The method to adjust oil supply of Cummins genset

 Today Starlight Power generator manufacturer tell you how to adjust fuel supply in Cummins diesel genset, hope it is helpful to you.

If the fuel supply of each cylinder of Cummins diesel generator set is not uniform (for example, the fuel supply of some cylinders is too large and that of some cylinders is too small), the stability of engine operation will be directly affected. The fuel injection pump can be removed to check and adjust on the test bench. However, if there is no test bed and it is necessary to check the uneven fuel supply, the fuel supply of the suspected cylinder can also be roughly checked. Inspection and adjustment method:

1.Prepare two glass measuring cylinders for use. If the measuring cylinder cannot be found for a while, two identical vials can be used instead.

2. Remove the high-pressure oil pipe joint between cylinder 1 with excessive fuel supply (or too small) and fuel injector.

3. Then remove the high-pressure pipe joint between cylinder 1 with normal fuel supply and fuel injector.

4. Insert the two tubing ends into two measuring cylinders (or vials) respectively.

5. Use the starter to turn the engine to make the fuel injection pump pump oil.

6. When there is a certain amount of diesel oil in the equivalent cylinder (or small bottle), put the measuring cylinder on the horizontal platform to compare the amount of oil, then we can determine whether the fuel supply is too large or too small. If a small bottle is used instead, it can be weighed and compared. The relative position of the fork (or ring gear) on the adjusting rod (gear rod) of the fuel injection pump can be adjusted. To P_ The pump can be adjusted by turning the flange sleeve.

 

During the operation of Cummins diesel generator set, the following points should be paid special attention to according to experience:

1.Loosen the fixed screw of fork (or gear ring, or flange sleeve). Only a small amount of movement is needed to change the oil supply quantity. Do not move too much, otherwise it is difficult to adjust accurately (if necessary, mark the initial position for easy comparison).

2.After each adjustment, the tightening degree of the set screw must be confirmed.

3. When adjusting the fuel supply, it should be ensured that the oil quantity is not higher than the standard oil supply. This is because the adjustment is carried out at low speed. Considering the influence of many factors such as oil leakage, a large nonuniformity (30%) is allowed at this time, but at high speed, due to the influence of throttling and other factors, the allowable unevenness is small (3%). If the fuel quantity at low speed is higher than the standard fuel supply, the high-speed fuel supply may have a large change, or even exceed the rated fuel supply.

4. If there is a big difference between the maximum fuel supply and the minimum fuel supply on the same engine, do not rush to adjust it. First, the outlet valves of the two pumps can be adjusted and installed to check and compare. Sometimes, the fuel supply can be changed by doing so. If there is no change in oil supply after the adjustment, the two pumps should be adjusted one by one.

5. The operation must be careful and careful when adjusting the fuel supply by comparison.

We are not only provide genset technical support, but also provide good quality 25kva-3000kva electric generators, contact us by email sales@dieselgeneratortech.com with your requirements, we will quote you according to your requirements. We believe we can give you high quality product and good service.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Silent Cummins 640kw Diesel Generating Sets

Technical data of 800KVA AC diesel generator set The DG Set is skid mounted, directly coupled with Cummins water cooled engine with built in shock absorber for anti vibration. The alternator is Stamford brand with brushless and self excited, with control panel and protection system complete set. Prime power: 640KW/800KVA Standby power:704KW/880KVA Rated voltage: 230/400V Rated current: 1152A Speed/frequency:1500rpm/50Hz ( or 1800rpm/60Hz) Power factory:0.8lag Size: open type genset: 4.2 x1.82x2.25m, silent genset: 6.5 x2.6 x2.78m Net wight: open type genset: 7800kg,   silent genset : 12000kg Technical Data of Diesel Engine Diesel engine brand/model: Chongqing Cummins/ KTA38-G2B( full new) Prime/standby power: 790KW/920KW 4 Stroke Cycle , 60° Vee , 12 Cylinder, Turbocharged &Aftercooled, 1500rpm, 50Hz, bore/stroke: 159/159mm. The Cummins diesel engine is equipped with electronic type governor, over speed shutdown devices to protect against runaway when electronic governor or con...

Guides to Clean VOLVO Diesel Generator Cooling System

VOLVO Engine Cooling System Volvo engine's internal cooling system makes sure the engine works at the right temperature. It is a closed system that must always be filled with a mixture of concentrated coolant and water in order to protect the engine against internal corrosion, cavitation and bursting due to freezing. Coolant of a suitable chemical composition must be used all year round. This also applies in areas where there is never any risk of freezing, to provide the engine of  diesel generator set   with full corrosion protection. The use of anti-corrosion agents alone is not permitted in Volvo Penta engines. Never use water alone as a substitute for coolant. The corrosion protection additives become less effective over time, which means that the coolant must be changed at regular intervals; refer to Maintenance Schedule. The cooling system must be flushed whenever the coolant is changed; Volvo Penta coolants have been prepared to work best ...