What is phenomenon when the rotating rectifier failure of generator?

After using for a certain period of time, the rotating rectifier of diesel generator set maybe break down, which often leads to the failure of normal operation of the whole generator set.

What is the function of rotating rectifier of diesel generator set?
Rotating rectifier is a device which rotates coaxially with AC exciter. Its main function is to convert the three-phase AC excitation current output by the armature of the AC exciter into the DC current through the diode on the rectifier, supply the rotor winding as the power supply for the excitation current. It is because of the application of rotating rectifier that the AC synchronous generator gets rid of the binding of brush, no longer has the trouble of frequent maintenance and replacement of parts, and also makes the application of the AC synchronous generator more extensive.

silent generators

Some rotating rectifiers of AC synchronous generators are installed on the outside of the AC exciter and fixed on the shaft with screws for easy installation and maintenance. Some rotating rectifiers of generators are installed on the inner side of the rear end cover and directly fixed on the bolts protruding from the armature core of the exciter, making the structure more compact. There are two kinds of rotating rectifier circuits: three-phase half wave and three-phase bridge rectifier. If the three-phase bridge rectifier circuit is adopted, in order to facilitate installation, reduce the connection line between the rectifier elements and improve the reliability of the generator operation, the rectifier diodes are of two tube types, positive and negative poles are exactly opposite, which is convenient for wiring.

What is phenomenon when the rotating rectifier failure?
Rotating rectifier is usually composed of silicon rectifier elements. If one or several rotating silicon elements in the circuit are damaged, the damaged silicon element will lose one-way conductivity (both positive and negative conduction), resulting in a short circuit of the circuit. Once the rotating silicon element is short circuited, the generator has no output voltage when the unit is running. If the faults are not found and removed in time, the armature winding of the AC exciter will be burnt out and the generator will be forced to stop.

What cause the rotating rectifier failure?
1.The silicon rectifier diode of rotating rectifier is damaged due to over-voltage or over-current.
2.When the silicon rectifier element of the rotating rectifier is installed, the torsional moment is too large, which leads to the deformation of the tube shell and the damage of the internal silicon wafer.
3.The load power factor is too low, which causes the excitation current to exceed the rated current of silicon rectifying element for a long time and damages it.

How to deal with the problems?
1.Rotating silicon elements shall be provided according to the current level specified in the drawing. If there is no drawing data at hand, the standard silicon element can be relied on according to the excitation current value of the main generator. At present, the common specifications of rotating rectifiers produced in China are 16A, 25A, 40A, 70A and 200A.
2.The voltage level of the rotating silicon element shall be reasonably selected, and the reverse peak voltage urn of the rotating silicon element shall be 10-15 times of the excitation voltage UIN.

3.Tighten the nut of rotating silicon element with proper torque, and tighten the nut with constant torque wrench. The torque value of tightening the rotating silicon element nut shall be in accordance with the provisions shown in the manual which provided by the supplier.
4.Take over-voltage protection measures. Overvoltage protection is usually equipped with varistor or resistance capacitance absorption circuit on DC side of rotating rectifier.

Hope the article is helpful to you. Starlight Power manufacturer also supplies diesel generator set, cover Cummins, Volvo, Perkins, Deutz, Yuchai, Shangchai, Ricardo, Weichai, MTU, Doosan etc. Power range 20kw-3000kw. Welcome to contact us by email sales@dieselgeneratortech.com, we will work with you. 

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...