The reason of electric generator tripping

 

Tripping phenomenon

A.If diesel genset operates under rated conditions for a few minutes, the automatic air switch trips, after recloses, then trips a few minutes later with a burning odor.

The cause:

The main contact of the automatic air switch is not well contacted or the spring pressure is insufficient. and the lead-out wire of the switch is not well contacted. The above two reasons will increase the contact resistance of the main circuit of the automatic air switch and cause serious fever, which will lead to the action of the thermal release and lead to wrong tripping.

Methods of resolution:

At this time, we should clean the main contacts of the automatic air switch and flatten them with a fine file or fine sandpaper; Adjust contact spring pressure to make good contact; clean contacts, apply conductive paste if necessary, and lock connection screw.

B.Diesel generator trips immediately after connecting load.

After the unit starts, the generator terminal voltage is normal, but when the external circuit is connected, the load automatic air switch will trip immediately.

The causes:

External circuit short circuit and too heavy load.

Methods of resolution:

Find out the short circuit point of the external circuit and repair it. Reduce load to reduce load current output of generators.

But when we do not know what is causes of genset tip, what should do? After power generator set tripping, first check genset to judge the cause of this trip, and then take appropriate measures, the specific steps are as follows:

1.Check whether there is a problem of wrong operation, and whether the secondary circuit will cause tripping;

2.When the main circuit breaker at the outlet of transformer set of generator trips automatically, first check whether the generator indicator has any obvious fault symbols, if have, should cut off the excitation immediately; if not abnormal symbol, under the situation of good furnace condition, the electrical attendant should adjust the generator voltage and frequency in the normal range, check whether the high-voltage auxiliary power with the generator set trips, whether the start-up transformer is put into linkage, and whether the auxiliary power is normal;

3.According to accident phenomena, to judge the nature and scope of the fault, and clearly inspect the external of transformer set of generator and related equipment, to identify whether there are external fault characteristics;

4.Need to pay attentions, If switch tripping occurs in incomplete phase, need to remove start of switch protection failure; if it is not failure protection problem, it is necessary to open all switches connected to the same bus in time;

5.If because of busbar differential protection operation, or generator is over-current protection and other over-step tripping due to faults in substations, check the generator's external, it is normal, after fault isolation, the connection network is adjusted and connected to the grid;

6.Before tripping, if there is forced excitation and current shock. Reflecting the main protection (differential, heavy mashgas, etc.) action of the internal faults of generator-transformer unit, while the power grid is running normally, should shut down at this time;

7.And that’s another one that will quickly shut down a generator: alternator or prime mover over-temperature, as heat causes lubrication to break down and bearings to swell, increasing friction, causing more heat, and potential total failure or more fire;

8.If there is no strong excitation action and no impulse current before tripping, the operation of power grid is also normal. The generator's hydro-oil system and main transformer are also normal. The following treatment should be done: check the generator and its circuit, check the protection of the action, if all is normal, generator can be boosted at zero. When boosting, if everything is normal, the generator can be connected to the grid, and then continue to find out the reasons. When boosting, the strong excitation and automatic adjustment device shall not be put into operation. The neutral point of the high-voltage side of the generator-transformer unit shall be grounded. If abnormal phenomena are found, the generator-transformer unit shall be stopped immediately for inspection.

If it is found that the tripping is not caused by the failure of diesel generator set, it may be caused by the wrong operation of the relevant personnel. At this time, the demagnetization switch is often still in the closing position. Operators should first manually trip the demagnetization switch and immediately re-connect generator set to the grid.

Starlight diesel generator set covers Cummins, Perkins, Volvo, Yuchai, Shangchai, Ricardo, MTU, Weichai etc. If you have purchase plan recently, please feel free to contact us by email sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Silent Cummins 640kw Diesel Generating Sets

Technical data of 800KVA AC diesel generator set The DG Set is skid mounted, directly coupled with Cummins water cooled engine with built in shock absorber for anti vibration. The alternator is Stamford brand with brushless and self excited, with control panel and protection system complete set. Prime power: 640KW/800KVA Standby power:704KW/880KVA Rated voltage: 230/400V Rated current: 1152A Speed/frequency:1500rpm/50Hz ( or 1800rpm/60Hz) Power factory:0.8lag Size: open type genset: 4.2 x1.82x2.25m, silent genset: 6.5 x2.6 x2.78m Net wight: open type genset: 7800kg,   silent genset : 12000kg Technical Data of Diesel Engine Diesel engine brand/model: Chongqing Cummins/ KTA38-G2B( full new) Prime/standby power: 790KW/920KW 4 Stroke Cycle , 60° Vee , 12 Cylinder, Turbocharged &Aftercooled, 1500rpm, 50Hz, bore/stroke: 159/159mm. The Cummins diesel engine is equipped with electronic type governor, over speed shutdown devices to protect against runaway when electronic governor or con...

Guides to Clean VOLVO Diesel Generator Cooling System

VOLVO Engine Cooling System Volvo engine's internal cooling system makes sure the engine works at the right temperature. It is a closed system that must always be filled with a mixture of concentrated coolant and water in order to protect the engine against internal corrosion, cavitation and bursting due to freezing. Coolant of a suitable chemical composition must be used all year round. This also applies in areas where there is never any risk of freezing, to provide the engine of  diesel generator set   with full corrosion protection. The use of anti-corrosion agents alone is not permitted in Volvo Penta engines. Never use water alone as a substitute for coolant. The corrosion protection additives become less effective over time, which means that the coolant must be changed at regular intervals; refer to Maintenance Schedule. The cooling system must be flushed whenever the coolant is changed; Volvo Penta coolants have been prepared to work best ...