Foundation requirements of 500kw diesel generator set

What are requirements of diesel generator set foundation? 500kw diesel generator set manufacturer answers for you.

Diesel generator set is an indispensable emergency equipment, which is required for the installation environment. The foundation of diesel generator set shall be built on the hard soil ground, a 200mm thick concrete ground shall be made, and the ground shall be flat. After leveling, the unit shall be placed on the foundation to make each fulcrum contact evenly. The uneven expenditure can be padded with sheet steel or rubber. Finally, the pressing plate or bolt shall be used for fastening, and no looseness is allowed in use.

The foundation structure of diesel generator set shall be determined according to the soil structure of the foundation. Generally, the foundation depth is 0.7-1m, and the foundation can be 150 mm higher than the plane or as flat as the plane. The length and width of the foundation are 200 mm larger than the length and width of the baseplate.

The foundation bottom shall be solid. When pouring concrete, the fixed anchor hole shall be reserved according to the position of the fixed hole of the base. The hole size is 120x120mm, the hole bottom size is 160x160mm, and the hole depth is 450mm for fixing bolts (the fixing bolt is M18).

generator foundation
The generator set can use the foot hole of the common chassis as the fixed installation, or it can also use the press plate type installation. When the press plate type is fixed, the width of the foundation foot hole shall be calculated and widened.

The space around the diesel generator set shall not be less than 1 m, and the ventilation window shall be reserved at the water tank end according to the size of the water tank core. This requirement is the minimum size of the machine room of the unit, which can be increased by the user as required.
For open type diesel generators, the machine room shall be well ventilated and the ground shall be flat and antiskid. Fire fighting tools such as fire extinguishers shall be provided in the machine room.

For generators requiring direct neutral grounding, the generating set shell must have reliable protective grounding.
The layout of various pipelines such as ventilation, water supply and drainage, oil supply, smoke exhaust and cables shall be carefully considered in the layout of generator unit equipment. The length of pipelines shall be minimized to avoid crossing and bending.
The layout of the diesel generator set shall meet the requirements of the process, pay attention to noise reduction, vibration isolation, ventilation and heat dissipation, and shall be equipped with facilities to ensure lighting and fire protection, so as to be neat and beautiful, and strive to create good use conditions and operation environment.

The area of the machine room should be considered according to the number of units, power and future expansion. On the premise of meeting the requirements, the construction area of the power station shall be reduced as much as possible to achieve economic rationality.
In order to ensure the safe and reliable operation of the unit, the machine room shall be provided with thermal insulation measures, and the heating and cooling of the machine room shall preferably be carried out by heating or air conditioning.

The best scheme of unit installation is to place and fix the unit with concrete foundation, which can make the unit run stably and reduce vibration.

The concrete foundation shall meet the following requirements:
1.The bearing weight of concrete foundation shall be designed as 1.5 times of the self weight of the unit, so as to support the weight of the whole unit and the dynamic impact load generated by the unbalanced force during the operation of the unit;
2.The subsoil under the concrete foundation must also have enough bearing strength to bear the weight of the unit and the concrete foundation;
3.The concrete foundation shall be as smooth as possible, with enough hardness and stability, so as to avoid affecting the coaxiality of diesel engine, main alternator and accessories due to its deformation;
4.The concrete foundation shall have the function of shock absorption, which can greatly absorb the vibration generated during the operation of the unit, and try to avoid transmitting vibration to the foundation and walls. For example, if the unit is installed on the floor of the building, it is recommended to install a spring shock absorber between the unit base and the concrete foundation;
5.During the construction of concrete foundation, the power distribution and output cable trench of generator shall be reserved, if possible, the drainage trench can be reserved to facilitate the discharge of waste water and oil;
6.The concrete foundation is a reliable and simple installation method, which is recommended to be used by users first. When pouring the concrete foundation, the surface of the concrete shall be smooth and free from any damage. It is recommended that the user use a level meter or similar instrument to install the unit and its exhaust system.

Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...