How to maintenance lubricating oil system of 600KW diesel generator

 

Today Starlight Power manufacturer shares how to maintenance lubricating oil system of diesel generator, hope it is helpful to you.


In order to let diesel generator set work normally, we need to pay attention to some items as follows:


1.Select suitable lubricating oil.

In general, every diesel engine manual requires the type of lubricating oil for diesel engine. If we can not buy a same type of lubricating oil required in the manual, we can buy a similar brand lubricating oil. Remember do not use different  lubricating oil.


2.Check the quality of engine oil during the use of diesel generator set.

A)Check mechanical impurities in engine oil when heating engine, take out the oil dipstick for inspection. If there are fine particles on the scale or the scale line cannot be seen clearly, it means that there are too many impurities in the oil. The oil should be replaced and the oil filter should be cleaned.


B)To check the oil viscosity, it is commonly used to twist the oil on the fingers. If there is a feeling of stickiness and stretching, it indicates that the oil viscosity is appropriate, otherwise it means that the oil viscosity is not enough. The accurate inspection method is to use the viscometer to measure.


 electric generators


3.The oil quantity should be appropriate.

Check the oil level before each startup to ensure that the oil level is within the specified range. When the oil level is too low, it is easy to burn the bush and pull the cylinder. The engine oil should be added in time, and the oil level should be within the specified range. When the oil level is too high, it is easy to cause the engine oil to enter the cylinder, the combustion chamber will deposit carbon, the piston ring will stick, and the exhaust will emit blue smoke. At this time, check whether there is water and fuel leakage in the engine oil, find out the causes, eliminate and replace the oil.


4.The oil pressure should be adjusted properly.

Each type of diesel engine has its own specified oil pressure. When the engine is started to rated speed or medium speed, the oil pressure should rise to the specified value within 1 minute, otherwise, the cause should be found out. Generally, diesel generator has oil pressure regulating screw, we can adjust it according to different specifications.


5.Clean the lubrication system and change the oil regularly.

A)The oil filter is cleaned regularly; the oil basin and oil passage are generally carried out when the oil is changed.

B)Cleaning method:

Drain the engine oil when the engine is hot, so as to remove the impurities in the oil pan, oil passage and oil filter as much as possible. Put the mixed oil (15% ~ 20% kerosene or diesel oil: engine oil = 9:1) in the oil pan, the suitable quantity is 60% ~ 70% of the capacity of the lubrication system, run the diesel engine at low speed for 5 to 8 minutes (oil pressure above 0.5 kgf/cm2), then shut down, drain the mixed oil, clean the oil filter, filter screen, oil radiator and crankcase, and add new oil.

 

If the oil pressure is too high, the oil circuit is easy to leak and crack; if the oil pressure is too low, the oil supply will not be smooth, resulting in poor lubrication and increasing wear of diesel engine. Similarly, too low or too high oil temperature will also bring adverse consequences. Too high oil temperature will cause oxidation and deterioration of engine oil, decrease of viscosity, unreliable lubrication and increase of wear of parts; if oil temperature is too low, viscosity will increase, friction resistance will increase, and oil cooling effect will be poor.

 

6.Replace the oil filter element and oil filter regularly.

Replace or clean the filter element and filter screen regularly, and pay attention to cleaning the lubricating oil circuit. The replacement cycle of these materials is different for filter elements and filters of different quality and in different service environments. In addition to referring to the service life specified by the product itself, in the maintenance and maintenance process of the lubricating system, if the quality of the engine oil becomes poor or the working condition of the diesel engine is deteriorated due to engine oil, it is necessary to check whether the filter element or filter needs to be replaced.

 

The engine oil will deteriorate after using for a period of time and cannot be used again. Under normal circumstances, the oil, oil filter element or oil filter must be replaced within 50 hours of the new machine. After the running in period, the engine oil is generally changed once every 300 hours.

 

Starlight Power is a manufacturer of electric generators, founded in 1974. Product covers Cummins, Perkins, Volvo, Yuchai, Shangchai, Weichai, Ricardo, Doosan, Deutz, etc. Power range is from 20kw to 3000kw, with open type, soundproof type, trailer type, container type. Welcome to contact us by email sales@dieselgeneratortech.com, if you want to buy diesel generator set.

Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz