engine oil, find out the causes, eliminate and replace the oil.


4.The oil pressure should be adjusted properly.

Each type of diesel engine has its own specified oil pressure. When the engine is started to rated speed or medium speed, the oil pressure should rise to the specified value within 1 minute, otherwise, the cause should be found out. Generally, diesel generator has oil pressure regulating screw, we can adjust it according to different specifications.


5.Clean the lubrication system and change the oil regularly.

A)The oil filter is cleaned regularly; the oil basin and oil passage are generally carried out when the oil is changed.

B)Cleaning method:

Drain the engine oil when the engine is hot, so as to remove the impurities in the oil pan, oil passage and oil filter as much as possible. Put the mixed oil (15% ~ 20% kerosene or diesel oil: engine oil = 9:1) in the oil pan, the suitable quantity is 60% ~ 70% of the capacity of the lubrication system, run the diesel engine at low speed for 5 to 8 minutes (oil pressure above 0.5 kgf/cm2), then shut down, drain the mixed oil, clean the oil filter, filter screen, oil radiator and crankcase, and add new oil.

 

If the oil pressure is too high, the oil circuit is easy to leak and crack; if the oil pressure is too low, the oil supply will not be smooth, resulting in poor lubrication and increasing wear of diesel engine. Similarly, too low or too high oil temperature will also bring adverse consequences. Too high oil temperature will cause oxidation and deterioration of engine oil, decrease of viscosity, unreliable lubrication and increase of wear of parts; if oil temperature is too low, viscosity will increase, friction resistance will increase, and oil cooling effect will be poor.

 

6.Replace the oil filter element and oil filter regularly.

Replace or clean the filter element and filter screen regularly, and pay attention to cleaning the lubricating oil circuit. The replacement cycle of these materials is different for filter elements and filters of different quality and in different service environments. In addition to referring to the service life specified by the product itself, in the maintenance and maintenance process of the lubricating system, if the quality of the engine oil becomes poor or the working condition of the diesel engine is deteriorated due to engine oil, it is necessary to check whether the filter element or filter needs to be replaced.

 

The engine oil will deteriorate after using for a period of time and cannot be used again. Under normal circumstances, the oil, oil filter element or oil filter must be replaced within 50 hours of the new machine. After the running in period, the engine oil is generally changed once every 300 hours.

 

Starlight Power is a manufacturer of electric generators, founded in 1974. Product covers Cummins, Perkins, Volvo, Yuchai, Shangchai, Weichai, Ricardo, Doosan, Deutz, etc. Power range is from 20kw to 3000kw, with open type, soundproof type, trailer type, container type. Welcome to contact us by email sales@dieselgeneratortech.com, if you want to buy diesel generator set.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Silent Cummins 640kw Diesel Generating Sets

Technical data of 800KVA AC diesel generator set The DG Set is skid mounted, directly coupled with Cummins water cooled engine with built in shock absorber for anti vibration. The alternator is Stamford brand with brushless and self excited, with control panel and protection system complete set. Prime power: 640KW/800KVA Standby power:704KW/880KVA Rated voltage: 230/400V Rated current: 1152A Speed/frequency:1500rpm/50Hz ( or 1800rpm/60Hz) Power factory:0.8lag Size: open type genset: 4.2 x1.82x2.25m, silent genset: 6.5 x2.6 x2.78m Net wight: open type genset: 7800kg,   silent genset : 12000kg Technical Data of Diesel Engine Diesel engine brand/model: Chongqing Cummins/ KTA38-G2B( full new) Prime/standby power: 790KW/920KW 4 Stroke Cycle , 60° Vee , 12 Cylinder, Turbocharged &Aftercooled, 1500rpm, 50Hz, bore/stroke: 159/159mm. The Cummins diesel engine is equipped with electronic type governor, over speed shutdown devices to protect against runaway when electronic governor or con...

Guides to Clean VOLVO Diesel Generator Cooling System

VOLVO Engine Cooling System Volvo engine's internal cooling system makes sure the engine works at the right temperature. It is a closed system that must always be filled with a mixture of concentrated coolant and water in order to protect the engine against internal corrosion, cavitation and bursting due to freezing. Coolant of a suitable chemical composition must be used all year round. This also applies in areas where there is never any risk of freezing, to provide the engine of  diesel generator set   with full corrosion protection. The use of anti-corrosion agents alone is not permitted in Volvo Penta engines. Never use water alone as a substitute for coolant. The corrosion protection additives become less effective over time, which means that the coolant must be changed at regular intervals; refer to Maintenance Schedule. The cooling system must be flushed whenever the coolant is changed; Volvo Penta coolants have been prepared to work best ...