Components maintenance details of Cummins engine generator


1.Connecting rod of Cummins generator
A.If the copper sleeve of connecting rod is excessively worn, connecting rod must be sent to the repair shop with milling machine to replace it with a new copper sleeve (Cummins repair service center). When replacing the new copper sleeve, the piston pin and the new copper sleeve must be brought. The diameter of the copper sleeve of the processed connecting rod is N (50). 825-50. 838mm), K (60.985-61. 024mm). The difference between the diameter of piston pin and copper sleeve is 0. 05mm.
B.The connecting rod with connecting rod bush must be scrapped.
C.When assembling connecting rod screws, it is necessary to carefully check whether the connecting rod screws are elongated, cracked or damaged. Unqualified connecting rod screws and nuts must be replaced.
D.If enlarge connecting rod bush, it is recommended not to exceed two levels at most.
E.When installing the connecting rod screw, it is necessary to check whether the connecting rod screw slips twice according to the specifications. or the slipping connecting rod screw, it must be replaced and the specified torque must be reached several times.
F.When the connecting rod and piston assembly are installed on the crankshaft journal, attention must be paid to the installation of the connecting rod, otherwise serious accidents of bearing burn will occur.

Cummins generator set

2.Cylinder block of Cummins generator
A.The cylinder liner must be maintained with qualified flatness. If the stop surface is uneven, the cooling water of the cylinder body will flow out of the cylinder body from the stop. Some cylinder bodies are equipped with liner washers. When pressing the liner, the liner washers must be put into the stop.

B.When the main bearing burns, the main bearing pedestal will be deformed, even cracks will occur. The deformation of the main bearing pedestal can be sent to a professional repair company for repair and recovery, while the cracked cylinder body will be scrapped. For the cylinder block of high-power diesel engine, when installing the cover screws on both sides, the length must be checked carefully. Otherwise, the screw with too long length will easily collide with the balance weight of crankshaft and damage the cylinder block and crankshaft.
C.During the overhaul of the unit, it is necessary to clean the oil passage of the cylinder block and keep the oil passage clean.
D.For the piston cooling nozzle installed in the cylinder block during the intermediate overhaul of the unit, it is recommended to install or remove the piston and connecting rod assembly after removal to prevent the piston and connecting rod assembly from breaking the piston cooling nozzle. After the piston and connecting rod components are installed, install the piston cooling nozzle.

E.When installing the main bearing, pay attention to whether the installation of each main bearing is correct. And check whether the bearing bush locating ring is missing. The main bearing screws must be loosened after reaching the specified torque according to the specification, check whether the main bearing cover screws have sliding wire phenomenon. Replace the screws with sliding wire phenomenon and damaged screw thread.
F.For burnt crankshaft, after grinding, it is necessary to check the bending degree of crankshaft and whether there is crack in the shaft stiffness. Do not use the cracked crankshaft.

3.Follow-up arm mechanism of Cummins generator set
There may be pockmarks or peeling on the valve or injector roller to the follower arm. If so, the roller, roller shaft and roller pin must be replaced, or the diesel engine (driven by land generator set) will emit black smoke.
4.Oil pump of Cummins generator set
During the mid overhaul of the unit, the oil pump must be inspected. If the internal gear of the oil pump is excessively worn, the unqualified parts must be replaced or replaced as a whole.
5.Cummins generator set water pump
When the unit is in medium overhaul, the oil pump must be overhauled, and the water pump shall be overhauled with the water pump overhaul package or the water pump minor repair package. When installing the water seal, special installation tools must be used for installation, otherwise it is easy to damage the water seal.
6.Cummins generator set belt
When replacing the belt of fan, water pump and charger, if there is more than one belt of the same type for one machine, all the belts of the same type must be replaced.
7.Turbine Holset of Cummins generator set
A.The impeller of exhaust gas turbine shaft and compressor shall not be damaged, otherwise, the air intake of diesel engine will be insufficient, and black smoke will be set when the diesel engine is loaded.
B.In particular, when the valve seat, valve and piston are damaged, the debris is discharged to the impeller of the exhaust gas turbine shaft of the Holset turbocharger along with the exhaust gas, and the impeller is damaged.
C.If the oil ring installation groove of the exhaust gas turbine shaft is worn, the oil will leak to the exhaust gas impeller end, resulting in a sharp increase in oil consumption.
8.Intercooler of Cummins generator set
A.During the overhaul of Cummins diesel engine, the intercooler must be inspected and cleaned. If there is rust and scale on the surface of the intercooler, it means that the intercooler has water leakage fault, and the intercooler must be scrapped.
B.When cleaning the intercooler, if the material of the intercooler is aluminum alloy sheet, it can be cleaned with metal cleaner, Tianna water and diesel oil and dried; if the material of the intercooler is other material (such as Cummins K Series), it can only be cleaned with Tianna water and diesel oil. After cleaning, it must be noted that it is moisture-proof and rusty, and it is absolutely forbidden to use water to clean K series intercooler, Otherwise, the intercooler will be rusted and scrapped.

Maybe above maintenance regulations for Cummins diesel generator set is not completed, but we hope it is helpful to you. Starlight manufacturer also supplies diesel gensets, welcome to contact us by email sales@dieselgeneratortech.com.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...