Generator Set Repair and Maintenance


6.1 General Provisions
Good maintenance and repair, the key of the long-term service life of the generator set, should be carried out by the qualified technical personnel. Good record shall be made in case of maintenance and repair, which will be helpful to arranging the working procedures of maintenance and repair in the future.

In general, the generator set shall be kept clean without liquids such as: fuel oil or lubricating oil piled up on any internal or external surfaces and on the surface of, under and around the sound absorption (if the device is available) materials. The industrial water solvent shall be used to clean the surface of the machine, but the flammable solvents can not be used for cleaning. For instance, the protection of the sound absorption material is torn down or penetrated, it should be replaced immediately so as to prevent the liquid or oils penetrated and accumulated on the material.

6.2 Preventative Maintenance
For the situations of the use of generator set is not the same, the requirements for maintenance are different. For

the detailed maintenance of the diesel engine, please refer to Manual for Diesel Engine. For it is associated with this chapter, the use shall read the relevant parts to practice by combining this chapter. The maintenance work can be performed more frequently than that according to the requirements of this chapter.

6.2.1 Daily maintenance and after-star-up maintenance per time: for the prepared generator set, these procedures can be performed once to visually check the surrounding area of the machine before start-up per time or day. The check before start-up specified in section 5.2 shall be performed here at the same time. For the check procedures of the diesel engine, please refer to Manual for Diesel Engine, in which the requirements can be seen the supplement of the section 5.2.

6.22 Check (referring to the reserve machines not always started) the machine every two weeks and start the machine to run for five minutes.

WARNING! Do remember not letting the diesel machine run under low load.

6.2.3 Check (referring to the reserve sets running without load increased) and start the machine to make run for five minutes and increase at least 50% load to run for 1-2 hours every month. 6.2.4 Check every 6 months or 250 hours:

1. Check the protective devices of the control system by adopting fault simulation method.
2. Clean the exhaust hole.
3. Tighten all connectors of the exhaust pipe
4. Tighten all connects of the electrical equipment.
5. Perform other special maintenance of the diesel machine listed in the Manual for Diesel Machine.

6. Observe all instruments on the control screen to see if the running is normal after starting the machine.
6.2.5 Preventative maintenance of alternator: its not necessary to perform daily maintenance of the alternator but it is required to check and clean the coil of the alternator regularly. Please to refer to the maintenance of alternator and Alternator Manual specified in section 8.2.

6.2.6 Preventative maintenance of alternator: in line with the requirements provided by the Manual for Diesel Engine, read this manual and perform frequent maintenance to maintain its highly efficient performance.

6.3 Dismantlement of Generator and Alternator
Dismantlement of diesel engine or alternator shall be started according to the following procedures:

1. Dismantle the circuit from power supply to the auxiliary equipment (such as: hot water jacket). 2. Disconnect the circuit for battery charging and battery wire (firstly dismantle the cathode), and move battery if necessary.
3. Provided that the generator has cap, then it is necessary to loosen the bolts fixed at each side of the cap, dismantle the exhaust pipe, and then move the cap away.
4. When dismantling the control screen, its necessary to dismantle all lines & bearers and fully ensure all the lines can be connected again.
5. If the diesel engine and alternator are dismantled, the rings of the diesel engine and alternator can be used to life them independently. But the bolts fixed at their chassis initially.

6.3.1 Only Dismantle Diesel Engine

1. In case of only dismantling the diesel engine, the hose pipe of the circuit on the diesel engine shall be dismantled initially.
2. Provided that the only foot of alternator is at the chassis, the front end of the alternator shall be stationed well by using the bearer when dismantling the diesel engine.
3. Removing the chassis bolt on the diesel engine and loosening the fixed bolt of the alternator might be helpful to dismantling diesel engine.
4. Remove the protection cover of the fan of alternator.
5. Use lifting hook or wooden bearer to hold it up, be careful and dont destroy fan blade.
6. Dismantle the diesel engine and alternator
7. Use the elevated crane or similar devices to lift it at the end of the diesel engine.
8. Dismantle the bolt of joint shell.
9. Now, move the generator forward until it is completely separated from alternator and the chassis can be lifted away.

Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...