Underloading Diesel and Gas Generator Sets





System health and reliability are critical to backup and prime power solutions for any installationfrom mission critical data centers to neighborhood grocery stores. While power systems vary in operation, application and load profile, theyre all designed to provide reliable power and maximized efficiency. The generator set is a key piece of the power system that requires special attention for long-term system reliability, availability and uptime. To achieve these, its important to understand system operation, load profile and required maintenance. This blog will focus on generator set operation in low-load scenarios, and what can result if they are used outside of specific parameters.



First, it is important to understand that generator sets are designed to run with load. This may seem trivial, but loading a generator set properly is essential to availability and a long engine life. Manufacturer service intervals and projected component life are based on operation in load ranges to deliver an ideal mix of product performance, power density and long-term operational life.



Incorrect generator set operation can result in reduced output, component damage, reduced lifecycles, and unscheduled downtime. The ideal operation targets of each generator set will depend on the application and rating.



Underloading Diesel Generator Sets



Generally speaking, standby- and prime-rated diesel generator sets are designed to operate between 50 and 85 percent load, while continuous-rated diesel generator sets optimize between 70 and 100 percent load. Operating diesel generator sets at loads less than 30 percent for extended periods can impact uptime and engine life.



The most prevalent consequence of underloading is exhaust manifold slobber, or wet stacking, which is the black oily liquid that can leak from the exhaust joints when the engine does not reach minimum temperatures and pressures. Visible engine slobber doesnt necessarily indicate a problem, but it signals possible underloading concerns, low ambient temperatures or jacket water temperatures that are too low. Additionally, long periods of light loading can lead to deposit build-up behind the piston rings or inside the cylinders, which can cause power loss, poor performance, accelerated wear and in extreme cases, cylinder liner polishing.



Underloading Gas Generator Sets



Natural gas and biogas generator sets, independent of application and rating, are typically designed for operation between 60 and 100 percent load. Without enough cylinder pressure to maintain oil control at low loads, gas engines can develop ash deposits, a reduced detonation margin and damaged engine components. Similar to diesel generator sets, deposit build-up on valves, spark plugs and behind piston rings can occurwhich may cause cylinder liner polishing, power loss, poor performance and accelerated component wearultimately increasing the likelihood of higher maintenance costs and downtime.



Managing Low Load



If maintained properly, diesel and gas generator sets can operate at light loads for long periods without harmful effects. After underloading, the generator sets should run at increased load to raise the cylinder pressure and temperature, which will clean the deposits from the combustion chamber. Regular low load operation requires a more aggressive maintenance plan to reduce excessive component wear and may require engine modification.


Diesel engines should run at a minimum of 30 percent load for about 30 minutes for every four hours of light-load operation, and operators should measure exhaust temperature prior to the turbo for analysis. Natural gas engines are more sensitive to low loads, so there are specific underloading time limits required to maintain optimal performance, see the chart above. After the time limit has expired, the engine should run at a minimum of 70 percent load for at least two hours.



Power system underloading impacts individual components as well as overall performance, so it should not be taken lightly. While the simple solution is to operate generator sets at a load that meets design requirements, the reality is that system needs sometimes change. This makes underloading common in the realm of power generationespecially in standby applications. However, the effects of underloading can be minimized with a thorough operation and maintenance plan to preserve system health and avoid extra costs down the road.

Comments

  1. Nice blog !! Thanks for sharing valuable information. We are provided Best diesel generator in bangladesh at affordable Price. Call Now +88 01751-452686

    ReplyDelete
    Replies
    1. Thanks. We are a manufacturer of diesel generator set in China, our factory was set up in 1974. If you need to purchase, contact us : sherly@dieselgeneratortech.com

      Delete
  2. Very helpful blog. Thanks for sharing such a useful information. Silent DG sets are used in places that have no connection to power grid, and as emergency power-supply if the grid fails.

    ReplyDelete

Post a Comment

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Silent Cummins 640kw Diesel Generating Sets

Technical data of 800KVA AC diesel generator set The DG Set is skid mounted, directly coupled with Cummins water cooled engine with built in shock absorber for anti vibration. The alternator is Stamford brand with brushless and self excited, with control panel and protection system complete set. Prime power: 640KW/800KVA Standby power:704KW/880KVA Rated voltage: 230/400V Rated current: 1152A Speed/frequency:1500rpm/50Hz ( or 1800rpm/60Hz) Power factory:0.8lag Size: open type genset: 4.2 x1.82x2.25m, silent genset: 6.5 x2.6 x2.78m Net wight: open type genset: 7800kg,   silent genset : 12000kg Technical Data of Diesel Engine Diesel engine brand/model: Chongqing Cummins/ KTA38-G2B( full new) Prime/standby power: 790KW/920KW 4 Stroke Cycle , 60° Vee , 12 Cylinder, Turbocharged &Aftercooled, 1500rpm, 50Hz, bore/stroke: 159/159mm. The Cummins diesel engine is equipped with electronic type governor, over speed shutdown devices to protect against runaway when electronic governor or con...

Guides to Clean VOLVO Diesel Generator Cooling System

VOLVO Engine Cooling System Volvo engine's internal cooling system makes sure the engine works at the right temperature. It is a closed system that must always be filled with a mixture of concentrated coolant and water in order to protect the engine against internal corrosion, cavitation and bursting due to freezing. Coolant of a suitable chemical composition must be used all year round. This also applies in areas where there is never any risk of freezing, to provide the engine of  diesel generator set   with full corrosion protection. The use of anti-corrosion agents alone is not permitted in Volvo Penta engines. Never use water alone as a substitute for coolant. The corrosion protection additives become less effective over time, which means that the coolant must be changed at regular intervals; refer to Maintenance Schedule. The cooling system must be flushed whenever the coolant is changed; Volvo Penta coolants have been prepared to work best ...