What Causes Blockage Faults in Perkins Generators

 Air blockage and elimination method
 
When the air bubbles from the oil outlet valve, it is judged that there is the air blockage fault in the engine fuel supply system, the starter can be continued to hit until the air in the pipeline is exhausted, indicating that the pipeline is not damaged and the engine can work normally.
 
If during hitting the starter, there is always air exhausted, indicating that there is a leak in the oil supply pipeline. The method of eliminating air blockage is to find the leak site, seal well to eliminate the leak, and then eliminate the air in the system. If the air in the oil supply pipeline is blocked by evaporation of fuel molecule into fuel vapor due to very hot weather and low air pressure, this is a special case. People call it high temperature air blockage, this is another case.


 
Foreign body blockage and elimination method
 
When check out there is no oil or less oil from the oil valve, foreign body blockage can be judged. Check the blockage parts, you can use the method of hand oil pump to continue to check, when pulling the handle of the hand oil pump feel great resistance, can focus on inspection of fuel supply pipeline from fuel tank to hand oil pump, the blockage may be at the inlet of the fuel pipe in the fuel tank, foreign matter in the fuel tank blocked the oil inlet, the blockage part maybe is fuel filter, impurities or colloids in the fuel block the filter
 
If the resistance is greater when pushing the hand oil pump, can focus on checking the oil supply pipeline from the hand oil pump to the high-pressure pump. The blockage may occur in the fine fuel filter.
 
The way to check whether the centrifugal oil filter is working properly is to monitor the "buzz" of the diesel engine when its rotor continues to rotate just after shutdown. If the sound is working normally for a long time, if the sound of rotation is not heard, indicating that the fault occurs.
 
When check ice blockage fault, it must be in Winter, maybe there is water in diesel oil. Common ice blockage fault part is in pipelines and fittings, the situation is more complex, warm pipeline, melting and freezing, if the pipeline is naturally open, it is not necessary to find the exact location of the ice blockage. After removing the foreign matter blockage, the fuel supply system should also be thoroughly cleaned, even the fuel tank should be cleaned. In order to prevent material resistance, attention should be paid to long-term injection of clean fuel oil in fuel tank.
 
Water blockage and elimination method
 
When the diesel engine is not stable enough, there is a fire phenomenon, even when the engine stops suddenly during operation, it can be judged that the diesel engine is blocked. Observing the exhaust pipe will find that the exhaust pipe continuously emits white smoke. When the exhaust pipe receives water droplets or drips more, the water blockage fault of the diesel engine can generally be judged.
 
Water blockage means that there is water in fuel supply system and fuel tank. If can sure water blockage fault, should release water and oil which in bottom, and the engine should be started continuously by the starter to see if the water blockage fault can be eliminated. If it can not be removed, all remaining fuel should be discharged, and the fuel tank and fuel supply system should be thoroughly cleaned, and the fuel filter (core) should be replaced. After that, should pay attention to the addition of clean and anhydrous fuel and the possibility of water entering the fuel system should be excluded. The performance of water blockage is complex, which should be distinguished from the difficult faults of diesel engines such as leakage of combustion chamber. For example, the damage of the cylinder gasket leaks into the combustion chamber, and the moisture is discharged from the exhaust pipe. The diesel engine also works unsteadily.
 
According to the degree of water leakage and the number of cylinders, the amount of drainage is different, and the working condition of diesel engine is also different. Therefore, it is necessary to apply experience and judge comprehensively according to many factors, such as engine operating time, common working conditions, medium consumption and so on.
 
Hope the article can help you to solve the leakage faults in Perkins diesel generator set. If you are interested in diesel generator set, welcome to contact us by email sales@dieselgeneratortech.com, we will guide you to select the most suitable product.

Comments

Popular posts from this blog

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz

Technical Parameters of Boduan 500KW Weichai Generator Set 6M33D572E200

  The 6M33D633E200 diesel engine is a special-purpose diesel engine for land-based power generation in the M33 series. It is a new-structure power generation diesel engine with a centrally - located turbocharger developed by Weichai Power Co., Ltd. in 2016. Continuous Power (COP): The maximum power at which the diesel engine can run continuously under a constant load with no limit on the annual operating hours. It is the ISO standard power. Prime Power (PRP): The maximum power at which the diesel engine can run continuously under variable loads with no limit on the annual operating hours. It is an ISO standard power that allows a 10% overload. Standby Power (ESP): The maximum power in a certain variable - power series that the diesel engine can operate for up to 200 hours per year. It is an ISO standard power with limited fuel consumption.   Operating Conditions and Applications of Baudouin  500KW Weichai Generator Set  Diesel Engine Power Classification Operating Co...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...