Volvo generators can start but not generate electricity

Why can Volvo generator start but not generate electricity? Today Starlight Power manufacturer shares with you, all the answers are in this article, hope our sharing is helpful to you.

Here is some reasons for reference:
1.After the diesel generator is stopped, the residual magnetism is often lost, because the material used for the magnetic pole of the exciter is close to the soft steel, and the residual magnetism is small. After the shutdown, when there is no current in the excitation winding, the magnetic field will disappear.
2.The magnetic pole of the diesel generator loses its magnetic properties.
3.Damage of excitation circuit components or circuit breakage, short circuit or grounding phenomena.
4.The exciter brush is not in good contact with the commutator and pressure of brush holder is insufficient.
5.Excitation winding wiring error, opposite polarity.
6.Stator winding and rotor winding of generator set open circuit.
7.Poor contact between diesel generator brush and slip ring, or insufficient brush pressure.
8.Diesel generator lead wire wiring is loose or switch contact is poor.
9.The fuse box is fused.
10.The "auto-manual-de-excitation" switch on the control panel is in the de-excitation position (automatic generator set has "auto-manual-de-excitation" switch).
11.The voltmeter is damaged.
12.Rotary rectifier module is damaged.

 Volvo diesel power generator

Methods of resolution:
1.We can have a battery and magnetize it before generating electricity.
2.Magnetize in the winding with a DC current which is greater than the rated current (short time).
3.Replace damaged components and repair faulty lines.
4.Remove the scale on the contact surface, adjust the brush pressure, and fasten the brush holder.
5.Correct the wiring and press the correct polarity to magnetize.
6.Remove the scale on contact surface, grind the brush, adjust the pressure of the brush, and make the brush in close contact with the slip ring.
7.Check and repair the break circuit position.
8.Connect the connector or repair the switch contact part.
9.Find out the cause of the fuse, and determine that the generator itself and the line are normal, replace the specified fuse.
In order to avoid diesel generators failling to generate electricity, here are some ways to check before start up the diesel genset:
1.Measure whether there is real electricity and replace the voltmeter.
2.Put it into automatic or manual mode.
3.Check and correct according to circuit diagram.
4.New generators or long-term unused generators can not easily produce electricity, it can be magnetized by pressing the charge button on the control panel or by using 12V battery to magnetize the excitation winding, the positive pole is connected to F1 and the negative pole is connected to F2. If there still is not electric pressure, we should adjust positive pole and negative pole, then try again.  
5.Clear collecting ring surface, sanding the end face of the carbon brush to make the area of the arc of the collector ring more than 70%, strengthen sparing pressure.
6.Clean carbon brush and carbon brush grip.
7.Check the diode forward and reverse resistance with a multimeter, if it is damaged, replace it.
8.Check with a multimeter, if the forward reverse resistors do not meet the diode characteristics, we need to replace new forward reverse resistors.
9.For diesel generator set, check the winding with 1K gear of multimeter, if the resistance value is infinite, it should be connected. Then check with 1 Ω gear of multimeter, if the resistance value is zero, we should replace or repair the windings. If the resistance value is not stable, check if the connector wiring is loose, if it is loose, need to screw it.

Starlight Volvo diesel power generators are approved by CE and ISO certificates, its quality is very good, maybe sometimes we meet it can not produce electricity, for other brands of diesel generators, they may also have this fault. So this article will be greater to help you to avoid and resolve the fault.

We are a manufacturer of diesel generator sets, our factory was set up in 1974, we have focused on high quality products for more than 40 years, we not only supply diesel generators, but also provide power solutions and technical supports. Welcome to inquire us by contacting sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz